SAMWONTECH
2nd Edition of TEMP2000M_Series IM : April. 8. 2014 Page 54 / 176
5.1 Program pattern setting
▶
It is a screen to set the segment according to the pattern No.
▶
Refer to the time signal setting [5.4 Time signal motion] for time signal setting.
①
Input the pattern No. to set the segment.
②
The starting condition for program operation can be set by selecting any of ‘TPV’, ‘SPV’ and ‘SSP.’
☞
TPV : The setting data for starting program operation (SP) is started with the present measured data
(PV) regardless of the tendency or starting setting data (SSP) and processes setting data 1
(SP1) set I segment 1 (SEG1) for the setting time (TM1).
☞
SPV: The setting data (SP) in program operation start is started from present measured data (PV) and
processes to the setting data 1 (SP1) which is set to segment 1 (SEG1).
The remained time for operation time is calculated by regarding the times is passed till the
program operation time by referring to the program pattern contents.
☞
SSP: The setting data (SP) in program operation starting process during the set time (TM1) from the
start setting data (SSP) till the setting data (SP1) set in the segment (SEG1).
③
The setting data of the segment to be operated is set.
④
The time for the segment to be operated is set.
⑤
The time signal for the segment to be operated is set.
☞
8 time signals can be set in each segment and each time signal can be set by selecting out of 20
types.
☞
Refer to [5.4 Time signal motion]
⑥
The SEG alarming of the segment to be operated is set.
⑦
The SEG PID for the segment to be operated is set.
⑧
When the segment is inserted, one of the buttons
(Segment 01 ~ 99) is selected and pressed,
the selected button from
(Segment 01 ~ 99) and
(Insert) button are activated. The selected
segment can be inserted when
(Insert) button is pressed.
⑨
When the segment is deleted, one of the buttons
(Segment 01 ~ 99) is selected and pressed,
the selected button from
(Segment 01 ~ 99) and
(Delete) button are activated. The
selected segment can be deleted when
(Delete) button is pressed.
⑩
The screen moves to the left/right with 4 segment units.
⑪
When
(Pattern) button is pressed, it moves to the [Fig. 5-1 Program setting screen].
④
③
⑥
②
⑤
①
⑧
⑦
⑪
⑩
⑨
[Fig. 5-2] Pattern editing screen