DVM design process
5-1. DVM design process
DVM is a multi-system air conditioner that changes its performance by different conditions such as design temperature,
indoor and outdoor unit combination rates, heating operation rates, piping length, and level difference. It is important to select
the appropriate design condition to the load specification of each room.
• Design temperature
• Calculate cooling and heating loads
• Power supply, piping length and level difference
• Consider design temperature conditions to select larger
indoor types than actual load.
No
Yes
Yes
No
Determine DVM design conditions
Select preliminary indoor unit
for each zone
Calculate actual capacity of each
indoor unit
Draw design diagram
Select DVM control system
Actual capacity of each indoor unit >=
cooling and heating load for each zone
Does actual combination rates of indoor
and outdoor units exceed 100%?
Does actual combination ratio of indoor
and outdoor units exceed 100%?
Calculate actual capacity of
outdoor units (Using the
relevant outdoor unit's
capacity table 100~130%)
Calculate actual capacity of
outdoor units (Using the
relevant outdoor unit's capacity
table 100%)
• Determine outdoor units by the sum of the capacity of
preliminary selected indoor units: At this time, decide how
much combination ratio to permit.
• If indoor units’ actual capacity is lower than the load, reselect
ones with a larger capacity. Depending on designers’ own
discretion.
• If there is no indoor unit with a larger capacity, add another
indoor unit.
• Calculate actual capacity of each indoor unit based
on the calculated outdoor capacity.
• Calculate actual capacity of outdoor
units considering design temperature,
indoor and outdoor unit combination
ratio, piping length, level difference,
heating operation rates, etc.
Select preliminary outdoor unit
(Max. combination ratio of indoor and
outdoor units: 130%)
Re-selection of
indoor units
1. products(01~41) 3/14/08 22:01 Page 32
Содержание Mini DVM
Страница 4: ...DVM PLUS III I 4 1 products 01 41 3 14 08 22 01 Page 4 ...
Страница 42: ...DVM PLUS III II 2 chapter2_Indoor units 002 051 3 14 08 22 09 Page 2 ...
Страница 44: ...II 4 Indoor Units chapter2_Indoor units 002 051 3 14 08 22 09 Page 4 ...
Страница 64: ...Indoor Units II 24 chapter2_Indoor units 002 051 3 14 08 22 09 Page 24 ...
Страница 76: ...II 36 Indoor Units chapter2_Indoor units 002 051 3 14 08 22 09 Page 36 ...
Страница 110: ...II 70 Indoor Units chapter2_Indoor units 052 107 3 14 08 22 15 Page 70 ...
Страница 183: ...II 143 I NDOOR U NITS chapter2_Indoor units 108 143 3 14 08 22 38 Page 143 ...
Страница 184: ...DVM PLUS III III 2 3 1 DVM HR3_Outdoor 002 037 3 21 08 11 19 Page 2 ...
Страница 186: ...Outdoor Units III 4 3 1 DVM HR3_Outdoor 002 037 3 21 08 11 19 Page 4 ...
Страница 504: ...DVM PLUS III IV 2 4 Accessories 02 31 3 6 08 13 59 Page 2 ...
Страница 506: ...IV 4 Accessories 4 Accessories 02 31 3 6 08 13 59 Page 4 ...
Страница 507: ...Panels Drain pumps 1 1 A CCESSORIES IV 5 1 1 Panels 1 2 Drain pumps IV IV 6 6 4 Accessories 02 31 3 6 08 13 59 Page 5 ...
Страница 516: ...IV 14 Accessories 4 Accessories 02 31 3 6 08 13 59 Page 14 ...
Страница 532: ...Accessories IV 30 4 4 EEV kits 4 5 Electrical wiring diagram 1 2 3 6 4 5 4 Accessories 02 31 3 6 08 13 59 Page 30 ...
Страница 533: ...IV 31 A CCESSORIES 4 Accessories 02 31 3 6 08 13 59 Page 31 ...
Страница 534: ...DVM PLUS III V 2 05 1_control systems 002 045 3 15 08 4 09 Page 2 ...
Страница 536: ...Control Systems V 4 05 1_control systems 002 045 3 15 08 4 09 Page 4 ...
Страница 614: ...Control Systems V 82 05 3_control systems 082 141 3 6 08 14 03 Page 82 ...
Страница 674: ...Control Systems V 142 05 4 6_control systems 142 171 3 6 08 14 09 Page 142 ...
Страница 696: ...V 164 Control Systems 05 4 6_control systems 142 171 3 6 08 14 09 Page 164 ...
Страница 703: ...V 171 C ONTROL S YSTEMS 05 4 6_control systems 142 171 3 6 08 14 09 Page 171 ...
Страница 704: ...DVM PLUS III VI 2 06_Installation 02 45 3 15 08 4 34 Page 2 ...
Страница 706: ...VI 4 Installation 06_Installation 02 45 3 15 08 4 34 Page 4 ...