
8
There are two refrigerant pipes of different diameters:
A smaller one for the liquid refrigerant
A larger one for the gas refrigerant
The inside of copper pipe must be clean & has no dust.
1. Remove the pinch pipe on the pipes and connect the assembly pipes to each pipe, tightening the nuts, first manually
and then with a torque wrench, a spanner applying the following torque.
2. Must use insulator which is thick enough to cover the refrigerant tube to
protect the condensate water on the outside of pipe falling onto the floor
and the efficiency of the unit will be better.
3. Cut off any excess foam insulation.
4. Be sure that there must be no crack or wave on the bended area.
5. It would be necessary to double the insulation thickness(10mm or more)
to prevent condensation even on the insulator when if the installed area
is warm and humid.
6. Do not use joints or extensions for the pipes that connect the indoor and outdoor unit. The only permitted connections
are those for which the units are designed.
Purging the unit
From factory the unit is supplied and set with a pre-charge of nitrogen gas (insert gas). Therefore, all insert gas must be purged
before connecting the assembly piping.
Unscrew the pinch pipe at the end of each refrigerant pipe.
RESULT : All inert gas escapes from the indoor unit.
• To prevent dirt or foreign objects from getting into the pipes
during installation, do NOT remove the pinch pipe completely
until you are ready to connect the piping.
• If the pipes must be shortened refer to page 9.
• Connect the indoor and outdoor units using pipes with flared connections(not supplied). For the lines, use
insulated, unwelded, degreased and deoxidized copper pipe,(Cu DHP type to ISO 1337), suitable for operating
pressures of at least 4200kPa and for a burst pressure of at least 20700kPa. Copper pipe for hydro-sanitary
applications is completely unsuitable.
• For sizing and limits (height difference, line length, max. bends, refrigerant charge, etc.) see the outdoor unit
installation manual.
• All refrigerant connection must be accessible, in order to permit either unit maintenance or removing it completely.
Refrigerant oil
Spanner
Union
Torque wrench
Flare nut
Outer Diameter (D)
Torque (N•m)
ø6.35 mm (1/4”)
14~18
ø9.52 mm (3/8”)
34~42
ø12.70 mm (1/2”)
49~61
ø15.88 mm (5/8”)
68~82
ø19.05 mm (3/4”)
100~120
Connecting the refrigerant pipe
Gas refrigerant port
Liquid refrigerant
port
Clamp
Insulation
refrigerant pipe
Insulation
refrigerant pipe
Gas
refrigerant
pipe
Liquid refrigerant pipe
CAC 유럽향 1way_IM_34507A-05_EN.indd 8
2016-08-02 오후 4:08:10