CW-6000/6100/6200 Series
10
<6> Flow alarm and output ports
In order to guarantee the equipment will not be damaged while cooling water
circulation is out of control, CW-6000/CW-6100 dual temperature series chiller
possesses a low flow alarm protection.
(1) Flow alarm output ports and the wiring diagram
2. Alarm causes and working status table.
Note: The flow alarm is connected to the normally open relay and normally closed
relay contacts, requiring operating current less than 5A, working voltage less than
300V.
Display
Condition
Alarm
code
Buzzer
OUT
H1
、
H2
OUT
H1
、
H3
Circulating pump works
properly
DISCONNECTI
ON
BREAKOVER
Blocked cooling water
circulation loop
E6
Sounds
BREAKOVER
DISCONNECTION
Alarm of water shortage
E6
Sounds
BREAKOVER
DISCONNECTION
Faulted circulating pump
E6
Sounds
BREAKOVER
DISCONNECTION
Ultrahigh room temp
E1
Sounds
BREAKOVER
DISCONNECTION
Ultrahigh water temp
E2
Sounds
BREAKOVER
DISCONNECTION
Ultralow water temp
E3
Sounds
BREAKOVER
DISCONNECTION
Faulted room temp sensor
(
constant temp invalid
)
E4
Sounds
BREAKOVER
DISCONNECTION
Faulted water temp sensor
E5
Sounds
BREAKOVER
DISCONNECTION
Chiller power failure
BREAKOVER
DISCONNECTION
Содержание CW-6000AN250S01
Страница 1: ...CW 6000 6100 6200 DUAL TEMPERATURE INDUSTRIAL CHILLER USER MANUAL...
Страница 15: ...CW 6000 6100 6200 Series 15 CW 6000 6100 6200...
Страница 16: ...CW 6000 6100 6200 Series 16 17 18 19 20 23 24 25 28...
Страница 17: ...CW 6000 6100 6200 Series 17 1 2 200 250V 110V 100 130V 3 50Hz 60Hz 4 NORMAL NORMAL 5 50cm 30cm 6 7 8...
Страница 18: ...CW 6000 6100 6200 Series 18...
Страница 19: ...CW 6000 6100 6200 Series 19 1 2 3 4 1 2 3 4 5 6 CW 6000 6100 6200 20...
Страница 22: ...CW 6000 6100 6200 Series 22 5 SET PARAM Set 1 2 2 25 RST 20 6 1 SET 00 PAS 8 SET F0 2 RST 20 SET 1 2 F0 3 F1...
Страница 24: ...CW 6000 6100 6200 Series 24 CW 6000 6100 6200 1 2 H1 H2 H1 H3 E6 E6 E6 E1 E2 E3 E4 E5 5A 300V...
Страница 28: ...CW 6000 6100 6200 Series 28 E6 E6 E2 E1 40...