S&C Instruction Sheet 466-500    17

OPEN/CLOSE lever

Figure 12. Operating the OPEN/CLOSE lever into the 

Closed position.

To Open: 

Pull the yellow OPEN/CLOSE lever down 

firmly using the straight prong of the Talon tool or a dis-
tribution prong. Remove the tool right away. The vacuum 
interrupter inside the VacuFuse II interrupter will open, 
and the POSITION indicator will show the green target. 
After one minute of the vacuum interrupter in the 

Open

 

position, the unit will drop out. See Figure 11. 

To Close: 

Push the pull-ring of the yellow OPEN/CLOSE 

lever up firmly using the straight prong of the Talon tool 
or a distribution prong. The vacuum interrupter inside the 
VacuFuse II interrupter will close after 45 seconds of the 
unit being powered, and the POSITION indicator will show 
the red target. See Figure 12. If the VacuFuse II interrupter 
is inadvertently closed into a fault, the vacuum interrupter 
will trip open independently of any force still applied to 
OPEN/CLOSE lever.

To R e set th e OPEN / CL O SE L ever Af ter 

Manually Closing into Fault Current:

 When the 

VacuFuse II interrupter trips in response to a fault, 
the lever does not move, leaving the lever in the  

Closed

 position when the vacuum interrupter is in the 

Open

 position. The lever can be “reset” by operating it into 

the 

Open

 position while the vacuum interrupter is in the 

Open

 position. When the lever is in the 

Closed

 position, 

the interrupter will automatically close the next time it is 
pushed into the cutout mounting and synchronize itself.

Note:

 After a permanent fault occurs, it is necessary to 

wait at least 20 seconds before closing the interrupter into 
the cutout mounting again. If the interrupter is closed into 
the cutout mounting immediately after a permanent fault, 
it will drop-out without closing. This happens due to the 
interrupter interpreting that it never dropped-out from the 
cutout mounting after the permanent fault.

Operation

Figure 11. Operating the OPEN/CLOSE lever into the Open 

position. 

OPEN/CLOSE lever

Содержание VacuFuse II

Страница 1: ...5 Location of Safety Labels 6 Safety Precautions 7 Shipping and Handling Inspection 8 Packing 8 Handling 8 Storage 8 Returning 8 Installation Before Starting 9 Installing a VacuFuse II Interrupter in...

Страница 2: ...alified persons They are not intended to be a substitute for adequate training and experience in safety procedures for this type of equipment Read this Instruction Sheet NOTICE Thoroughly and carefull...

Страница 3: ...nsformers up to 150 kVA and on 15 kV transformers up to 250 kVA when mounted in a 110 or 125 150 kV BIL cutout mounting To ensure proper performance VacuFuse II interrupters must only be installed in...

Страница 4: ...p out in response to a fault Warranty The warranty and or obligations described in S C s Price Sheet 150 Standard Conditions of Sale Immediate Purchasers in the United States or Price Sheet 153 Standa...

Страница 5: ...rtant procedures or requirements that can result in product or property damage if instructions are not followed Following Safety Instructions If you do not understand any portion of this instruction s...

Страница 6: ...e Description Part Number A WARNING A VacuFuse II Self Resetting Interrupter must be dropped out from the cutout mounting to be considered OPEN and de energized Device may be energized from either sid...

Страница 7: ...remove or obscure any of the DANGER WARNING CAUTION or NOTICE labels and tags Remove tags ONLY if instructed to do so 5 ENERGIZED COMPONENTS Always consider all parts live until de energized tested a...

Страница 8: ...ardware for securing the VacuFuse II Self Resetting Interrupter to the pole Handling NOTICE DO NOT DROP the VacuFuse II Self Resetting Interrupter or subject any of its parts to undue stress during in...

Страница 9: ...h the parts of the VacuFuse II Self Resetting Interrupter See Figure 3 Figure 3 An overview of the VacuFuse II Self Resetting Interrupter POSITION indicator CHARGING LED OPEN CLOSE lever Hinge end con...

Страница 10: ...into a damaged cutout mounting If installing in a new S C Cutout Mounting For overhead pole top style VacuFuse II Self Resetting Interrupters attach the mounting to its mounting bracket as illus trat...

Страница 11: ...on on page 15 for more information Place the OPEN CLOSE lever in the correct position for the closing sequence desired See the Understanding the Closing Sequence section on page 12 STEP 2 Stand firmly...

Страница 12: ...ays to close the vacuum interrupter Option 1 Automatic Delay Close Place the OPEN CLOSE lever into the Closed up position at any time before or after mounting the unit into the cutout mounting When cl...

Страница 13: ...the POSITION indicator will show a green target If the over current event persists after the reclosing event the unit will lock out and drop out from the cutout mounting Follow these steps if the Vacu...

Страница 14: ...s out If required by utilitypractice followthestepsinthe Removing the VacuFuse II Interrupter from the Cutout Mounting section starting on page 18 This creates a visible open gap showing the transform...

Страница 15: ...rupter to power the control from its Sleep state When powered the control will remain powered if the transformer primary current does not fall below 3 5 amperes If less than 3 5 amperes of primary cur...

Страница 16: ...use II Interrupter WARNING The VacuFuse II Self Resetting Interrupter is designed to protect distribution transformers from internal and external fault current A VacuFuse II interrupter found in the O...

Страница 17: ...pter will trip open independently of any force still applied to OPEN CLOSE lever To Reset the OPEN CLOSE Lever Af ter Manually Closing into Fault Current When the VacuFuse II interrupter trips in resp...

Страница 18: ...r displays a green target STEP 2 Wait one minute until the VacuFuse II Self Resetting Interrupter drops out If the VacuFuse II Self Resetting Interrupter stays in its cutout mounting confirm the POSIT...

Страница 19: ...its cutout mounting using Loadbuster The S C Loadbreak Tool Then re install the VacuFuse II interrupter as described in the Installation section starting on page 9 If there is no voltage present in t...

Страница 20: ...utout position A swift firm pull will be required Situation 3 The VacuFuse II Self Resetting Interrupter is stuck in the cutout mounting in Abnormal mode Situation 3 Action Check for voltage presence...

Страница 21: ...tool to an S C Universal Pole not less than 6 feet 183 cm long 8 feet 244 cm for catalog number 5400R3 with the frame of the tool in line with the pole As shown inFigures14and15 theLoadbustertoolmust...

Страница 22: ...ended to its maximum length A downward pull to open the VacuFuse II Self Resetting Interrupter extends the Loadbuster tool and charges the tool s internal spring At a predetermined point in the openin...

Страница 23: ...isting the pole after the Loadbuster tool has been tripped and fully extended To perform this operation smoothly always roll the Loadbuster tool so that it rotates in an upward direction STEP 7 To res...

Отзывы: