S&C Instruction Sheet 466-500    3

Introduction

The VacuFuse II Self-Resetting Interrupter, selected for a specific application, should have a 
maximum voltage rating equal to or greater than system line-to-line voltage when used in phase-
to-phase applications. The VacuFuse II Self-Resetting Interrupter can be applied on the primary 
side of 7.2-kV overhead distribution transformers up to 150 kVA and on 15-kV transformers up to 
250 kVA when mounted in a 110 or 125/150 kV-BIL cutout mounting. To ensure proper performance, 
VacuFuse II interrupters must only be installed in present-production (“-R10” or “-R11”) S&C-provided 
cutout mountings. See the example in Figure 1. An example of an earlier-production S&C cutout 
mounting is shown in Figure 2.

Figure 1. A present-production (“-R10” or 

“-R11”) S&C-provided Type XS Fuse Cutout 

mounting.

Figure 2. An earlier-production (“-R9”) S&C 

Type XS Fuse Cutout mounting. “-R8” and 

earlier versions have a similar upper contact.

Содержание VacuFuse II

Страница 1: ...5 Location of Safety Labels 6 Safety Precautions 7 Shipping and Handling Inspection 8 Packing 8 Handling 8 Storage 8 Returning 8 Installation Before Starting 9 Installing a VacuFuse II Interrupter in...

Страница 2: ...alified persons They are not intended to be a substitute for adequate training and experience in safety procedures for this type of equipment Read this Instruction Sheet NOTICE Thoroughly and carefull...

Страница 3: ...nsformers up to 150 kVA and on 15 kV transformers up to 250 kVA when mounted in a 110 or 125 150 kV BIL cutout mounting To ensure proper performance VacuFuse II interrupters must only be installed in...

Страница 4: ...p out in response to a fault Warranty The warranty and or obligations described in S C s Price Sheet 150 Standard Conditions of Sale Immediate Purchasers in the United States or Price Sheet 153 Standa...

Страница 5: ...rtant procedures or requirements that can result in product or property damage if instructions are not followed Following Safety Instructions If you do not understand any portion of this instruction s...

Страница 6: ...e Description Part Number A WARNING A VacuFuse II Self Resetting Interrupter must be dropped out from the cutout mounting to be considered OPEN and de energized Device may be energized from either sid...

Страница 7: ...remove or obscure any of the DANGER WARNING CAUTION or NOTICE labels and tags Remove tags ONLY if instructed to do so 5 ENERGIZED COMPONENTS Always consider all parts live until de energized tested a...

Страница 8: ...ardware for securing the VacuFuse II Self Resetting Interrupter to the pole Handling NOTICE DO NOT DROP the VacuFuse II Self Resetting Interrupter or subject any of its parts to undue stress during in...

Страница 9: ...h the parts of the VacuFuse II Self Resetting Interrupter See Figure 3 Figure 3 An overview of the VacuFuse II Self Resetting Interrupter POSITION indicator CHARGING LED OPEN CLOSE lever Hinge end con...

Страница 10: ...into a damaged cutout mounting If installing in a new S C Cutout Mounting For overhead pole top style VacuFuse II Self Resetting Interrupters attach the mounting to its mounting bracket as illus trat...

Страница 11: ...on on page 15 for more information Place the OPEN CLOSE lever in the correct position for the closing sequence desired See the Understanding the Closing Sequence section on page 12 STEP 2 Stand firmly...

Страница 12: ...ays to close the vacuum interrupter Option 1 Automatic Delay Close Place the OPEN CLOSE lever into the Closed up position at any time before or after mounting the unit into the cutout mounting When cl...

Страница 13: ...the POSITION indicator will show a green target If the over current event persists after the reclosing event the unit will lock out and drop out from the cutout mounting Follow these steps if the Vacu...

Страница 14: ...s out If required by utilitypractice followthestepsinthe Removing the VacuFuse II Interrupter from the Cutout Mounting section starting on page 18 This creates a visible open gap showing the transform...

Страница 15: ...rupter to power the control from its Sleep state When powered the control will remain powered if the transformer primary current does not fall below 3 5 amperes If less than 3 5 amperes of primary cur...

Страница 16: ...use II Interrupter WARNING The VacuFuse II Self Resetting Interrupter is designed to protect distribution transformers from internal and external fault current A VacuFuse II interrupter found in the O...

Страница 17: ...pter will trip open independently of any force still applied to OPEN CLOSE lever To Reset the OPEN CLOSE Lever Af ter Manually Closing into Fault Current When the VacuFuse II interrupter trips in resp...

Страница 18: ...r displays a green target STEP 2 Wait one minute until the VacuFuse II Self Resetting Interrupter drops out If the VacuFuse II Self Resetting Interrupter stays in its cutout mounting confirm the POSIT...

Страница 19: ...its cutout mounting using Loadbuster The S C Loadbreak Tool Then re install the VacuFuse II interrupter as described in the Installation section starting on page 9 If there is no voltage present in t...

Страница 20: ...utout position A swift firm pull will be required Situation 3 The VacuFuse II Self Resetting Interrupter is stuck in the cutout mounting in Abnormal mode Situation 3 Action Check for voltage presence...

Страница 21: ...tool to an S C Universal Pole not less than 6 feet 183 cm long 8 feet 244 cm for catalog number 5400R3 with the frame of the tool in line with the pole As shown inFigures14and15 theLoadbustertoolmust...

Страница 22: ...ended to its maximum length A downward pull to open the VacuFuse II Self Resetting Interrupter extends the Loadbuster tool and charges the tool s internal spring At a predetermined point in the openin...

Страница 23: ...isting the pole after the Loadbuster tool has been tripped and fully extended To perform this operation smoothly always roll the Loadbuster tool so that it rotates in an upward direction STEP 7 To res...