Install Manual
30
All
This allows setting all 16 sensors simultaneously to off or Normal Open (N.O.) / Normal Close
(N.C.).
(1) Set the input type after setting "All".
Individual sensor
This option allows setting each of the 16 sensor input types individually.
(1) Select a sensor then press [Enter].
(2) Set the input type for the selected sensor.
(3) Press [ESC] to exit to the OSD menu when you are finished.
Sensor setup lets you choose whether or not to use sensors and their type, and
Record & Relay setup, while set separately, should be set according to the
sensor type. Please refer to the “Record setup”, the “Event Action” heading in
the “Event setup”, and “Relay out” sections for more information.
3.3.3.2
Relay connections & settings
Specification
The alarm specifications are as follows.
No. of outputs
4 relay outputs
Output type
Dry contact
Specification
Connection method Insert stripped wire end into terminal block
DC 30V
1A
Rated
current
AC 125V
0.5A