Troubleshooting
24
Samsung Electronics
6-3-11 (L) Check of instantaneous over-current protection of IPM circuit.
√
Inverter instantaneous over-current protection mode is the mode to be actuated in order to prevent the damage of elements from
the peak current of IPM circuit elements.
√
In case that the inverter circuit instantaneous over-current protection mode actuates.
■
condition of installation
■
• The ventilation is not good because the outdoor unit is installed wrong (the ambient temperature is higher than 50 (°C) )
■
•
→
Reinstall the outdoor unit so that the good ventilation can be made.
■
• In case that the operation is made with the cover bent of the outdoor unit.
■
•
→
Take out the cover.
■
• If two outdoor units are operating face to face, (the bad ventilation is made)
■
•
→
Reinstall the outdoor unit for the good ventilation.
■
• The air circulation is bad due to the attachment of falling leaves.
■
•
→
Take away the leaves for the good ventilation.
■
• If the Refrigerant is overcharged.
■
•
→
Check the amount of Refrigerant.
■
Unit defect
■
• If the comp is locked.
■
•
→
Replace the comp.
■
• If the comp is operating without the revolution of fan motor.
■
•
→
Check the fan motor connector and replace the fan motor.
■
• In case the parts of the control board is damaged.
■
•
→
Replace the outdoor control board.
6-3-12 (M) Check of the comp discharge gas temperature and OLP temperature abnormal rise.
√
If the comp discharge gas temperature and OLP temperature rises higher than a certain level, it protects the circuit.
√
If the comp discharge gas temperature and OLP temperature rises abnormally,
■
Condition of installation
■
• The ventilation is not good because the outdoor unit is installed wrong (the ambient temperature is higher than 50 (°C) )
■
•
→
Reinstall the outdoor unit so that the good ventilation can be made.
■
• In case that the operation is made with the cover bent of the outdoor unit.
■
•
→
Take out the cover.
■
• If two outdoor units are operating face to face, (the bad ventilation is made)
■
•
→
Reinstall the outdoor unit for the good ventilation.
■
• The air circulation is bad due to the attachment of falling leaves
■
•
→
Take away the leaves for the good ventilation.
■
• If the refrigerant is insufficient.
■
•
→
Fill up the amount of refrigerant.
■
Unit defect
■
• If the comp is locked.
■
•
→
Replace the comp.
■
• If the comp is operating without the revolution of fan motor
■
•
→
Take out the protection cover.
■
•
→
Check the fan motor connector and replace the fan motor.
DB98_17175A_1 2/6/04 4:14 PM Page 25
Содержание SH09BPH
Страница 33: ...Samsung Electronics 32 7 3 Ass y Control In Indoor Unit SH09BPH SH12BPH DB93 02583A ...
Страница 35: ...Samsung Electronics 34 7 4 Ass y Control Out SH09BPHX DB93 02740D SH12BPHX DB93 02740C ...
Страница 37: ...Samsung Electronics 36 8 PCB Diagram 8 1 ASS Y PCB Indoor Unit DB93 02584A TOP ...
Страница 38: ...37 Samsung Electronics PCB Diagram BOTTOM ...
Страница 41: ...40 Samsung Electronics 8 2 Ass y PCB Outdoor Unit DB93 02741D 9K DB93 02741C 12K TOP ...
Страница 44: ...Samsung Electronics 43 PCB Diagram BOTTOM ...
Страница 51: ...MEMO Samsung Electronics 50 ...