Setting the Pulse Rate
f
f
You can set the pulse constant (Wh/Pulse or m
3
/Pulse or L/Pulse) value of the meter connected to each channel .
1 . Access to main menu by pressing the [Menu] button from the normal display . Then select ‘2 .Configuration’ by pressing
the [
], [
] buttons, and press the [Set] button .
Main Menu
2.Configuration
2 . Enter the password using the [
], [
] buttons and press the [Set] button .
- The default password is ‘0000’ .
Enter your P/W
0:0:0:0
3 . Select ‘2 .3 Pulse Rate’ by pressing the [
], [
] buttons and then press the [Set] button .
2.Configuratuion
2.3 Pulse Rate
4 . Move to the channel you want to set by pressing the [
], [
] buttons, and then press the [Set] button .
- You can select each channel or all channel altogether .
2.3 Pulse Rate
CH1:00001Wh/P
5 . Modify the digit by pressing the [
], [
] buttons .
You can move to the next digit by pressing the [Set] button .
Default
- Power : 1Wh/P
- Gas : 0 .001m
3
/P
- Water : 1L/P
Constant range
- Power : 1Wh/P ~ 10,000Wh/P
- Gas : 0 .001m
3
/P ~ 10m
3
/P
- Water : 1L/P ~ 10,000L/P
Set CH1 Value
CH1:00001Wh/P
6 . Press the [Set] button to save the setting .
7 . After the setting, press the [Menu] button to move to upper menu or cancel the setting .
- All menus will return to the normal display if there is no input for 1 minute .
English-23
INST
All
ING
Th
E PRODUC
T
02
MIM-B16N_PIM_IM_DB68-04502A-03_EN.indd 23
2016-10-19 오후 3:19:28