Samsung NS 1DXEA Series Скачать руководство пользователя страница 8

8

There are two refrigerant pipes of different diameters:

  A smaller one for the liquid refrigerant

  A larger one for the gas refrigerant

  The inside of copper pipe must be clean & has no dust.

1.  Remove the pinch pipe on the pipes and connect the assembly pipes to each pipe, tightening the nuts, first manually 

and then with a torque wrench, a spanner applying the following torque.

2.  Must use insulator which is thick enough to cover the refrigerant tube to 

protect the condensate water on the outside of pipe falling onto the floor 

and the efficiency of the unit will be better.

3.  Cut off any excess foam insulation.

4.  Be sure that there must be no crack or wave on the bended area.

5.  It would be necessary to double the insulation thickness(10mm or more) 

to prevent condensation even on the insulator when if the installed area 

is warm and humid.

 6.  Do not use joints or extensions for the pipes that connect the indoor and outdoor unit. The only permitted connections 

are those for which the units are designed.

Purging the unit

From factory the unit is supplied and set with a pre-charge of nitrogen gas (insert gas). Therefore, all insert gas must be purged 

before connecting the assembly piping.

Unscrew the pinch pipe at the end of each refrigerant pipe.

RESULT : All inert gas escapes from the indoor unit.

•   To prevent dirt or foreign objects from getting into the pipes 

 

during installation, do NOT remove the pinch pipe completely 

 

until you are ready to connect the piping.

•    If the pipes must be shortened refer to page 9.

•   Connect the indoor and outdoor units using pipes with flared connections(not supplied). For the lines, use 

insulated, unwelded, degreased and deoxidized copper pipe,(Cu DHP type to ISO 1337), suitable for operating 

pressures of at least 4200kPa and for a burst pressure of at least 20700kPa. Copper pipe for hydro-sanitary 

applications is completely unsuitable.

•   For sizing and limits (height difference, line length, max. bends, refrigerant charge, etc.) see the outdoor unit 

installation manual.

•   All refrigerant connection must be accessible, in order to permit either unit maintenance or removing it completely.

Refrigerant oil

Spanner

Union

Torque wrench

Flare nut

Outer Diameter (D)

 Torque (N•m)

ø6.35 mm (1/4”)

14~18

ø9.52 mm (3/8”)

34~42

ø12.70 mm (1/2”)

49~61

ø15.88 mm (5/8”)

68~82

ø19.05 mm (3/4”)

100~120

Connecting the refrigerant pipe

Gas refrigerant port

Liquid refrigerant 

port

Clamp
Insulation  

refrigerant pipe

Insulation  

refrigerant pipe

Gas 

 

refrigerant  

pipe

Liquid refrigerant pipe

CAC 유럽향 1way_IM_34507A-05_EN.indd   8

2016-08-02   오후 4:08:10

Содержание NS 1DXEA Series

Страница 1: ...lation manual imagine the possibilities Thank you for purchasing this Samsung product Cassette Type Series NS 1DXEA AC FB1DEH EN PT IT RU ES DE FR EL DB98 34507A 05 CAC 유럽향 1way_IM_34507A 05_EN indd 27 2016 08 02 오후 4 08 21 ...

Страница 2: ...theindoorunitisnotsuitabletobe installedinareasusedforlaundry Donotusetheunitsifdamaged Ifproblemsoccur switchtheunitoffanddisconnectitfromthepowersupply Inordertopreventelectricshocks firesorinjuries alwaysstoptheunit disabletheprotectionswitchandcontactSAMSUNG s technicalsupportiftheunitproducessmoke ifthepowercableishotordamagedoriftheunitisverynoisy Alwaysremembertoinspecttheunit electricconne...

Страница 3: ...evicesdisconnectedfromthepowersupplyshouldbecompletelydisconnectedintheconditionofovervoltagecategory Besurenottoperformpowercablemodification extensionwiring andmultiplewireconnection Itmaycauseelectricshockorfireduetopoorconnection poorinsulation orcurrentlimitoverride Whenextensionwiringisrequiredduetopowerlinedamage referto Howtoconnectyourextendedpowercables in theinstallationmanual Makesuret...

Страница 4: ... consult your dealer Avoid installing the air conditioner In areas where it is exposed to direct sunlight Close to heat sources In damp areas or locations where it could come into contact with water for example rooms used for laundry In areas where curtains and furniture could affect the supply and discharge of air Without leaving the required minimum space around the unit as shown in the drawing ...

Страница 5: ...und if the unit has a duct with a well defined length 300mm or more to avoid fan motor blower contact If you install the cassette or duct type indoor unit on the ceiling with temperature over 27 C or humidity over 80 you must apply extra 10mm of polyethylene foam or other insulation with similar material on the body of the indoor unit The units must be installed according to distances declared in ...

Страница 6: ...ection ø9 52 3 Drain pipe connection VP20 OD26 ID20 4 Power supply connection 5 Air discharge grille 6 Air suction grille Dimension and weight Net dimension Indoor unit mm 970X135X410 Panel size 1180X25X460 Net weight Indoor unit Panel kg 13 970 135 280 410 460 150 25 1036 1074 1180 Drain hole CAC 유럽향 1way_IM_34507A 05_EN indd 6 2016 08 02 오후 4 08 09 ...

Страница 7: ...curely after adjusting level of the unit by using a leveler 4 Remove the pattern sheet connect the other cables and install the front panel Since the diagram is made of paper it may shrink or stretch slightly due to temperature or humidity For this reason before drilling the holes maintain the correct dimensions between the markings Piping must be laid and connected inside the ceiling when suspend...

Страница 8: ...g the assembly piping Unscrew the pinch pipe at the end of each refrigerant pipe Result All inert gas escapes from the indoor unit To prevent dirt or foreign objects from getting into the pipes during installation do NOT remove the pinch pipe completely until you are ready to connect the piping If the pipes must be shortened refer to page 9 Connect the indoor and outdoor units using pipes with fla...

Страница 9: ...ign the pipes and tighten the flare nuts first manually and then with a torque wrench applying the following torque In case of welding the pipe you must weld with nitrogen gas blowing Oblique Rough Burr Pipe cutter Pipe Outer Diameter D Depth A ø6 35 mm 1 4 1 3 mm ø9 52 mm 3 8 1 8 mm ø12 70 mm 1 2 2 0 mm ø15 88 mm 5 8 2 2 mm ø19 05 mm 3 4 2 2 mm Pipe Flare Uneven Thickness Cracked Damaged Surface ...

Страница 10: ...le ducts 5 Selecttheinsulationoftherefrigerantpipe Insulate the gas side and liquid side pipe referring to the thickness according to the pipe size Less than indoor temperature of 30 C and humidity of 85 is the standard condition If installing in a high humidity condition use one grade thicker insulator by referring to the table below If installing in an unfavorable conditions use thicker one Insu...

Страница 11: ...nd then fix it as indicated When installing insulation in places and conditions below use the same insulation that is used for high humidity conditions Geological condition High humidity places such as shoreline hot spring near lake or river and ridge when the part of the building is covered by earth and sand Operation purpose condition Restaurant ceiling sauna swimming pool etc Building construct...

Страница 12: ...ce to the piping on the unit side when connecting the drain hose The hose should not be allowed to hang loose from its connection to the unit Fasten the hose to a wall frame or other support as close to the unit as possible Support pieces 1 1 5m Ceiling 1 100 or more If it is necessary to increase the height of the drainpipe install the drainpipe straightly within 300 mm from the drain hose port I...

Страница 13: ...e control box cover and turn on the indoor unit 3 Check whether the drain pump works correctly 4 Check whether the drainage is performing correctly at the end of the drain pipe 5 Check for leakage at the drain pipe and drain pipe connection part 6 When leakage occurs check whether the indoor unit is level and check the drain hose connection part drainpipe connection part and drain pump connection ...

Страница 14: ...ationinsyntheticrubberandjacketinpolychloroprene neoprene inaccordancewiththerequirementsofstandardEN60335 2 40 1 Removethescrewontheelectricalcomponentboxandremovethecoverplate 2 Routetheconnectioncordthroughthesideoftheindoorunitandconnectthecabletoterminals refertothefigurebelow 3 Routetheotherendofthecabletotheoutdoorunitthroughtheceiling theholeonthewall 4 Reassembletheelectricalcomponentboxc...

Страница 15: ...erminal block must not be unscrewed with the torque less than 12 kgf cm Since it has the external power supply refer to the outdoor unit installation manual for MAIN POWER Between Indoor and Outdoor Connection cable Specifications Common in use Terminal Block SPEC Indoor When installing the indoor unit in a computer room use the double shielded Tape aluminum polyester braid copper cable of FROHH2R...

Страница 16: ...be CAUTION Unit mm 120 60 20 20 20 180 Power cable 20 Pre installed tube for the power cable 3 Insert both sides of core wire of the power cable into the connection sleeve f f Method 1 Push the core wire into the sleeve from both sides Connection sleeve f f Method 2 Twist the wire cores together and push it into the sleeve Connection sleeve 4 Using a crimping tool compress the two points and flip ...

Страница 17: ...wrap it with the insulation tape to finish Make sure that the connection parts are not exposed to outside Be sure to use insulation tape and a contraction tube made of approved reinforced insulating materials that have the same level of withstand voltage with the power cable Comply with the local regulations on extensions CAUTION Insulation tape In case of extending the electric wire please DO NOT...

Страница 18: ...SEG21 SEG22 SEG23 SEG24 2 X X X X X 3 X X X X X The procedure of setting option Set the indoor unit address and installation option with remote controller option Set the each option separately since you cannot set the ADDRESS setting and indoor unit installation setting option at the same time You need to set twice when setting indoor unit address and installation option On SEG1 12 Off SEG13 24 Se...

Страница 19: ...otation 6 Setting Fan mode Press Mode button to be changed to FAN mode in the ON status 7 Setting SEG9 SEG10 option Press Low Fan button to enter SEG9 value Press High Fan button to enter SEG10 value Each time you press the button will be selected in rotation 8 Setting Heat mode Press Mode button to be changed to HEAT mode in the ON status 9 Setting SEG11 SEG12 option Press Low Fan button to enter...

Страница 20: ...ess the button will be selected in rotation 18 Setting Heat mode Press Mode button to be change to HEAT mode in the OFF status 19 Setting SEG23 SEG24 mode Press Low Fan button to enter SEG23 value Press High Fan button to enter SEG24 value Each time you press the button will be selected in rotation SEG16 SEG18 SEG21 SEG23 SEG17 SEG20 SEG22 SEG24 Step 4 Input option Press operation button with the ...

Страница 21: ...in address RESERVED RESERVED The unit digit of an indoor unit Remote Controller Display Indication andDetails Indication Details Indication Details Indication Details Indication Details 0 A 0 No Main address 0 3 A single digit 1 Main address setting mode Option SEG7 SEG8 SEG9 SEG10 SEG11 SEG12 Explanation PAGE RESERVED Setting RMC address RESERVED Group channel 16 Group address Remote Controller D...

Страница 22: ... Settinganindoorunitinstallationoption suitablefortheconditionofeachinstallationlocation SEG1 SEG2 SEG3 SEG4 SEG5 SEG6 0 2 RESERVED Exterior temperature sensor Central control RESERVED SEG7 SEG8 SEG9 SEG10 SEG11 SEG12 1 Drain pump RESERVED RESERVED RESERVED Master Slave SEG13 SEG14 SEG15 SEG16 SEG17 SEG18 2 External control External control output S Plasma ion Buzzer Number of hours using filter S...

Страница 23: ...Explanation PAGE Useofexternal control Setting the output of external control S Plasma ion Buzzer control Number of hours using filter Remote Controller Display Indication and Details Indication Details Indication Details Indication Details Indication Details Indication Details Indication Details 2 0 Disuse 0 Thermo on 0 Disuse 0 Useofbuzzer 2 1000Hour 1 ON OFF Control 1 Operation on 1 Use 1 Nonus...

Страница 24: ...dication Details Indication Details Indication Details 0 D Option mode 0 F Tens digit ofSEG 0 9 Unitdigit ofSEG 0 9 The changed value 0 F When changing a digit of an indoor unit address setting option set the SEG3 as A When changing a digit of indoor unit installation option set the SEG3 as 2 Ex When setting the buzzer control into disuse status Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6 Explanation PAG...

Страница 25: ...n for 2 minutes between indoor units Communication error for more than 2 minutes 2 Indoor unit receiving the communication error from outdoor unit 3 Outdoor unit tracking 3 minutes error 4 When sending the communication error from the outdoor unit the mismatching of the communication numbers and installed numbers after completion of tracking Communication error for more than 2 minutes X X X 1 Indo...

Страница 26: ... gu Gwangju si Korea 62218 Samsung Electronics UK Ltd Euro QA Lab Blackbushe Business Park Saxony Way Yateley Hampshire GU46 6GG United Kingdom AEEE Yönetmeliğine Uygundur This product is RoHS compliant CAC 유럽향 1way_IM_34507A 05_EN indd 26 2016 08 02 오후 4 08 21 ...

Отзывы: