16_

 installing your air conditioner

Indoor Unit Installation

It is recommended to install the Y-joint before installing the 

indoor unit.

1.

Place the pattern sheet on the ceiling at the spot where you 

want to install the indoor unit.

  

  Since the diagram is made of paper, it may shrink 

or stretch slightly due to temperature or humidity. 

For this reason, before drilling the holes maintain 

the correct dimensions between the markings.

Note

2.

Insert bolt anchors, use existing ceiling supports or  

construct a suitable support as shown in figure.

3.

Install the suspension bolts depending on the ceiling type.

         

 

 

  

 

Ensure that the ceiling is strong enough to 

support the weight of the indoor unit.  

Before hanging the unit, test the strength  

of each attached suspension bolt.

   

 

   If the length of suspension bolt is more than 

1.5m, it is required to prevent vibration.

   

   If this is not possible, create an opening on 

the false ceiling in order to be able to use it 

to perform the required operations on the 

indoor unit.

4.

Screw eight nuts to the suspension bolts making space for 

hanging the indoor unit.

           

 

              

     

 

You must install the suspension bolts more than 

four when installing the indoor unit.

   

Concrete

Suspension bolt(3/8" or M10)

Hole in anchor

Hole in plug

Insert

Ceiling support

5.

Hang the indoor unit to the suspension bolts between two nuts.

Piping must be laid and connected inside the  

ceiling when  suspending the unit. If the ceiling is 

already constructed, lay the piping into  

position for connection to the unit before  

placing the unit inside the ceiling.

Note

6.

Screw the nuts to suspend the unit.

7.

Adjust level of the unit by using measurement plate for all 4 sides.

For proper drainage of condensate, give a 1

°

 slant 

to the left or right side of the unit which will be 

connected with the drain hose, as shown in the 

figure. Make a tilt when you wish to install the drain 

pump, too.

Note

Performing Leak Test & Insulation

LEAK TEST WITH NITROGEN(before opening valves)

In order to detect basic refrigerant leaks, before recreating the 

vacuum and recirculating the R410A, it’s responsible of installer 

to pressurize the whole system with nitrogen(using a pressure 

regulator) at a pressure above 4.1MPa(gauge).

LEAK TEST WITH R410A(after opening valves)

Before opening valves, discharge all the nitrogen into the  

system and create vacuum. After opening valves check leaks 

using a leak detector for refrigerant R410A.

Leak test

Discharge all the nitrogen to create a vacuum and 

charge the system.

Rubber

1.

To avoid condensation problems, place 

T13.0 or thicker 

Acrylonitrile Butadien Rubber 

separately around each 

refrigerant pipe.

  

  Always make the seam of pipes face upwards.

Note

Once you have checked that there are no leaks in the system,  

you can insulate the piping and hose.

Insulation

No gap

NBR(T13.0 or thicker)

Installation Part

Drain hose port

Leak check

Big Duct type_IB_E_33763-1.indd   15

2011-06-09   오후 12:32:33

Содержание ND***HH Series

Страница 1: ...k you for purchasing this Samsung product To receive more complete service please register your product at www samsung com register Duct Type Series BIG duct ND HH I F S E P Ne R G D Hu Po DB98 33763A 1 Big Duct type_IB_E_33763 1 indd 20 2011 06 09 오후 12 32 36 ...

Страница 2: ...e at www samsung com Important safety symbols and precautions WARNING Hazards or unsafe practices that may result in severe personal injury or death CAUTION Hazards or unsafe practices that may result in minor personal injury or property damage CAUTION To reduce the risk of fire explosion electric shock or personal injury when using your air conditioner follow these basic safety precautions Do NOT...

Страница 3: ...ug power cable or loosened power receptacle Potential risk of fire or electric shock Install an exclusive circuit breaker and short circuit breaker for the air conditioner Potential risk of electric shock or fire Do not insert anything such as fingers or branches into the air conditioner vents while the air conditioner is running Keep the children away from the air conditioner to prevent them from...

Страница 4: ...wable concentration from being exceeded If the refrigerant leaks and cause the concentration limit to be exceeded hazards due to lack of oxygen in the room may result If the indoor unit gets wet turn the power off immediately and call your nearest contact center Potential risk of fire or electric shock Always make sure that the power supply is compliant with current safety standards Always install...

Страница 5: ...ic shock or fire if repairs or installations are attempted by a non qualified service technician Do not spray flammable gases such as insecticide near the air conditioner Potential risk of electric shock fire or unit malfunction Do not open the front grille during operation Potential risk of electric shock or unit malfunction Cool air should not flow directly towards people pets and plants It is h...

Страница 6: ...ng material and used batteries of the remote controller optional must be disposed of in accordance with the national standards The refrigerant used in the air conditioner must be treated as chemical waste Dispose the refrigerant following national standards Have a qualified service technician install the air conditioner and perform a trial operation Firmly connect the drain hose to the air conditi...

Страница 7: ...maintenance and repairs The units components must be accessible and that can be disassembled in conditions of complete safety either for people or things For this reason where it is not observed as indicated into the Installation Manual the cost necessary to reach and repair the unit in safety as required by current regulations in force with slings trucks scaffolding or any other means of elevatio...

Страница 8: ... with other household waste at the end of their working life To prevent possible harm to the environment or human health from uncontrolled waste disposal please separate these items from other types of waste and recycle them responsibly to promote the sustainable reuse of material resources Household users should contact either the retailer where they purchased this product or their local governme...

Страница 9: ...ur air conditioner and stay cool or warm with optimal efficiency Please read the user manual to get started and to make the best use of the air conditioner Big Duct Type Your air conditioner may look slightly different from the illustration shown above depending on your model Air intake Air Outlet Big Duct type_IB_E_33763 1 indd 9 2011 06 09 오후 12 32 32 ...

Страница 10: ...ioner stops heating The air conditioner will operate automatically in De ice mode for 10 minutes The steam produced on the outdoor unit in De ice mode is safe No intervention is required after about 10 minutes the air conditioner operates again normally The unit will not operate when it starts to de ice Fan Fan may not operate for about 3 5 minutes at the beginning to prevent any cold blasts while...

Страница 11: ...an the condensate drain pan 2 Thoroughly clean the heat exchanger 2 Clean the condensate drain pipe 2 Replace the remote control batteries 1 Outdoor unit Clean the heat exchanger on the outside of the unit 2 Clean the heat exchanger on the inside of the unit 2 Clean the electric components with jets of air 2 Verify that all the electric components are firmly tightened 2 Clean the fan 2 Verify that...

Страница 12: ...otection of internal battery The compressor will be off to protect internal battery when the air conditioner operates in Cool mode Protect compressor The air conditioner does not start operating immediately to protect the compressor of the outdoor unit after it has been started If the heat pump is operating in Heat mode De ice cycle is actuated to remove frost from an outdoor unit that may have de...

Страница 13: ...speed does not change Check if you selected Auto or Dry mode The air conditioner automatically adjusts the fan speed to Auto in Auto Dry mode Timer function does not set Check if you press the Power button on the remote control after you have set the time Odors permeate in the room during operation Check if the appliance is running in a smoky area or if there is a smell entering from outside Opera...

Страница 14: ... or drops on the floor HEATING 27 C or less 20 C to 24 C Internal protection triggers and the air conditioner will stop DRYING 18 C to 32 C 5 C to 43 C Condensation may occur on the indoor unit with risk to have either water blow off or drops on the floor The standardized temperature for heating is 7 C If the outdoor temperature drops to 0 C or below the heating capacity can be reduced depending o...

Страница 15: ...een two nuts Piping must be laid and connected inside the ceiling when suspending the unit If the ceiling is already constructed lay the piping into position for connection to the unit before placing the unit inside the ceiling Note 6 Screw the nuts to suspend the unit 7 Adjust level of the unit by using measurement plate for all 4 sides For proper drainage of condensate give a 1 slant to the left...

Страница 16: ...n part of it to prevent moisture from entering Wind the refrigerant pipe with insulation tape if it is exposed to outside sunlight Install the refrigerant pipe respecting that the insulation does not get thinner on the bent part or hanger of pipe Add the additional insulation if the insulation plate gets thinner Additional insulation Refrigerant pipe insulation a 3 a Hanger Drain pipe and Drain Ho...

Страница 17: ... currents of each indoor unit T Refer to each installation manual about the rating current of indoor unit Decide the power cable specification and maximum length within 10 power drop among indoor units T Coef 1 55 T Lk Distance among each indoor unit m Ak Power cable specification mm2 ik Running current of each unit A Coef 35 6 Lk ik 10 of input voltage V 1000 Ak n k 1 Without the drain pump H 2 1...

Страница 18: ...dress Setting from the outdoor unit see details on the outdoor unit installation manual Note When MAIN address is set as 12 For Example Setting RMC Address The SW03 and SW04 RMC switch is the address setting switch for controlling the indoor unit with the centralized controller You must set the SW03 SW04 and K2 switch when using the centralized controller You don t have to set the SW03 and SW04 RM...

Страница 19: ...sung com LUXEMBURG 261 03 710 www samsung com BRAZIL 0800 124 421 4004 0000 www samsung com MACEDONIA 023 207 777 CHILE 800 SAMSUNG 726 7864 www samsung com MONTENEGRO 020 405 888 COLOMBIA 01 8000112112 www samsung com NETHERLANDS 0900 SAMSUNG 0900 7267864 0 10 Min www samsung com COSTA RICA 0 800 507 7267 www samsung com NORWAY 815 56 480 www samsung com DOMINICA 1 800 751 2676 www samsung com PO...

Отзывы: