Single enclosure unit
When using with the enclosure unit, design the semi-outdoor unit according to the following specifications to prevent
discharged hot air from flowing back into the inlet.
•
Design the locations of the enclosure unit inlet and outlet to match the locations of the semi-outdoor unit inlet and
outlet.
•
Allow clearance of 50
mm or more between the product and the enclosure unit.
•
Total open area of Ventilation holes
Total open area of
Ventilation holes
Air outlet
,
20,000
mm² or more each
,
20,000
mm² or more each
Air inlet
,
20,000
mm² or more each
,
20,000
mm² or more each
–
When installing an enclosure, refer to the “Required clearance when installing an enclosure” (
English - 10