CW-6000/6100/6200 Series
7
(4). RST key: confirm
(5). SET key: setting function
2. Restore to factory settings
Before machine startup, press and hold
keys until the controller
displays rE, 6 seconds later after releasing the keys, the controller works in
normal order. All parameters values settings of the controller have been
restored to factory settings.
3.
Alarm function
(1) Alarm Display:
When alarm occurs, the error code and the temperature will be alternately
displayed.
E1
E2
E3
E4
E5
E6
Ultrahigh
room
temperature
Ultrahigh
water
temperature
Ultralow
water
temperature
Room
temperature
sensor failure
Water
temperature
sensor failure
External
alarm input
(2) To suspend the alarm:
In alarming state, the alarm sound could be suspended by pressing any button,
but the alarm display remains until the alarm condition is eliminated.
4. Temperature controller parameters list
Order
Code
Item
Range
T-506
Temperature
controller
Factory Setting
T-506H
Temperature
controller
Factory Setting
Note
1
F0
Temperature
setting
F9~F8
30
25
Constant
temperature
control effecting
2
F1
Temperature
Difference values
-15~+5
-2
-2
Intelligent control
effecting
3
F2
Cooling
hysteresis
0.1~3.0
0.3
0.3
4
F3
Way of control
0~1
1
0
1: intelligent
0: constant
temperature
5
F4
Alarm for ultrahigh
water temperature
1~20
10
10
6
F5
Alarm for ultralow
water temperature
1~20
15
15
7
F6
Alarm for ultrahigh
room temperature
40~50
45
45
8
F7
Password
00~99
8
8
9
F8
The allowed highest
water temperature
(
F9+1
)
~40
35
30
10
F9
The allowed lowest
water temperature
1 ~
(
F8-1
)
20
20
Содержание CW-6000AN250S01
Страница 1: ...CW 6000 6100 6200 DUAL TEMPERATURE INDUSTRIAL CHILLER USER MANUAL...
Страница 15: ...CW 6000 6100 6200 Series 15 CW 6000 6100 6200...
Страница 16: ...CW 6000 6100 6200 Series 16 17 18 19 20 23 24 25 28...
Страница 17: ...CW 6000 6100 6200 Series 17 1 2 200 250V 110V 100 130V 3 50Hz 60Hz 4 NORMAL NORMAL 5 50cm 30cm 6 7 8...
Страница 18: ...CW 6000 6100 6200 Series 18...
Страница 19: ...CW 6000 6100 6200 Series 19 1 2 3 4 1 2 3 4 5 6 CW 6000 6100 6200 20...
Страница 22: ...CW 6000 6100 6200 Series 22 5 SET PARAM Set 1 2 2 25 RST 20 6 1 SET 00 PAS 8 SET F0 2 RST 20 SET 1 2 F0 3 F1...
Страница 24: ...CW 6000 6100 6200 Series 24 CW 6000 6100 6200 1 2 H1 H2 H1 H3 E6 E6 E6 E1 E2 E3 E4 E5 5A 300V...
Страница 28: ...CW 6000 6100 6200 Series 28 E6 E6 E2 E1 40...