Samsung ND 4HXEA Series Скачать руководство пользователя страница 8

8

There are two refrigerant pipes of different diameters :

  A smaller one for the liquid refrigerant

  A larger one for the gas refrigerant

  The inside of copper pipe must be clean & has no dust

1.  Remove the pinch pipe on the pipes and connect the assembly pipes to each pipe, tightening the nuts, first manually 

and then with a torque wrench, a spanner applying the following torque.

2.  Must use insulator which is thick enough to cover the refrigerant tube to 

protect the condensate water on the outside of pipe falling onto the floor 

and the efficiency of the unit will be better.

3.  Cut off any excess foam insulation.

4.  Be sure that there must be no crack or wave on the bended area.

5.  It would be necessary to double the insulation thickness(10mm or more) 

to prevent condensation even on the insulator when if the installed area is 

warm and humid.

 6.  Do not use joints or extensions for the pipes that connect the indoor and outdoor unit. The only permitted connections 

are those for which the units are designed.

Purging the unit

From factory the unit is supplied and set with a pre-charge of nitrogen gas. (insert gas) Therefore, all insert gas must be purged 

before connecting the assembly piping.

Unscrew the pinch pipe at the end of each refrigerant pipe.

RESULT : All inert gas escapes from the indoor unit.

•   To prevent dirt or foreign objects from getting into the pipes during 

installation, do NOT remove the pinch pipe completely until you are 

ready to connect the piping.

•    If the pipes must be shortened refer to page 9.

•   Connect the indoor and outdoor units using pipes with flared connections(not supplied). For the lines, use 

insulated, unwelded, degreased and deoxidized copper pipe (Cu DHP type to ISO 1337 or UNI EN 12735-1), suitable 

for operating pressures of at least 4200kPa and for a burst pressure of at least 20700kPa. Copper pipe for hydro-

sanitary applications is completely unsuitable.

•   For sizing and limits (height difference, line length, max. bends, refrigerant charge, etc.) see the outdoor unit 

installation manual.

•   All refrigerant connection must be accessible, in order to permit either unit maintenance or removing it completely.

Gas refrigerant port

Liquid refrigerant 

port

Refrigerant oil

Spanner

Union

Torque wrench

Flare nut

Outer Diameter (D)  Torque (N•m)

ø6.35 mm

18

ø9.52 mm

42

ø12.70 mm

55

ø15.88 mm

65

Connecting the refrigerant pipe

ND***4HXEA_IM_E_33497A(1).indd   8

2011-03-08   오후 2:00:21

Содержание ND 4HXEA Series

Страница 1: ...nstallation manual imagine the possibilities Thank you for purchasing this Samsung product To receive more complete service please register your product at www samsung com register E DB98 33497A 1 ND 4HXEA_IM_E_33497A 1 indd 27 2011 03 08 오후 2 00 34 ...

Страница 2: ...nty Theairconditionershouldbeusedonlyfortheapplicationsforwhichithasbeendesigned theindoorunitisnotsuitabletobe installedinareasusedforlaundry Donotusetheunitsifdamaged Ifproblemsoccur switchtheunitoffanddisconnectitfromthepowersupply Inordertopreventelectricshocks firesorinjuries alwaysstoptheunit disabletheprotectionswitchandcontactSAMSUNG s technicalsupportiftheunitproducessmoke ifthepowercable...

Страница 3: ...nit in such conditions first consult your dealer Avoid installing the air conditioner In areas where it is exposed to direct sunlight Close to heat sources In damp areas or locations where it could come into contact with water for example rooms used for laundry In areas where curtains and furniture could affect the supply and discharge of air Without leaving the required minimum space around the u...

Страница 4: ...Maintain sufficient clearance around the indoor unit Make sure that the water dripping from the drain hose runs away correctly and safely The indoor unit must be installed in this way that they are out of public access Not touchable by the users Insulation cover band Insulation pipe Cable tie Drain hose Installation manual Clamp If you install the cassette type indoor unit on the ceiling with humi...

Страница 5: ...eople or things Do not hold the discharge while carrying the indoor unit to avoid the possibility of breakage You must hold the hanger plate on the corner and carry the indoor unit MODEL ND0454HX ND0564HX ND0714HX ND0904HX ND1124HX ND1284HX ND1404HX C mm 251 293 335 Net dimension mm 840 204 840 840 246 840 840 288 840 Required space for an indoor unit installation Obstruction 20mm 17mm 1500mm or m...

Страница 6: ...8 840 840 288 840 Net weight kg 15 5 15 5 17 5 19 5 Liquid pipe connection 1 4 3 8 Gas pipe connection 1 2 5 8 Drain Hose connection mm OD Ф32 0 ID Ф26 5 Drawing of the indoor unit 890 910 Celling opening 950 735 Suspension position 890 910 Celling opening 735 Suspension position Sub duct connection 55 840 370 346 185 96 950 120 45 86 164 216 55 55 840 330 240 270 300 ND 4HXEA_IM_E_33497A 1 indd 6...

Страница 7: ...he indoor unit 2 Adjust a space between the ceiling and the indoor unit by using the gauge of dimensions 3 Fix the indoor unit securely after adjusting level of the unit by using a leveler 4 Remove the pattern sheet connect the other cables and install the front panel Since the diagram is made of paper it may shrink or stretch slightly due to temperature or humidity For this reason before drilling...

Страница 8: ...n gas insert gas Therefore all insert gas must be purged before connecting the assembly piping Unscrew the pinch pipe at the end of each refrigerant pipe RESULT All inert gas escapes from the indoor unit To prevent dirt or foreign objects from getting into the pipes during installation do NOT remove the pinch pipe completely until you are ready to connect the piping If the pipes must be shortened ...

Страница 9: ...anually and then with a torque wrench applying the following torque Cutting flaring the pipes In case of needing brazing you must work with Nitrogen gas blowing Uneven Thickness Cracked Damaged Surface Inclined Correct Oblique Rough Burr Flaring tool Clutch type Wing nut type A Die Copper pipe York Die Copper pipe Flare nut Outer diameter mm A mm Flare tool for R410A clutch type Conventional flare...

Страница 10: ...d to the wall with suitable ducts If the pipes require brazing ensure that OFN Oxygen Free Nitrogen is flowing through the system Leak test Insulation No gap NBR T13 0 or thicker Insulation cover pipe Indoor unit Be sure to overlap the insulation Insulation pipe Must fit tightly against body without any gap Always make the seam of pipes face upwards All refrigerant connection must be accessible in...

Страница 11: ...tionpartofittopreventmoisture fromentering Windtherefrigerantpipewithinsulationtapeifitisexposedtooutsidesunlight Installtherefrigerantpiperespectingthattheinsulationdoesnotgetthinneronthebentpartorhangerofpipe Addtheadditionalinsulationiftheinsulationplategetsthinner Additional insulation Hanger Refrigerant pipe insulation a 3 a Pipe Pipesize InsulationType Heating Cooling Remarks Standard 30 C 8...

Страница 12: ... and upward gradient after the connection port This will cause water to flow backwards when the unit is stopped resulting in water leaks Air ventilation Ceiling Install air ventilation to drain condensate water smoothly Do not apply force to the piping on the unit side when connecting the drain hose The hose should not be allowed to hang loose from its connection to the unit Fasten the hose to a w...

Страница 13: ...nt of the farthest indoor unit from the main drain when installed indoor units are more than 3 2 You may need to install individual air vent to prevent water flow back at the top of each indoor unit drainpipe Hanger Main drainpipe Individual air vent Main air vent Centralized horizontal drainpipe more than 1 100 slope 550mm or less 1 1 5m ND 4HXEA_IM_E_33497A 1 indd 13 2011 03 08 오후 2 00 23 ...

Страница 14: ...stallation You should test the drainage after completing the installation Prepare a little water about 2 0 liters 1 Turn the cover drain pump then pull it out 2 Pour water into the indoor unit as shown in figure 3 Confirm that the water flows out through the drain hose 4 Reassemble the cover drain pump Testing the drainage If you do not pour water inside the water supply intake water may spill fro...

Страница 15: ...stalling the wired remote Control Indoor Unit 1 Outdoor Unit Indoor Unit 2 Indoor Unit 3 Wired Remote Control 220 240V h ELB Essential Installation TighteningTorque kgf cm M3 5 6 M3 5 8 10 M4 12 14 7 Using the correct tools connect the cables to the terminal board securely within the range of rated torque so the cable is firm and cannot be moved by external force or pressure Make sure the cables a...

Страница 16: ... 10 power drop among indoor units h X The capacity of ELB MCCB h Ai Sum of Rating currents of each indoor unit h Refer to each installation manual about the rating current of indoor unit Rating current Unit Model Ratingcurrent ND 4H 045 056 071 090 112 128 140 0 15A 0 15A 0 21A 0 30A 0 36A 0 36A 0 45A Selecting compressed ring terminal Silver solder Norminal dimensions forcable mm2 Norminal dimens...

Страница 17: ... Indoor unit1 ELB Coef 35 6 Lk ik 10 of input voltage V 1000 Ak n k 1 220 V 2 2 V 2 0 V 2 5 mm2 208 8 V Within 198V 242V 2 2 2 0 1 8 1 5 1 3 1 1 0 9 0 7 0 4 0 2 11 2 V it s okay 2 5 mm2 2 5 mm2 Installing with 1 sort wire 220 V 1 4 V 1 2 V 2 5 mm2 209 5 V Within 198V 242V 1 4 1 2 1 8 1 5 1 3 1 1 0 9 0 7 0 4 0 2 10 5 V it s okay 4 0 mm2 4 0 mm2 Installing with 2 different sort wire ND 4HXEA_IM_E_33...

Страница 18: ...13 SEG19 are not set as page option Set the SEG2 SEG6 SEG8 SEG12 as ON status and SEG14 18 SEG20 24 as OFF status SEG1 SEG2 SEG3 SEG4 SEG5 SEG6 SEG7 SEG8 SEG9 SEG10 SEG11 SEG12 0 X X X X X 1 X X X X X SEG13 SEG14 SEG15 SEG16 SEG17 SEG18 SEG19 SEG20 SEG21 SEG22 SEG23 SEG24 2 X X X X X 3 X X X X X The procedure of option setting Settinganindoorunitaddressandinstallationoption Set the indoor unit add...

Страница 19: ...tation 6 Setting Fan mode Press Mode button to be changed to FAN mode in the ON status 7 Setting SEG9 SEG10 option Press Low Fan button to enter SEG9 value Press High Fan button to enter SEG10 value Each time you press the button will be selected in rotation 8 Setting Heat mode Press Mode button to be changed to HEAT mode in the ON status 9 Setting SEG11 SEG12 option Press Low Fan button to enter ...

Страница 20: ...gh Fan button to enter SEG22 value Each time you press the button will be selected in rotation 18 Setting Heat mode Press Mode button to be change to HEAT mode in the OFF status 19 Setting SEG23 SEG24 mode Press Low Fan button to enter SEG23 value Press High Fan button to enter SEG24 value Each time you press the button will be selected in rotation SEG16 SEG18 SEG21 SEG23 SEG17 SEG20 SEG22 SEG24 S...

Страница 21: ...n Details Indication Details Indication Details Indication Details 0 A 0 No Main address 0 9 100 digit 0 9 10 digit 0 9 A unit digit 1 Main address setting mode Option SEG7 SEG8 SEG9 SEG10 SEG11 SEG12 Explanation PAGE Setting RMC address Group channel 16 Group address Remote Controller Display Indication andDetails Indication Details Indication Details Indication Details Indication Details Indicat...

Страница 22: ...G1 SEG2 SEG3 SEG4 SEG5 SEG6 0 2 RESERVED Exterior temperature sensor Central control FAN RPM compensation SEG7 SEG8 SEG9 SEG10 SEG11 SEG12 1 Drain pump Hot water heater Electronic heater Opening the electronic expansion valve Master Slave SEG13 SEG14 SEG15 SEG16 SEG17 SEG18 2 External control External control output S Plasma ion Buzzer Number of hours using filter SEG19 SEG20 SEG21 SEG22 SEG23 SEG...

Страница 23: ...8 Explanation PAGE Useofexternal control Setting the output of external control S Plasma ion Buzzer control Number of hours using filter Remote Controller Display Indication and Details Indication Details Indication Details Indication Details Indication Details Indication Details Indication Details 2 0 Disuse 0 Thermo on 0 Disuse 0 Mixedoperation control1 Use buzzer 2 1000Hour 1 ON OFF Control 1 O...

Страница 24: ... Indication Details Indication Details Indication Details 0 D Option mode 0 F Tens digit ofSEG 0 9 Unitdigit ofSEG 0 9 The changed value 0 F When changing a digit of an indoor unit address setting option set the SEG3 as A When changing a digit of indoor unit installation option set the SEG3 as 2 Ex When setting the buzzer control into disuse status Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6 Explanation ...

Страница 25: ...oor temperature sensor Error of the condensor temperature sensor Error of the discharge temperature sensor X X No communication for 2 minutes between indoor and outdoor unit communication error for more than 2minutes X X Error of outdoor unit X Detection of the float switch X X EEPROM error X EEPROM option error Mixed operation error X X X If you turn off the air conditioner when the LED is flicke...

Страница 26: ...26 Memo ND 4HXEA_IM_E_33497A 1 indd 26 2011 03 08 오후 2 28 13 ...

Страница 27: ...27 ND 4HXEA_IM_E_33497A 1 indd 27 2011 03 08 오후 2 28 13 ...

Страница 28: ... EEE Yönetmeliğine Uygundur This EEE is compliant with RoHS ND 4HXEA_IM_E_33497A 1 indd 26 2011 03 08 오후 2 00 34 ...

Отзывы: