TY-JS-211220-00

13 

3.Alarm function 

(1) Alarm display: 
When alarm occurs, the error code and the temperature will be alternately displayed. 
(2) To suspend the alarm: 

In alarming state, the alarm sound could be suspended by pressing any button, but 

the alarm display remains until the alarm condition is eliminated. 

4. General settings adjustment

 

Press  SET  key  to  enter  into  the  user-defined  state.  Meanwhile,  PARAM  SET  is  on, 
controller in parameters setup status.   
(1).Under intelligent mode, the control panel displays the difference value between water 
temperature and room temperature(default value is -2). 
(2).Under  constant  temperature  mode

the  control  panel  displays  the  set  water 

temperature value (default value is 25). 

At this moment, press 

keys to change settings. After modifying the value, press 

RST  key  to  save  and  exit,  then  new  parameters  take  effect.  If  there  is  no  more  action 
within 20 seconds, it will automatically exit modifying status without saving parameters. 

5. Advanced settings adjustment 

(1)  Press  and  hold  the

key  while  press SET  key  for  5  seconds  until  00  displayed in 

upper  window  and  PAS  in  lower  window.  Then  press 

keys  to  select  the 

password (default setting is 8), and then press the SET key, if the password is correct, F0 
is  displayed,  entering  into  setup  status  and  indicating  that  the  controller  is  under 
parameters setup status. If the password is incorrect, it returns to temperature display.   

(2) Enter setup state, press

keys to switch parameter items circularly, then press   

keys  to  modify  the  parameter  values.  Press  enter  key  RST  at  any  time  to  exit 

parameters  setup  with  saving  modified  parameters  and  return  to  temperature  display, 
then chiller runs under the new parameters. If no key is pressed within 20 seconds, the 
controller will automatically exit parameters setup without saving the modified parameters 
(under  parameters  setup  status,  system  running  in  original  parameters).  Under 
parameters setup status, SET key does not work. 
Note: 
1.During parameters setting condition, system runs under original parameters. 
2.Under  constant  temperature  control  mode,  the  water  temperature  is  controlled  by 

parameter F0. 

3.Under intelligent control mode, the water temperature will be automatically adjusted as 

the room temperature changes. The temperature difference is commanded by F1. 

 

 

E1 

E2 

E3 

E4 

E5 

E6 

E7 

Ultrahigh 

room 

temperature 

Ultrahigh 

water 

temperature 

Ultralow 

water 

temperature 

Room 

temperature 

sensor 

failure 

Water 

temperature 

sensor 

failure 

External 

alarm 

input 

Water flow 

alarm 

input 

Содержание CWFL-500

Страница 1: ...TY JS 211220 009 1 CWFL 500 1000 1500 2000 3000 Industrial Chiller User Manual...

Страница 2: ...rly so that you can refer to it whenever you need information This manual is not a quality guarantee Our company reserves the right to the interpretation of the correction of misprint and improperly d...

Страница 3: ...e 4 I Overview 7 II Model Illustration 7 III Product Outlines Parts 8 IV Installation 9 V Operating States Parameters Adjustment 13 VI Alarm Output Terminal 15 VII Maintenance 16 VIII Simple Troublesh...

Страница 4: ...on a The power supply must conform to the standard indicated in the nameplate or the manual b Use the standard cable and select the standard wire diameter c The grounding wire must be installed and th...

Страница 5: ...nesthesia and suffocation if a large amount of refrigerant fills the enclosed space b Avoid contacting with skin or it will cause frostbite DANGER Failure to take safety measures will result in minor...

Страница 6: ...it is blocked the cooling ability will decrease and the power consumption will increase and the alarm will not work properly Equipment surface cleaning a Please use cleaning agents that are non corro...

Страница 7: ...hiller the refrigerant in the evaporator coil absorbs the heat of the return water and vaporizes into steam The compressor continuously extracts the generated steam from the evaporator and compresses...

Страница 8: ...ly different in different models Power Switch Temperature Controller laser head circuit Temperature Controller laser circuit Water Pressure Gauge Air Inlet Filter Gauze Water Supply Inlet Electrical C...

Страница 9: ...dust high temperature and humidity strong magnetic field direct sunlight etc 4 Operating Environment Ambient Temperature Ambient Humidity Altitude 0 45 90 RH 3 000m 5 Medium Requirements Cooling medi...

Страница 10: ...sor and other components according to different conditions the time is range from seconds to minutes so do not turn off the power and again on frequently 6 Electrical connection 1 Please select the ca...

Страница 11: ...n the air exhaust plug of the water pump do not unscrew and air is discharged until water flows out and then tighten the air exhaust plug See below diagram only the exhaust position of the horizontal...

Страница 12: ...working Heating ON heating rod working INT Ctrl ON controller working in intelligent control mode CT Ctrl ON controller working in constant temperature control mode PARAM Set ON controller working in...

Страница 13: ...d default setting is 8 and then press the SET key if the password is correct F0 is displayed entering into setup status and indicating that the controller is under parameters setup status If the passw...

Страница 14: ...erature is 3 lower than room temperature When room temperature remains the water temperature fluctuation shall not exceed 0 5 There will be an alarm when water temperature is 15 lower or higher than t...

Страница 15: ...voltage should be smaller than 300V Display Condition Alarm code Buzzer OUT H1 H2 OUT H1 H3 Circulating pump works properly DISCONNECTION BREAKOVER Ultrahigh room temp E1 Sounds BREAKOVER DISCONNECTI...

Страница 16: ...is shut down for a long time 1 Remove Dust Regularly Regularly disassemble the filter gauze for cleaning and use a compressed air gun to blow away the dust on the condenser about 1 week is suggested...

Страница 17: ...culation pipe Ultrahigh water temperature alarm temperature controller displays E2 Blocked dust gauze bad thermolysis Disassemble and clean the dust gauze regularly Poor ventilation for air outlet and...

Страница 18: ...TY JS 211220 009 18 Attachment Schematic CWFL 500 1000...

Страница 19: ...TY JS 211220 009 19 CWFL 1500 2000...

Страница 20: ...TY JS 211220 009 20 CWFL 3000...