Installation
Duct
AC***BNHDCH
0.39(9.8)
0.50(12.6)
0.30(7.5)
0.35(9)
0.
54
(1
3.
8)
0.
75
(19
)
AC power: M4 screw
Communication: M3.5 screw
Unit : inch(mm)
Tightening torque lbf·ft (kgf • cm)
M3.5
0.58 to 0.87 (8.0 to 12.0)
M4
0.87 to 1.30 (12.0 to 18.0)
• Power supply cords of parts of appliances for outdoor use
shall not be lighter than polychloroprene sheathed flexible
cord.
–Code designation
[1-phase]
IEC: 60245 IEC 57 / CENELEC: H05RN-F grade or more
• Be sure to run the power supply cable and the communication
cable through electrical conduit as seen in the picture.
AC***BNLDCH
Conduit
AC***BNHDCH
Conduit
CAUTION
• Be sure not to put your finger into the conduit.
• Since it has the external power supply, refer to the outdoor
unit installation manual for MAIN POWER.
CAUTION
• When installing the indoor unit in a computer room or a
server room, use the double shielded communication cable
(tape aluminum / polyester braid + copper) of FROHH2R type.