ENGLISH

3

Safety precautions

The safety information and precautions below must be kept for the safety of users and installers.

K

  After installation and trial operation, explain to the customer how to use the air conditioner and give the installation manual 

to the user.

K

  The manufacturer is not responsible for accidents due to incorrect installation. Any claims caused by failing to keep the safety 

precautions are installer’s responsibility. (The installer is responsible for the service cost.)

WARNING

In case of not following the safety precautions, the service agent or the user may get the risk of 
serious wound or death.

CAUTION

In case of not following the safety precautions, the service agent or the user may get the risk of 
injury or loss of property.

FOR INSTALLATION

WARNING

Installation must be done by the installer or its service agent.

X

  Installation by an unqualified person may cause a water leakage, electric shock or fire and so on.

Install the unit correctly according to the installation manual.

X

  An incorrect installation may cause a water leakage, electric shock or fire.

When installing the unit in a small place, take measures in order to keep the refrigerant concentration from exceeding allowable 
safety limits in the event of a refrigerant leak.

X

  Excessive refrigerant concentration can lead to suffocation.

If any gas or impurities except R-410A refrigerant get into the refrigerant pipe, serious problems may occur and this may cause 
injury.

When installing the unit, only use the components and tools which are specified for the installation.

X

  Using the uncertified components and tools may cause a unit fall, water leakage, electric shock, and a fire. 

(Never use the components and pipe for R-22 refrigerant)

Install the unit safely on a place that can support its weight.

X

  If the place cannot support its weight, the unit may fall down and cause injury.

Check out the safety precautions below before installing or fixing the unit.

X

  Before welding the unit, you must remove all the hazardous materials around the unit that may cause an explosion and a fire. 

X

  When refrigerant is in the product or the pipe before welding the unit, you must remove the refrigerant. 

-  If you weld the unit when there is refrigerant inside, the increased pressure of refrigerant may explode or break the leaking spot so that 

causes serious injuries.

X

  When welding the unit, please use nitrogen gas to prevent oxide from generating in the pipe 

Make sure to cut off all the power supply before installing, fixing, and cleaning the unit.

When the electric wire is damaged, you must exchange it by the manufacturer or its service agent, or a person who has the 
equivalent qualification. 

When turning on the power, make sure to connect the power supply to the circuit breaker designated for indoor units. (ELCB, 
ELB, MCCB) 

X

  If you do not install the circuit breaker for MCU(ELCB, ELB, MCCB), excessive current or failure to blocking the power supply may cause 

electric shock, a fire.  

 

Before installing an air conditioner, please read this manual thoroughly to ensure that you know how to safely and 
efficiently install a new appliance.

J

  DVM S air conditioner uses R-410A refrigerant.

 

-  When using R-410A, moisture or foreign substances may affect the capacity and reliability of the product.  

Safety precautions must be taken when installing the refrigerant pipe. 

 

-  The designing pressure of the system is 4.1MPa. Select appropriate material and thickness according to the regulations. 

 

-  R-410A is a quasi-azeotrope of  two refrigerants.  

Make sure to charge with liquid phase when filling refrigerant.  
If you charge gaseous refrigerant, it may affect the capacity and reliability of the product as a result of change 
formation of the refrigerant.

J

  Connect the indoor units for R-410A refrigerant. Check whether the indoor units can be connected with the product’s 

catalogue. (When incorrect indoor units are connected, they cannot operate normally.)

tj|Tz]ullXu†pt†luGWZ[`WhTW]U•‹‹GGGZ

YWX\TW`TX^GGG㝘㤸GXWa\Za[[

Содержание MCU-S2NEK1N

Страница 1: ...tj Tz ullXu pt luGWZ WhTW U GGGY YWX TW TX GGG㝘㤸GXWa Za ...

Страница 2: ...EE2N MCU S2NEK1N MCU installation manual imagine the possibilities Thank you for purchasing this Samsung product This manual is made with 100 recycled paper DB68 03490A 06 EN ZH tj Tz ullXu pt luGWZ WhTW U GGGY YWX TW TX GGG㝘㤸GXWa Za ...

Страница 3: ...precautions 3 Preparing the installation 5 Space requirements 7 Installing the unit 8 Refrigerant piping works 11 Wiring works 13 Commisioning 21 Contents tj Tz ullXu pt luGWZ WhTW U GGGY YWX TW TX GGG㝘㤸GXWa Za ...

Страница 4: ...ck out the safety precautions below before installing or fixing the unit X Before welding the unit you must remove all the hazardous materials around the unit that may cause an explosion and a fire X When refrigerant is in the product or the pipe before welding the unit you must remove the refrigerant If you weld the unit when there is refrigerant inside the increased pressure of refrigerant may ex...

Страница 5: ...t does not generate X If the draining work is done incompletely property damage may occur due to a leakage Install the power cable and communication cable of MCU at least 1m away from the electric appliances and at least 2m away from the lightning rod X However you may hear a noise 1 meter away from the unit depending on the condition of the electric wave Install MCU away from lighting apparatus u...

Страница 6: ...Accessories For pipes larger than Ø 19 05mm 3 4 drawn type C1220T 1 2H or C1220T H type copper pipe must be used If an annealed type C1220T O copper pipe is used pipe may break due to its low pressure resistance and cause personal injury Outerdiameter Minimumthickness Tempergrade mm inch mm inch 6 35 1 4 0 70 0 028 Annealed 9 52 3 8 0 70 0 028 12 70 1 2 0 80 0 031 15 88 5 8 1 00 0 039 19 05 3 4 0 ...

Страница 7: ...ption MCU S6NEE1N Below 6 indoor units below 56 kW 192MBH MCU S4NEE1N Below 4 indoor units below 56 kW 192MBH MCU S4NEE2N Below 2 large capacity indoor unit below 56 kW 192MBH MCU S2NEK1N Below 2 indoor units below 28 kW 96MBH Gas pipe connected to indoor unit Liquid pipe connected to indoor unit Side view of MCU ø 28 58 ø 1 1 8 ø 19 05 ø 3 4 ø 15 88 ø 5 8 nipple ø 12 7 ø 1 2 nipple ø 9 52 ø 3 8 n...

Страница 8: ...re MCU is installed should be coated with qualityTex that has a good soundproof function X Minimize the size of the hole between the walls and the pipe connection After the installation block the gap to prevent noise from leaking Living area Living area Living area Bulkhead Living area Hallway MCU MCU Hallway Spaces with developed ceiling Ceiling of the office 4 Secure over 0 25m 0 82 of space whe...

Страница 9: ...E1N MCU S4NEE2N MCU S2NEK1N Exterior of MCU Number of connectable indoor units Up to 6 units Up to 4 units Up to 2 units Refer to the detail information of installation Up to 2units Maximum capacity of connectable indoor units 56 kW 192MBH 56 kW 192MBH 56 kW 192MBH 28 kW 96MBH Internal EEV Not inluded Cannot connect indoor unit without internal EEV Ceiling tex Ceiling concrete MCU 1 5m 5 or less 1...

Страница 10: ...equired operations on the indoor unit Model MCU S6NEE1N MCU S4NEE1N MCU S4NEE2N MCU S2NEK1N Example installing Installation Condition Singlecapacityrange10kW 30MBH orunder Connecttheliquid gaspipeofindoorunittoasingleportinMCU 11 2 14kW 36 48MBH UseY Joint Theindoorunit scapacityof20 kw 60MBH orover mustusethe appropriateMCU Applywhenconnectingtheindoor unit scapacityofover11 2kW 36MBH UseY Joint ...

Страница 11: ...t be connected in series 70mm 70mm 4 Cautions about MCU installation X When fixing the unit at the upper place using suspension bolts use a nut and washer to vertically fasten the unit X There are four spots to fix the suspension bolts Make sure every spot is fixed X The upper and the lower side of MCU is distinguished so be careful not to turn the unit upside down when installing the unit Otherwi...

Страница 12: ...er than one month Taping Inside exposure Taping Brazing part Nitrogen gas 1 4 copper pipe Stop valve Taping Pressure regulator Flowmeter Insulation cover pipe Indoor unit Be sure to overlap the insulation Insulation pipe Method and cautions on refrigerant pipe insulation Make sure to check for gas leakage before completing the installation hose and pipe insulation and insulate hoses and pipes when...

Страница 13: ...25 1 38 1 1 2 RefrigerantpipebeforeEEVkitandMCUorwithoutEEVkitandMCU f You can contact the gas side and liquid side pipes but the pipes should not be pressed f When contacting the gas side and gas side pipe use 1 grade thicker insulator Refrigerant pipe after EEV kit and MCU f Install the gas side and liquid side pipes leave 10mm 3 8 of space f When contacting the gas side and liquid side pipe use...

Страница 14: ...stalling the circuit breaker and wires Powersupply MCCB ELB Powercable Earthcable Communicationcable Max 242V Min 198V X A X A 30mmA 0 1 sec 0 0039inch2 2 5mm2 0 0039inch2 2 5mm2 0 0012 0 0023inch2 0 75 1 5mm2 The capacity of ELB MCCB X A 1 25 X 1 1 X Ai X Decide the capacity of ELB and MCCB by below formula X Decide the power cable specification and maximum length within 10 power drop among indoo...

Страница 15: ...nch2 4 0mm2 f Apply following equation Coef 35 6 LK iK 10 of input voltage V 1000 AK n k 1 Indoor unit Power supply MCCB A ELB A Power cable mm2 Earth cable mm2 Communication cable mm2 DVM Hydro unit 1Ø 220 240 V 50 Hz Max 264 V Min 198 V X A X A 30 mA 0 1 sec 0 0039 inch2 2 5 mm2 Single Installation 0 0039 inch2 2 5 mm2 0 0012 0 0023 inch2 0 75 1 5 mm2 DVM Hydro unit HT 1Ø 220 240 V 50 Hz Max 264...

Страница 16: ...n drawing Input socket X Power Line and communication line must be installed as shown in drawing Case 1 Indoor Unit Indoor Unit Outdoor Unit ELB MCCB 220 240V 208 230V Supply separately Case 2 Indoor Unit Indoor Unit Outdoor Unit ELB MCCB 220 240V 208 230V Supply separately Hole for indoor unit power supply Upto 2 indoor units per 1 hole Hole for MCU main power supply Hole for communication tj Tz ...

Страница 17: ...0 3 0 011 0 2 0 007 d1 Standard dimension mm inch 1 7 0 066 2 3 0 090 3 4 0 133 Allowance mm inch 0 2 0 007 0 0 2 0 007 0 0 2 0 007 0 E Min mm inch 4 1 0 161 6 0 236 6 0 236 F Min mm inch 6 0 236 6 0 236 5 0 196 L Max mm inch 16 0 629 17 5 0 688 20 0 787 d2 Standard dimension mm inch 4 3 0 169 4 3 0 169 4 3 0 169 Allowance mm inch 0 2 0 007 0 0 2 0 007 0 0 2 0 007 0 t Min mm inch 0 7 0 027 0 8 0 0...

Страница 18: ...ESS on the MCU PCB same as the ADDRESS of connected indoor unit X When installing more than 2 MCU set each rotary switch for MCU ADDRESS properly 012 3 4 5 6 7 8 9 A B C D E F Indoor Unit Indoor Unit MCU PCB MCU PCB Setting the number of Indoor Unit Setting the number of MCU Indoor Unit ADDRESS Outdoor Unit PCB MCU ADDRESS MCU ADDRESS Indoor Unit ADDRESS MCU DIP S W MCU DIP S W MCU PCB MCU DIP S W...

Страница 19: ...unit Indoorunit Indoorunit Indoorunit Indoorunit Indoorunit Indoorunit Indoorunit Indoorunit Indoorunit Indoorunit MCU MCU Communication cables are connected as shown above when installing MCU When installing electricity and wires of MCU please proceed the work refering to the installation manual of the HR outdoor unit X Address on the rotary switch at the MCU PCB and the rotary switch on the indo...

Страница 20: ... 13 On Off for solenoid valve C_C C_H C 14 On Off for solenoid valve D_C D_H D 15 On Off for solenoid valve E_C E_H E 16 On Off for solenoid valve F_C F_H F 17 On Off for liquid by pass solenoid valve G Blank 0 N Ex On 0 F F Ex Off 18 Version 8 A 2 0 Ex October 20 2008 p 8A 20 19 End of K1 display K2 Pushedtime DisplayContents Displaysegment Remarks 1 2 3 4 1 Indoor unit main address for matching ...

Страница 21: ...P A 1 0 2 A_H sol valve ON other sol valve Off P A 0 1 3 B_C sol valve ON other sol valve Off P B 1 0 4 B_H sol valve ON other sol valve Off P B 0 1 5 C_C sol valve ON other sol valve Off P C 1 0 6 C_H sol valve ON other sol valve Off P C 0 1 7 D_C sol valve ON other sol valve Off P D 1 0 8 D_H sol valve ON other sol valve Off P D 0 1 9 E_C sol valve ON other sol valve Off P E 1 0 10 E_H sol valve...

Страница 22: ...or not 5 Checking malfunction of the wire and the communication line 6 If the MCU frame has been installed upside down or not 7 If the wire earthing work has been done or not 8 If the space between sidewalls ceiling concrete and the ceilingTex has been secured enough or not to install the MCU frame 9 If the supporting tool of the MCU pipe has been safely placed in 1 5m intervals or not 10 If the p...

Страница 23: ...22 Memo tj Tz ullXu pt luGWZ WhTW U GGGYY YWX TW TX GGG㝘㤸GXWa Za ...

Страница 24: ...ENGLISH 23 Memo tj Tz ullXu pt luGWZ WhTW U GGGYZ YWX TW TX GGG㝘㤸GXWa Za ...

Отзывы: