Connect the cables to the terminal board with solderless ring terminals.
•
Properly connect the cables by using certified and rated cables and make sure to fix them properly so that
external force is not applied to the terminal.
•
Use a driver and wrench that can apply the rated torque when tightening the screws on the terminal board.
•
Tighten the terminal screws by complying rated torque value. If the terminal is loose, fire can occur due to arc
heat generation and if the terminal is too tight, terminal board could get damaged.
Power cable protection tube
The place where the sheath of the
power supply cable is removed.
Connector
Thin cable
Thick cable
When connecting two cables to one terminal,
separate the solderless terminal up and down to
prevent it from getting loose. Place the thin cable
upward and the thick cable downward. Fix the power
cable with a cable tie.
Solderless ring
terminal
Cable tie
1 Front connection
10. Installation
Connecting the power terminal
2 Closing the cover
CAUTION
•
When removing the outer sheath of the power supply cable, be careful not to scratch the inner sheath of the
cable.
•
Make sure that more than 20mm (0.79inch) of the outer sheath of the indoor unit power and communication
cable are inside the electrical component box.
•
Install the communication cable separately from power cable and other communication cables.
•
There is a risk of electric shock when power is applied. Close the cover of the control box before proceeding to
work.
•
To inspect the compressor or PBA, first make sure to turn off the system. Electricity may flow even in a
compressor that has not been used recently. Exercise caution to protect yourself from an electric shock.
Screw
Tightening torque for
terminal
Remarks
N·m
lbf·ft
M3.5
ߢߩߪड़ߣߣߪ
ߢߨड़ߢ߫
communication cable
M4
ߣߤड़ߣߪ
ߢ߫ड़ߣߥ
Ɗ̈͝˝̷ʪΧ˵ɇϑʪߤߢߪड़ߤߥߢǤΧͱиʪθʀɇɵ̷ʪ
M8
ߧߧड़ߩߥ
ߦߣड़ߧߦ