25
ENGLISH
f
f
Code: 20**
T
S
#2021 or #2031
#2022 or #2032
#2011
#2012
T
A
T
S
Target water temperature
T
A
Ambient (outdoor) temperatur
1) In case of outdoor temperature (Ta)°C < (Code #2011)°C
- Code #2041: 1 (Floor) Setting Ts = #2021
- Code #2041: Setting 2 (Fan Coil Unit) Ts = #2031
2) In case of (Code #2011)°C ≤ outdoor temperature(Ta)°C < (Code #2012)°C
- Code #2041: Setting 1(Floor) Ts = #2021 + (#2022 - #2021) / (#2012 - #2011) * (Ta - #2011)
- Code #2041: Setting 2(Fan Coil Unit) Ts = #2031 + (#2032 - #2031)/(#2012 - #2011) * (Ta - #2011)
3) In case of (Code #2012)°C ≤ outdoor temperature(Ta) °C
- Code #2041: Setting 1(Floor) Ts = #2022
- Code #2041: Setting 2(Fan Coil Unit) Ts = #2032
2091 : Application of External thermostat in user’s system
- 0: Disabled
- 1: Turn on or off the device using the thermostat
- 2: Turn on or off the device in connection with the thermostat and discharged water temperature settings
❋
❋
Discharged water temperature setting when a thermostat is connected
- Cooling mode : #1012 value (Wired remote controller category field specifications)
- Heating mode : Value set according to water laws
f
f
Code 30**
- User’s options for domestic hot water (DHW) tank heating
3011: Application of DHW tank
302*: Heat pump variables for tank temp. control and combination with booster heater
•
3021: Maximum DHW tank temperature with heat pump (H/P) operation
•
3022: Offset temperature of forced DHW’s thermo off (Only Hydro Unit / Not Hydro Unit HT)
Forced DHW’s thermo off : Water tank temperature ≥ Code #3021 - Code #3022
•
3023: Offset temperature of DHW’s thermo on (Only Hydro Unit / Not Hydro Unit HT)
Temperature of Hot Water Tank ≤ Setting temperature of Hot Water Tank + 1
AND Temperature of Hot Water Tank ≤ Code #3021 – Code #3022 + Code #3023
•
3024: When Heating and DHW mode is operating at the same time and heating mode is operating based on leaving
water temperature with Thermo off, heating will operate for number of minutes stated in #3024 after every
time maximum DHW operation time ends
•
3025: DHW operation time when heating and DHW mode is operating at the same time
•
3026: Heating operation time when heating and DHW mode is operating at the same time
303*: Booster heater variables for combination with heat pump
•
3031: Application of Booster heater
•
3032: Booster heater startup delay timer
•
3033: Booster heater overshoot temperature(FSV #3033, Default “0˚C”, Range 0 ~ 4˚C)
304*: Setting hot water tank disinfection period