14-7-2 “Pump down” Procedure
Pump down will be carried out when an evaporator is replaced or when the unit is relocated in another area.
1) Remove the caps from the 3-Way valve and the
3-Way valve.
3) Set the unit to cool operation mode.
(Check if the compressor is operating.)
4) Turn the 3-Way valve clockwise to close.
7) Close the cap of each valve.
2) Turn the 3-Way valve clockwise to close and
connect a pressure gauge (low pressure side)
to the service valve, and open the 3-Way valve
again.
5) When the pressure gauge indicates "0" turn the
3-Way valve clockwise to close.
6) Stop operation of the air conditioner.
3-Way Valve
2-Way Valve
Relocation of the air conditioner
• Refer to this procedure when the unit is relocated.
• Carry out the pump down procedure (refer to the details of 'pump down').
• Remove the power cord.
• Disconnect the assembly cable from the indoor and outdoor units.
• Remove the flare nut connecting the indoor unit and the pipe.
• At this time, cover the pipe of the indoor unit and the other pipe using a cap or vinyl plug to avoid foreign
material entering.
•
Disconnect the pipe connected to the outdoor unit.
At this time, cover the valve of the outdoor unit and the other pipe using a cap or vinyl plug to avoid foreign material
entering.
• Make sure you do not bend the connection pipes in the middle and store together with the cables.
• Move the indoor and outdoor units to a new location.
• Remove the mounting plate for the indoor unit and move it to a new location.
Reference Sheet
14-10
25888A(1)_1.indd 10
2006-04-14 ソタネト 2:26:22
Содержание UH035EAV Series
Страница 46: ...MEMO Samsung Electronics 4 27 ...
Страница 57: ...Samsung Electronics 5 11 5 3 Ass y Control Out UH035EAV DB93 03453A ...
Страница 59: ...Samsung Electronics Ass y Control Out cont UH052EAV DB93 03665D UH070EAV DB93 03665E 5 13 ...
Страница 100: ...Samsung Electronics 7 3 This Document can not be used without Samsung s authorization UH052EAV Wiring Diagram ...
Страница 101: ...7 4 Samsung Electronics This Document can not be used without Samsung s authorization UH070EAV Wiring Diagram ...
Страница 104: ...Samsung Electronics Main This Document can not be used without Samsung s authorization 8 3 Schematic Diagram ...
Страница 106: ...Samsung Electronics MEMO 8 5 ...
Страница 111: ...9 2 Refrigerating Cycle Diagram 9 5 Samsung Electronics EH035EAV UH035EAV ...
Страница 112: ...Samsung Electronics EH052EAV UH052EAV EH070EAV UH070EAV Circuit Descriptions 9 6 ...
Страница 152: ...Samsung Electronics 13 5 OUTDOOR FAN B D DIODE IPM DC_LINK CAP SMPS IGBT 13 2 2 UH052EAV Block Diagram ...
Страница 153: ...13 6 Samsung Electronics OUTDOOR FAN B D DIODE IPM DC_LINK CAP SMPS IGBT 13 2 3 UH070EAV Block Diagram ...
Страница 164: ...Samsung Electronics 14 10 MEMO ...
Страница 165: ...Samsung Electronics MEMO 14 11 ...