background image

7

Indoor unit cable connection

f

f

After cutting off  the power of the indoor unit, connect the cable between the AC POWER terminal block of the indoor 
unit and the INDOOR POWER terminal block of the Multi Tenant Function Controller.

f

f

Connect the cable between the Commnunication/Power terminal block V1/V2 of the indoor unit and the V1/V2 of the 
Multi Tenant Function Controller, complying the correct voltage polarity.

If the cable is connected incorrectly, Multi Tenant Function Controller will not work properly. Furthermore, indoor unit 
communication error may occur and entire system may stop. 

f

f

Connect the DC power cable (5 V), which is included in the box, between the DOWNLOAD conenctor of the indoor unit 
and the DC 5 V connector of the Multi Tenant Function Controller.

If you cut the DC power cable (5 V) and extend it on your own, it may cause problem on the product.

f

f

To check the connection of the cable, disconnect the AC power cable of the indoor unit and supply the AC 24 V power. 
If the green LED of the Multi Tenant Function Controller turns on, cable is correctly connected.

If the green LED of the Multi Tenant Function Controller does not turn on, check if the polarity of the V1 and V2 are correct.

f

f

For the products with no V1 and V2 terminal block on the indoor units (such as RAC, 2WAY), connect the #1 wire (RED) of 
the 4P connector wire, connected to the communication SUB PCB, to the V1. (V2 connection is not required)

N

L

 AC power for an indoor unit

INDOOR POWER

F1

F2

V1 V2

F3

F4

Use UL Standard, Class 2, AC 24 V 
1 A electric transformer

AC 24 V

AC 24 V ±15 %

50/60 Hz

1 A

Indoor unit 

Download

Indoor unit

communication/power

DC powe

r cable (5 V)

Connecting power cable

1.  Make sure to cut-off  the power before connecting the power cable.
2.  Use appropriate tools to connect the cables fi rmly within rated torque range so that it can withstand external forces, and 

arrange the cables neatly so that cover or any other parts won't get loose.  When the connection is loose, there is risk of 
overheat, electric shock or fi re.

Tightening torque: 6 N•cm

CAUTION

•  Specifi cation of the compatible compressed terminal

Range of permitted wires

Rated size

Stud size

Basic size (mm)

AWG

mm

2

mm

2

mm

t

øD

G

E

F

W

L

22~16

0.25~1.65

1.5

3

0.7

3.8

10.0

4.5

6.5

6.0

21.2

W

t

G

E

F

L

Stud

D

보조전원 모듈_MCM-C21FR_03929A-06.indd   7

2016-04-21   오후 3:30:10

Содержание MCM-C210N

Страница 1: ...ner installation manual imagine the possibilities Thank you for purchasing this Samsung product Multi Tenant Function controller MCM C210 MCM C210N 보조전원 모듈_MCM C210_IM_EN FR_03929A 06 indd 11 2016 04 21 오후 3 30 11 ...

Страница 2: ...ATION CAUTION When connecting a wire do not tighten it too much f f Failure to do so may result in breakage of the wire Make sure the MultiTenant Function Controller installation doesn t cause interference with other electrical appliances particularly in a hospital etc f f Failure to do so may result in abnormal operation Do not install the product in an area where combustible gas leaks or possibl...

Страница 3: ...Assurez vous que le contrôleur de fonctions multi tenant ne provoque pas d interférence avec d autres appareils électriques en particulier dans un hôpital etc f f Le non respect de cette consigne risque de provoquer un dysfonctionnement N installez pas l appareil dans un emplacement présentant des fuites de gaz combustible ou s il existe un risque potentiel de fuite de gaz f f Le non respect de ce...

Страница 4: ...on of the Multi Tenant Function Controller and wiring work must be done in advance so that they can be connected to each other About protection box Protection box for the MultiTenant Function Controller must be purchased separately Installing the MultiTenant Function Controller within an Ingress Protection IP box or a box made of metal metrial is recommended Accessories Name MultiTenant Function C...

Страница 5: ...Download Circuit Breaker Fuse Not provided When installing a the AC 24 V transformer use a box or metal material with the same or higher level of fire retardant as the IP box You should close the gap around the place where wires are input so that any rodents or water cannot come into the box and then remove all the sharp surfaces AC 24V needs to be purchased at a local shop You should purchase a r...

Страница 6: ... entering The installation location of MultiTenant Function Controller box f f For ceiling type indoor unit the distance between an indoor unit and the MultiTenant Function Controller box should be within 3 m When the MultiTenant Function Controller is installed the MultiTenant Function Controller box should be fixed f f For wall mounted indoor unit the MultiTenant Function Controller box should b...

Страница 7: ... cable is correctly connected IfthegreenLEDoftheMultiTenantFunctionControllerdoesnotturnon checkifthepolarityoftheV1andV2arecorrect f f For the products with noV1 andV2 terminal block on the indoor units such as RAC 2WAY connect the 1 wire RED of the 4P connector wire connected to the communication SUB PCB to theV1 V2 connection is not required N L AC power for an indoor unit INDOOR POWER F1 F2 V1...

Страница 8: ... option f f To use the MultiTenant Function Controller installation option must be changed f f SEG2 of the installation option on installed indoor units must be set to 5 and SEG11 must be set to 2 SEG11 0 Disable MultiTenant Function Controller 2 Enable MultiTenant Function Controller For detail information on the method of setting the installation option please refer to the indoor unit installati...

Страница 9: ...rUnit 1 When installing one transformer with multiple MTFCs MultiTenant Function Controller AC220V AC220V AC24V N 1A Transformer MTFC MTFC N Numberof MTFC DC12V DC5V DC12V DC5V Comm IndoorUnit 2 IndoorUnit 1 f f When one transformer is installed with multiple MTFCs current capacity setting should be 1 A x number of MTFC 보조전원 모듈_MCM C210_IM_EN FR_03929A 06 indd 9 2016 04 21 오후 3 30 11 ...

Страница 10: ...보조전원 모듈_MCM C210_IM_EN FR_03929A 06 indd 10 2016 04 21 오후 3 30 11 ...

Отзывы: