FOR INSTALLATION

WARNING

Make sure to connect wires thoroughly and fix them firmly so that no outer pressure of the wires would put on the terminal 
block.

X

  If the terminal is loose, it may generate heat and cause a fire. 

Supplied power should be more or less than 2% of the rated power.

X

  If the power is supplied unevenly, a life span of the storage battery shortens. If the supplied power is more than 4 % of the rated power, 

the unit terminates and indicates errors to protect it.

Make sure the interior power supply shouldn’t be over the maximum voltage or under the minimum voltage.

X

  Otherwise, it could result in malfunction of the unit due to damaged electrical components or decreased function of components.

Only use copper wire as the power cable and all wiring, components and materials should comply with the applicable local and 
national codes.

Make sure that all wiring is properly installed.

X

  Otherwise, the unit can be heated and cause a fire.

Never use the pipe and flare parts for R-22 refrigerant.

In case of a refrigerant gas leakage during installation, please ventilate the area.

X

  If refrigerant gas combines with inflammable materials, toxic gases can be generated.

The electric work must be done by service agent or qualified persons according to national wiring regulations and use only rated 
cable.

X

  Voltage drop, shortage of power supply, improper electric work and using unapproved wires can cause an electric shock or a fire.

FOR INSTALLATION

CAUTION

Make sure to earth.

X

  Do not connect the earth wire to the gas pipe, lighting rod or telephone wire.

X

  If earthing is incomplete, electric shock or fire may occur.

Make sure that the condensed water from the drain hose runs out properly based on this installation manual and insulate the 
drain pipe so that frost does not generate.

X

  If the draining work is done incompletely, property damage may occur due to a leakage.

Install the power cable and communication cable of MCU at least 1m away from the electric appliances and at least 2m away 
from the lightning rod.

X

  However, you may hear a noise 1 meter away from the unit depending on the condition of the electric wave.

Install MCU away from lighting apparatus using the ballast.

X

  If you use the wireless remote control, it may not operate normally.

Do not install the unit in following places.

X

 

The place packed with mineral oil and the place where there are lots of moisture, or arsenic acid:

 

The resin parts may burn and cause the fall of the components or a refrigerant leakage.

X

 

The place where corrosive gas such as sulfurous acid gas generates from the vent pipe or air outlet:

 

The copper pipe or connection pipe may corrode and refrigerant may leak.

X

 

The place where there is a machine that generates electromagnetic waves:

 

The unit may not operate normally due to malfunction in the control system.

X

 

The place where there is a possibility of combustible gas leakage, and where inflammable materials like thinner or gasoline is 
handled. The place where a carbon fiber or inflammable dust is floating in the air:

 

If the gas leaks and stays around the main valve, it may result in a fire.

X

 

The places where have a possibility of the MCU corrosion like a spa and a shore.

When there is a possibility that the place in which MCU is installed could be the shelter of small animals, take proper measures to 
prevent this situation in advance.

X

  If small animals contact the unit, this may result in malfunction of the unit or cause a fire and smoke. Please remind users of cleaning the 

place around MCU.

K

 Any claims caused by failing to keep the safety precautions are installer’s responsibility.  

(The installer is responsible for the service cost.)

Safety precautions

tj|Tz]ullXu†pt†luGWZ[`WhTW]U•‹‹GGG[

YWX\TW`TX^GGG㝘㤸GXWa\Za[[

Содержание MCU-S2NEK1N

Страница 1: ...tj Tz ullXu pt luGWZ WhTW U GGGY YWX TW TX GGG㝘㤸GXWa Za ...

Страница 2: ...EE2N MCU S2NEK1N MCU installation manual imagine the possibilities Thank you for purchasing this Samsung product This manual is made with 100 recycled paper DB68 03490A 06 EN ZH tj Tz ullXu pt luGWZ WhTW U GGGY YWX TW TX GGG㝘㤸GXWa Za ...

Страница 3: ...precautions 3 Preparing the installation 5 Space requirements 7 Installing the unit 8 Refrigerant piping works 11 Wiring works 13 Commisioning 21 Contents tj Tz ullXu pt luGWZ WhTW U GGGY YWX TW TX GGG㝘㤸GXWa Za ...

Страница 4: ...ck out the safety precautions below before installing or fixing the unit X Before welding the unit you must remove all the hazardous materials around the unit that may cause an explosion and a fire X When refrigerant is in the product or the pipe before welding the unit you must remove the refrigerant If you weld the unit when there is refrigerant inside the increased pressure of refrigerant may ex...

Страница 5: ...t does not generate X If the draining work is done incompletely property damage may occur due to a leakage Install the power cable and communication cable of MCU at least 1m away from the electric appliances and at least 2m away from the lightning rod X However you may hear a noise 1 meter away from the unit depending on the condition of the electric wave Install MCU away from lighting apparatus u...

Страница 6: ...Accessories For pipes larger than Ø 19 05mm 3 4 drawn type C1220T 1 2H or C1220T H type copper pipe must be used If an annealed type C1220T O copper pipe is used pipe may break due to its low pressure resistance and cause personal injury Outerdiameter Minimumthickness Tempergrade mm inch mm inch 6 35 1 4 0 70 0 028 Annealed 9 52 3 8 0 70 0 028 12 70 1 2 0 80 0 031 15 88 5 8 1 00 0 039 19 05 3 4 0 ...

Страница 7: ...ption MCU S6NEE1N Below 6 indoor units below 56 kW 192MBH MCU S4NEE1N Below 4 indoor units below 56 kW 192MBH MCU S4NEE2N Below 2 large capacity indoor unit below 56 kW 192MBH MCU S2NEK1N Below 2 indoor units below 28 kW 96MBH Gas pipe connected to indoor unit Liquid pipe connected to indoor unit Side view of MCU ø 28 58 ø 1 1 8 ø 19 05 ø 3 4 ø 15 88 ø 5 8 nipple ø 12 7 ø 1 2 nipple ø 9 52 ø 3 8 n...

Страница 8: ...re MCU is installed should be coated with qualityTex that has a good soundproof function X Minimize the size of the hole between the walls and the pipe connection After the installation block the gap to prevent noise from leaking Living area Living area Living area Bulkhead Living area Hallway MCU MCU Hallway Spaces with developed ceiling Ceiling of the office 4 Secure over 0 25m 0 82 of space whe...

Страница 9: ...E1N MCU S4NEE2N MCU S2NEK1N Exterior of MCU Number of connectable indoor units Up to 6 units Up to 4 units Up to 2 units Refer to the detail information of installation Up to 2units Maximum capacity of connectable indoor units 56 kW 192MBH 56 kW 192MBH 56 kW 192MBH 28 kW 96MBH Internal EEV Not inluded Cannot connect indoor unit without internal EEV Ceiling tex Ceiling concrete MCU 1 5m 5 or less 1...

Страница 10: ...equired operations on the indoor unit Model MCU S6NEE1N MCU S4NEE1N MCU S4NEE2N MCU S2NEK1N Example installing Installation Condition Singlecapacityrange10kW 30MBH orunder Connecttheliquid gaspipeofindoorunittoasingleportinMCU 11 2 14kW 36 48MBH UseY Joint Theindoorunit scapacityof20 kw 60MBH orover mustusethe appropriateMCU Applywhenconnectingtheindoor unit scapacityofover11 2kW 36MBH UseY Joint ...

Страница 11: ...t be connected in series 70mm 70mm 4 Cautions about MCU installation X When fixing the unit at the upper place using suspension bolts use a nut and washer to vertically fasten the unit X There are four spots to fix the suspension bolts Make sure every spot is fixed X The upper and the lower side of MCU is distinguished so be careful not to turn the unit upside down when installing the unit Otherwi...

Страница 12: ...er than one month Taping Inside exposure Taping Brazing part Nitrogen gas 1 4 copper pipe Stop valve Taping Pressure regulator Flowmeter Insulation cover pipe Indoor unit Be sure to overlap the insulation Insulation pipe Method and cautions on refrigerant pipe insulation Make sure to check for gas leakage before completing the installation hose and pipe insulation and insulate hoses and pipes when...

Страница 13: ...25 1 38 1 1 2 RefrigerantpipebeforeEEVkitandMCUorwithoutEEVkitandMCU f You can contact the gas side and liquid side pipes but the pipes should not be pressed f When contacting the gas side and gas side pipe use 1 grade thicker insulator Refrigerant pipe after EEV kit and MCU f Install the gas side and liquid side pipes leave 10mm 3 8 of space f When contacting the gas side and liquid side pipe use...

Страница 14: ...stalling the circuit breaker and wires Powersupply MCCB ELB Powercable Earthcable Communicationcable Max 242V Min 198V X A X A 30mmA 0 1 sec 0 0039inch2 2 5mm2 0 0039inch2 2 5mm2 0 0012 0 0023inch2 0 75 1 5mm2 The capacity of ELB MCCB X A 1 25 X 1 1 X Ai X Decide the capacity of ELB and MCCB by below formula X Decide the power cable specification and maximum length within 10 power drop among indoo...

Страница 15: ...nch2 4 0mm2 f Apply following equation Coef 35 6 LK iK 10 of input voltage V 1000 AK n k 1 Indoor unit Power supply MCCB A ELB A Power cable mm2 Earth cable mm2 Communication cable mm2 DVM Hydro unit 1Ø 220 240 V 50 Hz Max 264 V Min 198 V X A X A 30 mA 0 1 sec 0 0039 inch2 2 5 mm2 Single Installation 0 0039 inch2 2 5 mm2 0 0012 0 0023 inch2 0 75 1 5 mm2 DVM Hydro unit HT 1Ø 220 240 V 50 Hz Max 264...

Страница 16: ...n drawing Input socket X Power Line and communication line must be installed as shown in drawing Case 1 Indoor Unit Indoor Unit Outdoor Unit ELB MCCB 220 240V 208 230V Supply separately Case 2 Indoor Unit Indoor Unit Outdoor Unit ELB MCCB 220 240V 208 230V Supply separately Hole for indoor unit power supply Upto 2 indoor units per 1 hole Hole for MCU main power supply Hole for communication tj Tz ...

Страница 17: ...0 3 0 011 0 2 0 007 d1 Standard dimension mm inch 1 7 0 066 2 3 0 090 3 4 0 133 Allowance mm inch 0 2 0 007 0 0 2 0 007 0 0 2 0 007 0 E Min mm inch 4 1 0 161 6 0 236 6 0 236 F Min mm inch 6 0 236 6 0 236 5 0 196 L Max mm inch 16 0 629 17 5 0 688 20 0 787 d2 Standard dimension mm inch 4 3 0 169 4 3 0 169 4 3 0 169 Allowance mm inch 0 2 0 007 0 0 2 0 007 0 0 2 0 007 0 t Min mm inch 0 7 0 027 0 8 0 0...

Страница 18: ...ESS on the MCU PCB same as the ADDRESS of connected indoor unit X When installing more than 2 MCU set each rotary switch for MCU ADDRESS properly 012 3 4 5 6 7 8 9 A B C D E F Indoor Unit Indoor Unit MCU PCB MCU PCB Setting the number of Indoor Unit Setting the number of MCU Indoor Unit ADDRESS Outdoor Unit PCB MCU ADDRESS MCU ADDRESS Indoor Unit ADDRESS MCU DIP S W MCU DIP S W MCU PCB MCU DIP S W...

Страница 19: ...unit Indoorunit Indoorunit Indoorunit Indoorunit Indoorunit Indoorunit Indoorunit Indoorunit Indoorunit Indoorunit MCU MCU Communication cables are connected as shown above when installing MCU When installing electricity and wires of MCU please proceed the work refering to the installation manual of the HR outdoor unit X Address on the rotary switch at the MCU PCB and the rotary switch on the indo...

Страница 20: ... 13 On Off for solenoid valve C_C C_H C 14 On Off for solenoid valve D_C D_H D 15 On Off for solenoid valve E_C E_H E 16 On Off for solenoid valve F_C F_H F 17 On Off for liquid by pass solenoid valve G Blank 0 N Ex On 0 F F Ex Off 18 Version 8 A 2 0 Ex October 20 2008 p 8A 20 19 End of K1 display K2 Pushedtime DisplayContents Displaysegment Remarks 1 2 3 4 1 Indoor unit main address for matching ...

Страница 21: ...P A 1 0 2 A_H sol valve ON other sol valve Off P A 0 1 3 B_C sol valve ON other sol valve Off P B 1 0 4 B_H sol valve ON other sol valve Off P B 0 1 5 C_C sol valve ON other sol valve Off P C 1 0 6 C_H sol valve ON other sol valve Off P C 0 1 7 D_C sol valve ON other sol valve Off P D 1 0 8 D_H sol valve ON other sol valve Off P D 0 1 9 E_C sol valve ON other sol valve Off P E 1 0 10 E_H sol valve...

Страница 22: ...or not 5 Checking malfunction of the wire and the communication line 6 If the MCU frame has been installed upside down or not 7 If the wire earthing work has been done or not 8 If the space between sidewalls ceiling concrete and the ceilingTex has been secured enough or not to install the MCU frame 9 If the supporting tool of the MCU pipe has been safely placed in 1 5m intervals or not 10 If the p...

Страница 23: ...22 Memo tj Tz ullXu pt luGWZ WhTW U GGGYY YWX TW TX GGG㝘㤸GXWa Za ...

Страница 24: ...ENGLISH 23 Memo tj Tz ullXu pt luGWZ WhTW U GGGYZ YWX TW TX GGG㝘㤸GXWa Za ...

Отзывы: