Main pipe 1 size increment
Pipe size
Thickness(mm)
Material
(O. D. mm)
ø 6.35
0.7
ø 9.52
0.7
ø 12.70
0.8
ø 15.88
0.8
ø 19.05
ø 22.23
ø 25.40
1.0
ø 28.58
ø 31.75
ø 38.10
1.35
ø 44.45
1.6
ø 50.80
2.0
Main pipe
❇
Main pipe : from outdoor unit to the first branch
joint
Equivalent pipe length between
outdoor unit and the farthest indoor unit
C1220T-1/2H
(Half-hard)
C1220T-O
(Annealed)
0.9
1.1
The pipe length between outdoor and the farthest indoor unit
below 90 m
90m and over
ø 9.52
ø 12.70
ø 12.70
ø 15.88
ø 15.88
ø 19.05
ø 19.05
ø 22.23
ø 22.23
ø 25.40
ø 25.40
ø 28.58
ø 28.58
ø 31.75
ø 31.75
ø 38.10
ø 38.10
ø 44.45
ø 44.45
ø 50.80
Elbow
Pipe size (O. D. mm)
Equivalent length (m)
ø 9.52
0.18
ø 12.70
0.20
ø 15.88
0.25
ø 19.05
0.35
ø 22.23
0.40
ø 25.40
0.45
ø 28.58
0.50
ø 31.75
0.55
ø 38.10
0.60
ø 41.30
0.70
ø 44.45
0.75
ø 50.80
0.80
Type
Equivalent length (m)
Y joint
0.5
Header joint
1.0
When the equivalent pipe length from outdoor unit to the farthest indoor unit is over
than 90m, the main pipe (both liquid and gas pipe) has to be increased with 1 size like
below table.
❈
Equivalent length calculation method
Equivalent length = actual pipe length(m) + number of ‘Y-joint' X 0.5(m) + number
of 'Header joint' X 1.0(m) + number of elbows X equivalent
length of each elbow
06_Installation(02~45) 3/15/08 4:34 Page 23
Содержание Mini DVM
Страница 4: ...DVM PLUS III I 4 1 products 01 41 3 14 08 22 01 Page 4 ...
Страница 42: ...DVM PLUS III II 2 chapter2_Indoor units 002 051 3 14 08 22 09 Page 2 ...
Страница 44: ...II 4 Indoor Units chapter2_Indoor units 002 051 3 14 08 22 09 Page 4 ...
Страница 64: ...Indoor Units II 24 chapter2_Indoor units 002 051 3 14 08 22 09 Page 24 ...
Страница 76: ...II 36 Indoor Units chapter2_Indoor units 002 051 3 14 08 22 09 Page 36 ...
Страница 110: ...II 70 Indoor Units chapter2_Indoor units 052 107 3 14 08 22 15 Page 70 ...
Страница 183: ...II 143 I NDOOR U NITS chapter2_Indoor units 108 143 3 14 08 22 38 Page 143 ...
Страница 184: ...DVM PLUS III III 2 3 1 DVM HR3_Outdoor 002 037 3 21 08 11 19 Page 2 ...
Страница 186: ...Outdoor Units III 4 3 1 DVM HR3_Outdoor 002 037 3 21 08 11 19 Page 4 ...
Страница 504: ...DVM PLUS III IV 2 4 Accessories 02 31 3 6 08 13 59 Page 2 ...
Страница 506: ...IV 4 Accessories 4 Accessories 02 31 3 6 08 13 59 Page 4 ...
Страница 507: ...Panels Drain pumps 1 1 A CCESSORIES IV 5 1 1 Panels 1 2 Drain pumps IV IV 6 6 4 Accessories 02 31 3 6 08 13 59 Page 5 ...
Страница 516: ...IV 14 Accessories 4 Accessories 02 31 3 6 08 13 59 Page 14 ...
Страница 532: ...Accessories IV 30 4 4 EEV kits 4 5 Electrical wiring diagram 1 2 3 6 4 5 4 Accessories 02 31 3 6 08 13 59 Page 30 ...
Страница 533: ...IV 31 A CCESSORIES 4 Accessories 02 31 3 6 08 13 59 Page 31 ...
Страница 534: ...DVM PLUS III V 2 05 1_control systems 002 045 3 15 08 4 09 Page 2 ...
Страница 536: ...Control Systems V 4 05 1_control systems 002 045 3 15 08 4 09 Page 4 ...
Страница 614: ...Control Systems V 82 05 3_control systems 082 141 3 6 08 14 03 Page 82 ...
Страница 674: ...Control Systems V 142 05 4 6_control systems 142 171 3 6 08 14 09 Page 142 ...
Страница 696: ...V 164 Control Systems 05 4 6_control systems 142 171 3 6 08 14 09 Page 164 ...
Страница 703: ...V 171 C ONTROL S YSTEMS 05 4 6_control systems 142 171 3 6 08 14 09 Page 171 ...
Страница 704: ...DVM PLUS III VI 2 06_Installation 02 45 3 15 08 4 34 Page 2 ...
Страница 706: ...VI 4 Installation 06_Installation 02 45 3 15 08 4 34 Page 4 ...