9
• Press the Power button to turn on the S-NET mini.
• Check if the power indicator turns red.
If the power indicator has not turned on, check the power terminal and
make sure power cable is correctly connected.
Checking the power cable
• Check if the LAN indicator and the Data indicator turns green.
• Check if the Error indicator turns red.
If the Error indicator has turned red, check the power and communication cable
connection.
Checking the indicators
Connected with DMS
• Make sure LAN cable is correctly connected to the LAN port.
• Make sure power terminal is correctly connected.
Connected to Centralized controller/Transmitter
• Make sure communication cable is correctly connected to 485 communication
terminal. Check the polarity of the 485 communication cable. When the polarity
changes, communication will be unavailable.
• Make sure power terminal is correctly connected.
Checking the connection
Compatible models
Type
Maximum number of connections
Remarks
Centralized controller
256 Indoor units
Maximum 16 Centralized
controller connection
Transmitter
256 Indoor units
Maximum 16 Transmitter
connection
DMS
256 Indoor units
Maximum 4 DMS connection
Maximum number of connections
Type
Model
Remarks
Centralized controller
MCM-A202
-
Transmitter
MIM-B04A
-
MIM-B13(For DVM PLUS
II
)
-
MIM-B13A(For DVM PLUS
III
)
Maximum 48 connections for
DVM PLUS
III
DMS
MIM-D00
-