9
1011-530
to 7 series groups per phase (interpolate between the curves for
S
= 6 and
S
= 8). Here,
V
n
= 0.0043 per unit.
Similarly, for
F
= 2, enter the graph at 16.67 on the horizontal scale. Follow this up to a
point corresponding to 7 series groups per phase. Here,
V
n
= 0.0093 per unit.
To convert
V
n
to an actual voltage, multiply by the system voltage
V
L-n
:
For
F
= 1,
For
F
= 2,
To determine the lockout level, calculate the midpoint value between
V
n
for
F
= 1 and
V
n
for
F
= 2 (=
F
c
):
Thus, the desired lockout level for this capacitor bank is 949 volts.
Formula Method
To calculate the lockout level for the capacitor bank:
A.
Calculate
V
o
for a series of steps corresponding to increasing values of
F
(up to and
including
F
c
) using the following formulas:
B.
For each value of
F
used in Step A, calculate
V
n
:
C.
Determine the desired lockout level: the midpoint between the
V
n
(actual voltage) for the
critical step
F
c
and the
V
n
(actual voltage) for
F
c-1
.
Formula Method – Example 1
An installation has the following profile:
•
Highest anticipated continuous system line-to-neutral voltage (
V
L-n
): 20 kV
•
Nameplate rating of the capacitor units (
V
r
): 9.96 kV
•
Number of series groups per phase (
S
): 2
•
Number of capacitor units in parallel per series group (
P
): 10
V
n
0.0043
139440 volts
×
600 volts
=
=
V
n
0.0093
139440 volts
×
1297 volts
=
=
600 volts
1297 volts
+
2
------------------------------------------------------
949 volts
=
V
o
(volts)
3
P
(
)
V
L
n
–
2
F
3
S
(
)
P
F
–
(
)
+
-------------------------------------------
=
V
o
(per unit)
V
o
(volts)
V
r
------------------------
=
V
n
(volts)
F
( )
V
L
n
–
2
F
3
S
(
)
P
F
–
(
)
+
-------------------------------------------
=