22
Field specification setting mode of wired remote controller
Classification
Function
Detail
Code
(Main
+ sub
menu)
Basic Min.
Max.
Step
Unit
Heating
Heating mode
Heating/hot water
priority
4011
0 (Hot
water)
0
1
(Heating)
-
-
Heating priority
4012
0
-15
20
1
°C
Heating Off
4013
35
14
35
1
°C
Others
Outing mode
Temperature of
cooling water oulet
5011
25
5
25
1
°C
Room Temperature
of cooling Mode
5012
30
18
30
1
°C
Temperature of
heating leaving
water
5013
15
15
50
1
°C
Indoor heating
temperature
5014
16
16
30
1
°C
Temperature of auto
heating WL1 water
5017
15
15
50
1
°C
Temperature of auto
heating WL2 water
5018
15
15
50
1
°C
Temperature of hot
water Tank
5019
30
30
75
1
°C
Economic DHW mode
Temperature of hot
water Tank
5021
5
0
40
1
°C
Smart grid (Power peak control)
Operation
5041
0 (No)
0
1 (Yes)
-
-
Heat source for
operation limit
5042
0 (All)
0
2
1
-
Contact Logic
5043 1 (High) 0 (Low)
1
-
-
Ratio of hot water supply compare
to heating
A/7 (Ratio is
determined based
on the value of the
A)7 means Heating
capacity=Hot water
capacity
5061
7
1
7
1
-
•
The menu not supported by the product will not be displayed.
NOTE