E-
57
Indoor Unit
Single indoor unit has following point list.
Instance
Number
Object
Object
Type
Object Name
Unit
Status value
Inactive Active
Text-1 Text-2
Text-3
Text-4 Text-5
1
Indoor Temperature
AI AC_RoomTemp_xx_
xxxxxx
°C
2
Set temperature
AV AC_Temp_Set_xx_
xxxxxx
°C
3
Setting lower temperature limit AV AC_Cool_LimitTemp_
xx_xxxxxx
°C
4
Setting upper temperature limit AV AC_Heat_LimitTemp_
xx_xxxxxx
°C
5
The power value of an indoor unit
after the basic date
AI AC_Baseline_kWh_xx_
xxxxxx
kWh
6
The number of hours usage of an
indoor unit after the basic date
AI AC_Baseline_Minute_
xx_xxxxxx
Minute
7
Power value within period
AI AC_Period_kWh_xx_
xxxxxx
kWh
8
The number of hours usage of an
indoor unit within period
AI AC_Period_Minute_xx_
xxxxxx
Minute
9
Power On/Off
BV AC_Power_xx_xxxxxx
Off
On
10
Applying lower temperature
limit setting
BV AC_Cool_Limit_set_xx_
xxxxxx
Off
On
11
Applying upper temperature
limit setting
BV AC_Heat_Limit_set_xx_
xxxxxx
Off
On
12
Filter sign status
BI AC_FilterSign_xx_
xxxxxx
Off
On
13
Filter sign reset
BO AC_FilterSign_Reset_
xx_xxxxxx
Off
On
14
Operation mode status
MV AC_Operation_Mode_
xx_xxxxxx
Auto
Cool
Heat
Fan
Dry
15
Fan speed status
MV AC_FanSpeed_xx_
xxxxxx
Auto
Low
Mid
High
16
Air flow direction status
MV AC_FanFlow_xx_xxxxxx Stop UpDown LeftRight UpDown/
LeftRight
17
Operation mode limit status
MV AC_Mode_Limit_xx_
xxxxxx
No
Limt
Cool
Only
Heat
Only
18
Remote controller limit status
MV AC_Remocon_Limit_
xx_xxxxxx
Work
Fully
Limited
Power
On
Limited
19
Integrated error code of both
indoor unit and outdoor unit
AI AC_Error_Code_xx_
xxxxxx
Refer to list of error code
Temperature setting range can be different depending on the
model and the common range is as follows:
Auto: 18˚C~30˚C
Cool: 18˚C~30˚C
Heat: 16˚C~30˚C
Fan: Temperature cannot be adjusted
Dry: 18˚C~30˚C
BACnet Point List
MIM-B17_BACnet Gateway_IM_E 32390-3.indd 57
2011-04-04 오후 3:44:31