1th Edition of TEMP1000_Series IM : Apr. 2014 Page 8 / 63
█ Example for
SUM
◈
Example
To read the consecutively D-Register from D0001 (NPV) to D0005 (MVOUT)
- Rrquest
: [stx]01RSD,05,0001[cr][lf]
- Rrquest (with CheckSum)
: [stx]01RSD,05,0001C8[cr][lf]
☞ As
shown below, hexa decimal value adding each text at 01RSD,05,0001 by ASCII code is 2C8, and lower
digit 2 characters C8 will be used for CheckSum.
Text
0
1
R
S
D
,
0
5
,
0
0
0
1
Ascii value
30
31
52
53
44
2C
30
35
2C
30
30
30
31
█ ASCII Table