S&C TA-3370 Скачать руководство пользователя страница 29

S&C Instruction Sheet 661-500    29

Appendix B

Table 9. J3 Connector Input Definitions

Upper Row

Pin Number

Connection Name

Description

1

PHASE 1 VOLTAGE SENSOR NEUTRAL

Phase 1 input current return from S&C voltage sensor

2

PHASE 1 VOLTAGE SENSOR LINE

Phase 1 input current from S&C voltage sensor

3

PHASE 3 VOLTAGE SENSOR NEUTRAL

Phase 3 input current return from S&C voltage sensor

4

PHASE 3 VOLTAGE SENSOR LINE

Phase 3 input current from S&C voltage sensor

5

PHASE 2 VOLTAGE SENSOR NEUTRAL

Phase 2 input current return from S&C voltage sensor

6

PHASE 2 VOLTAGE SENSOR LINE

Phase 2 input current from S&C voltage sensor

7

NO CONNECTION

8

AC INPUT NEUTRAL

Single-phase 120-Vac input connection

9

AC INPUT LINE

10

EARTH GROUND

Lower Row

Pin Number

Connection Name

Description

11

(+24) VDC OUTPUT

Positive supply to RTU

12

(+24) VDC OUTPUT

13

(+24) VDC OUTPUT

14

OVER VOLTAGE INDICATOR NO 1

Relay dry contacts for battery 

Over Voltage condition indicator . The relay will 

turn on when the battery voltage is over 34 V . The battery will be disconnected 

from the charger . The relay will be latched until conditions are cleared .

15

OVER VOLTAGE INDICATOR COMMON 1

16

OVER VOLTAGE INDICATOR NC 1

17

OVER VOLTAGE INDICATOR NO 2

Relay dry contacts for battery 

Over Voltage condition indicator . The relay will 

turn on when the battery voltage is over 34 V . The battery will be disconnected 

from the charger . The relay will be latched until conditions are cleared .

18

OVER VOLTAGE INDICATOR COMMON 2

19

OVER VOLTAGE INDICATOR NC 2

20

(+)24 VDC OUTPUT

Positive supply to RTU

Table 10. J4 Connector Input Definitions

Upper Row

Pin Number

Connection Name

Description

1

UNDER VOLTAGE INDICATOR COMMON 1

Relay dry contacts for 

Battery Under Voltage condition indicator . The relay will 

turn on when the battery voltage is below 23 V when an ac source is present 

and 22 V when an ac source is not present . The relay will be latched until 

conditions are cleared .

2

UNDER VOLTAGE INDICATOR NO 1

3

UNDER VOLTAGE INDICATOR NC 1

4

BAT CHECK INDICATOR COMMON 2

Relay dry contacts for 

Battery Test indicator . The relay will turn on during the 

battery test and turn off when the battery test is complete .

5

BAT CHECK INDICATOR NC 2

6

BAT CHECK INDICATOR NO 2

7

BAT CHECK INDICATOR NO 1

Relay dry contacts for 

Battery Test indicator . The relay will turn on during the 

battery test and turn off when the battery test is complete .

8

BAT CHECK INDICATOR NC 1

9

BAT CHECK INDICATOR COMMON 1

10

OC INDICATOR NO 1

See details on pin 19 and 20

Lower Row

Pin Number

Connection Name

Description

11

UNDER VOLTAGE INDICATOR NO 2

Relay dry contacts for 

Battery Under Voltage condition indicator . Relay will 

turn on when the battery voltage is below 23 V when an ac source is present 

and 22 V when an ac source is not present . The relay will be latched until 

conditions are cleared .

12

UNDER VOLTAGE INDICATOR NC 2

13

UNDER VOLTAGE INDICATOR COMMON 2

14

(+)24 VDC OUTPUT

Positive supply to RTU

15

(-)24 VDC OUTPUT

Negative supply to RTU

16

AC INDICATOR COMMON 2

Relay dry contacts for an ac source being present . The relay will turn on when 

there is no ac source (either 120 Vac or three-phase current source) supplying 

the  charger . The relay will be latched until conditions are cleared .

17

AC INDICATOR NC 2

18

AC INDICATOR NO 2

19

OC INDICATOR COMMON 1

Relay dry contacts for 

Open Cell or Battery Not Connected condition 

indicator . Relay will turn on when there is no battery connected to charger or if 

a battery has open cell(s) . The relay will be latched until the alarm is reset .

20

OC INDICATOR NC 1

Содержание TA-3370

Страница 1: ...tings and Standards 6 Components Overview 7 Wiring Interface 9 LCD Screen 10 Operation Accessing the GUI Application Software 11 Navigating the GUI Application Software 12 Power Switch Operation and C...

Страница 2: ...whenever Three Phase Battery Charger is to be used Retain this instruction sheet in a location where you can easily retrieve and refer to this publication Proper Application WARNING The equipment in...

Страница 3: ...precautions are not followed NOTICE NOTICE identifies important procedures or requirements that can result in product or property damage if instructions are not followed Following Safety Instructions...

Страница 4: ...eing performed inside the enclosure Mini Rupter Switches have switch operating shaft access covers located on the sides of the pad mounted gear enclosure They must be closed and padlocked at all times...

Страница 5: ...and tested for voltage install suitable grounding cables in all compartments before touching any device to be inspected replaced serviced or repaired in the high voltage compartments 13 SWITCH POSITIO...

Страница 6: ...85 C 40 F to 185 F Relative humidity 5 to 95 at 60 C 140 F non condensing Regulatory Compliance The Three Phase Battery Charger complies to the following standards Emissions Testing IEC 60255 26 2013...

Страница 7: ...raphical user interface GUI computer application software to monitor the gear Table 4 on page 8 provides the description of the components J4 connector pinout label J2 connector pinout label J3 connec...

Страница 8: ...hows the pin locations to connect the output wires J3 connector pinout label Drawing label Shows the pin locations to connect the power wires J4 connector pinout label Drawing label Shows the pin loca...

Страница 9: ...flathead screwdriver unscrew the pin location needed to wire See Figure 3 STEP 2 When the pin screw is loosened place the bare part of the wire in the square slot under the loosened screw and tighten...

Страница 10: ...the LCD screen are also cleared if the charger is turned off and then turned back on This information will automatically scroll on the LCD screen every three seconds Display on the screen when the cha...

Страница 11: ...harger and the USB end to the user s computer STEP 2 Run the BatteryCharger exe file from the computer to launch the GUI application NOTICE The GUI application software BatteryCharger exe file can be...

Страница 12: ...tab is the default screen when the user logs in and is used for updating the charger firmware See Figure 7 Table 5 defines the fields and buttons in the Firmware Upload screen Table 5 Firmware Upload...

Страница 13: ...to be refreshed to capture present data Click on the Battery Status tab to refresh The two buttons the user can use are Convert to C This button enables the user to convert the temperature seen on the...

Страница 14: ...000 to 500 amperes A readback of this value is displayed on the Battery Status screen under the User Set Max Current field Date Time The user can configure the date and time By placing the cursor on t...

Страница 15: ...ty and can be started remotely with the GUI application Battery Test command as shown in Figure 11 by the Battery Test Start input relay through the J2 connector or by the BAT TEST pushbutton on the c...

Страница 16: ...n the Test History button This will enable the user to see the subtab report NOTICE If the data does not appear click on the Test History button again to refresh the data STEP 3 If desired the user ca...

Страница 17: ...is turned on turn on the CHARGER POWER switch The LCD screen will turn on and the charger will power on NOTICE If the charger has a battery connection a 120 Vac single phase power source connection an...

Страница 18: ...minate the wires STEP 3 Connect the two pin connector See Figure 17 Before turning on the charger use a voltmeter to confirm the voltage at the J2 connector Voltage across pin 1 battery positive and p...

Страница 19: ...rs on the GUI application software STEP 4 To place a new battery or to rewire the existing battery to the charger follow Steps 2 through 4 of the previous section on page 18 STEP 5 Using the Battery S...

Страница 20: ...wire to pin 1 and battery negative wire to pin 4 of the J2 connector See the J2 connector pinout label on the charger faceplate for exact pin locations to terminate the wires Now connect the two pin c...

Страница 21: ...head screwdriver to secure the 24 Vdc battery to the charger by connecting the battery positive lead to pin 1 and the battery negative lead to pin 4 on the J2 connector Now connect the two pin connect...

Страница 22: ...s no 120 Vac single phase power source connected to the charger the charger will be powered by the three phase power source If there is a 120 Vac single phase power source connected to the charger the...

Страница 23: ...t If these actions do not resolve the issue contact S C Electric Company BAT LOW appears on the LCD screen or in the GUI application Battery voltage is less than 22 Vdc during a battery test Troublesh...

Страница 24: ...urrent date and time via the LCD screen NOTICE S C recommends using the Settings tab in the GUI application software to configure the battery charger See page 14 for configuration instructions Complet...

Страница 25: ...CE The UP button increases the value of the digit by 1 At the maximum value 12 for month the next push rolls over to the minimum value 1 for month Certain digit positions within the configurable value...

Страница 26: ...STEP 3 To select another position push the DOWN pushbutton which will move the flashing position to the right Push it again to go to another position to change its value STEP 4 When the desired value...

Страница 27: ...Battery status Date Time Temperature VL voltage under load BZ battery impedance NOTICE The battery test results on the LCD screen will be overwritten by the results of subsequent battery tests The bat...

Страница 28: ...o RTU 6 BAT TEST START INPUT Apply external 24 Vdc positive to pin 6 and negative to pin 7 for 3 seconds to start the battery test 7 BAT TEST START INPUT 8 ALARM RESET Apply external 24 Vdc positive t...

Страница 29: ...ON 1 Relay dry contacts for Battery Under Voltage condition indicator The relay will turn on when the battery voltage is below 23 V when an ac source is present and 22 V when an ac source is not prese...

Страница 30: ...t for 10 seconds Using a voltmeter measure the voltage Vac at the J2 connector and record the measurements in the Table 13 Table 13 Analog Output Voltage Analog Output Voltage Phase 1 J2 20 to J2 17 P...