1
1. Installation
1-1 Refrigerant Refill Procedure
• Refill an air-conditioner with refrigerant when refrigerant has been leaked at installing or using
1. Purge air(for new installation only).
3. Connect the tank to refill with Refrigerant
4. Set the unit to cool operation mode.
7. Stop operation of the air conditioner.
9. Close the cap of each valve.
2. Turn the 3-way valve clockwise to close, connect the
pressure gauge(low pressure side) to the service valve,
and open the 3-way valve again.
5. Check the pressure indicated by the pressure
gauge(low pressure side).
* Standard pressure is should be 4.5~5.5kg/cm
2
in a
regular, high operation mode.
6. Open the refrigerant tank and fill with refrigerant until
the rated pressure is reached.
* It is recommended not to pour the refrigerant in too
quickly, but gradually while operating a pressure valve.
8. Close the 3-way valve, disconnect the pressure gauge,
and open the 3-way valve again.
R-22
Suspension hook
High
pressure
gauge
Hand
wheel
Finger tight
fittings
Connected to
high pressure
side
Charging
line
For mounting
other and of
hose when
not in use
Compound
gauge
DB81-00188A(4)-1** 10/30/02 10:44 AM Page 1
Содержание UQ18A0RCD
Страница 23: ...22 MEMO DB81 00188A 4 1 10 30 02 10 44 AM Page 22 ...
Страница 25: ...24 6 PCB Diagrams 6 1 Main PCB PD SH30ZC 02 DB81 00188A 4 1 10 30 02 10 45 AM Page 24 ...
Страница 27: ...26 7 Wiring Diagrams 7 1 Indoor Unit AQ24A2RC AQ18AORCD AQ18A6RC DB81 00188A 4 1 10 30 02 10 45 AM Page 26 ...
Страница 30: ...29 MEMO DB81 00188A 4 1 10 30 02 10 45 AM Page 29 ...
Страница 31: ...31 30 8 Schematic Diagrams 8 1 Indoor Unit DB81 00188A 4 1 10 30 02 11 00 AM Page 30 ...
Страница 32: ...32 MEMO DB81 00188A 4 1 10 30 02 10 45 AM Page 32 ...
Страница 33: ...ELECTRONICS 1 00188A 4 CO 10 30 02 10 43 AM Page 2 ...