Model  : AM***BXVTFH/AA, AM***BXVTJH/AA

VRF

Technical 

Data Book

Max Heat DVM S2 for America

(R410A, 60Hz, HP)

Содержание Max Heat DVM S2

Страница 1: ...Model AM BXVTFH AA AM BXVTJH AA VRF Technical Data Book Max Heat DVM S2 for America R410A 60Hz HP...

Страница 2: ...Version Modification Date Remark Ver 1 0 Release Max Heat DVM S2 HP TDB for America 23 12 20 History...

Страница 3: ...ter 6 Feature 2 A Standard General Temp Module H High EER Low Temp Module G High EER General Temp Module D Standard General Temp Non Module 7 Rating Voltage 8 Mode H Heat Pump R Heat Recovery OutdoorU...

Страница 4: ...ligent features make installation and maintenance easier and more cost effective Perfectly compatible with WindFree Active Frequency Drive 10Hz Enjoy continuous comfort and avoid wasting energy Active...

Страница 5: ...st capacity It combines Flash Injection technology with a strengthened Triple Profile Scroll and efficient Optimal Discharge Superheat DSH Control technology Samsung circulates 14 400cc sec refrigeran...

Страница 6: ...Combination Table Design Procedure Combination Ratio 2 Specification 3 Electric Characteristics 4 Dimensional Drawing 5 Center of Gravity 6 Electrical Wiring Diagrams 7 Sound Data 8 Operation Range 9...

Страница 7: ...m design Refer to the Design Procedure Combination Ratio section of this document for details You can connect maximum 64 indoor units to the outdoor unit Maximum quantity of connectable indoor unit is...

Страница 8: ...dard allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50 130 Combination ratio of up to 184 is allowed depending on operation mode minimum oper...

Страница 9: ...ON Model Name Model 6 8 10 External Appearance 1 Combination Table Outdoor units AM072BXVTFH AA AM096BXVTFH AA AM120BXVTFH AA 12 14 16 AM144BXVTFH AA AM168BXVTFH AA 18 20 AM192BXVTFH1AA 22 AM264BXVTFH...

Страница 10: ...el 6 8 10 External Appearance 1 Combination Table Outdoor units AM072BXVTJH AA AM096BXVTJH AA AM120BXVTJH AA 12 14 16 AM144BXVTJH AA AM168BXVTJH AA 18 20 AM192BXVTJH1AA 22 AM264BXVTJH AA 24 AM288BXVTJ...

Страница 11: ...necessaryto design a combination ratio exceeding130 the following conditions must be complied with Design Selection Procedure Determine DVM Design Condition Design temperature Calculate cooling and he...

Страница 12: ...e Peak Loads at 14 00 61 0kW When a system combination ratio is over130 a max system capacity is the same as the published capacity in TDB capacity table at the combination ratio of 130 NOTE Cooling O...

Страница 13: ...capacity of indoor units running in both cooling heating mode 100 Sum of nominal capacity of indoor units The Minimum Operation Ratio should be determined during the project design stage using Fig 2...

Страница 14: ...including abnormal noise that arises during heating operation due solely to the operation rate being lower than the designated combination ratio shown in Fig 2 Please contact your local Samsung repre...

Страница 15: ...x 2 Inverter Scroll x 2 Output kW x n 4 39 x 2 6 45 x 2 6 45 x 2 Model Name DS2GT7046EV x 2 DS4GT5066EV x 2 DS4GT5066EV x 2 Oil Type PVE PVE PVE Initial charge cc x n 900 x 2 1 100 x 2 1 100 x 2 fl o...

Страница 16: ...the rated outdoor unit capacity is 50 130 Combination ratio of up to 184 is allowed depending on operation mode minimum operation ratio and connected indoor unit models DVM Pro 2 design software suppo...

Страница 17: ...oll x 4 Output kW x n 4 39 x 2 x 2 4 39 x 2 x 1 6 45 x 2 x 1 6 45 x 2 x 2 Model Name DS2GT7046EV x 2 x 2 DS2GT7046EV x 2 x 1 DS4GT5066EV x 2 x 1 DS4GT5066EV x 2 x 2 Oil Type PVE PVE PVE Initial charge...

Страница 18: ...The standard allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50 130 Combination ratio of up to 184 is allowed depending on operation mode min...

Страница 19: ...kW x n 4 39 x 2 x 3 4 39 x 2 x 2 6 45 x 2 x 1 4 39 x 2 x 2 6 45 x 2 x 1 Model Name DS2GT7046EV x 2 x 3 DS2GT7046EV x 2 x 2 DS4GT5066EV x 2 x 1 DS2GT7046EV x 2 x 2 DS4GT5066EV x 2 x 1 Oil Type PVE PVE...

Страница 20: ...ation ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50 130 Combination ratio of up to 184 is allowed depending on operation mode minimum operation ratio and con...

Страница 21: ...1 6 45 x 2 x 2 Model Name DS2GT7046EV x 2 x 1 DS4GT5066EV x 2 x 2 Oil Type PVE Initial charge cc x n 900 x 2 x 1 1 100 x 2 x 2 fl oz x n 30 4 x 2 x 1 37 2 x 2 x 2 Fan Type Propeller Dischargedirectio...

Страница 22: ...indoor unit models DVM Pro 2 design software supports designing over 130 based on system design Refer to the Design Procedure Combination Ratio section of this document for details 3 IIf outdoor unit...

Страница 23: ...erter Scroll x 2 Output kW x n 4 39 x 2 6 67 x 2 6 67 x 2 Model Name DS2GR7046FV x 2 DS4GR7066FV x 2 DS4GR7066FV x 2 Oil Type PVE PVE PVE Initial charge cc x n 900 x 2 1 100 x 2 1 100 x 2 fl oz x n 30...

Страница 24: ...he rated outdoor unit capacity is 50 130 Combination ratio of up to 184 is allowed depending on operation mode minimum operation ratio and connected indoor unit models DVM Pro 2 design software suppor...

Страница 25: ...Output kW x n 4 39 x 2 x 2 4 39 x 2 x 1 6 67 x 2 x 1 6 67 x 2 x 2 Model Name DS2GR7046FV x 2 x 2 DS2GR7046FV x 2 x 1 DS4GR7066FV x 2 x 1 DS4GR7066FV x 2 x 2 Oil Type PVE PVE PVE Initial charge cc x n...

Страница 26: ...he standard allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50 130 Combination ratio of up to 184 is allowed depending on operation mode minim...

Страница 27: ...4 39 x 2 x 3 4 39 x 2 x 2 6 67 x 2 x 1 4 39 x 2 x 2 6 67 x 2 x 1 Model Name DS2GR7046FV x 2 x 3 DS2GR7046FV x 2 x 2 DS4GR7066FV x 2 x 1 DS2GR7046FV x 2 x 2 DS4GR7066FV x 2 x 1 Oil Type PVE PVE PVE Ini...

Страница 28: ...ion ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50 130 Combination ratio of up to 184 is allowed depending on operation mode minimum operation ratio and conne...

Страница 29: ...ressor Type Inverter Scroll x 6 Output kW x n 4 39 x 2 x 1 6 67 x 2 x 2 Model Name DS2GR7046FV x 2 x 1 DS4GR7066FV x 2 x 2 Oil Type PVE Initial charge cc x n 900 x 2 x 1 1 100 x 2 x 2 fl oz x n 30 4 x...

Страница 30: ...ndoor unit models DVM Pro 2 design software supports designing over 130 based on system design Refer to the Design Procedure Combination Ratio section of this document for details 3 IIf outdoor unit i...

Страница 31: ...76 0 90 0 4 2 4 2 76 0 90 0 Capacity Model Name Power Supply Module 1 Module 2 Module 3 FLA A MCA A MOP A FLA A MCA A MOP A FLA A MCA A MOP A TON Hz Voltage FAN1 FAN2 FAN1 FAN2 FAN1 FAN2 6 AM072BXVTJ...

Страница 32: ...Liquid Ref pipe See NOTE 4 6 Knock out Hole forRef Piping front 3 Powerwiring conduit 44 4 Communication wiring conduit 34 NOTE 1 Detail A and SECTION B B indicate the dimension after fixing the attac...

Страница 33: ...Outdoorunit 5 Centerof Gravity C A Foundation bolt hole B Model A B C Unit mm inches AM072BXVT H AA AM096BXVT H AA AM120BXVT H AA 324 12 3 4 520 20 1 2 678 26 11 16...

Страница 34: ...RSSOR2 Motor compressor2 AIR 10K Thermistor Ambient Temp _10Kohm OD EEV V V Electronic expansion valve Outdoor EEV FAN1 Motor fan1 COND 10K Thermistor Cond Out Temp _10Kohm F101 FUSE INV PCB FAN2 Moto...

Страница 35: ...ermistor Ambient Temp _10Kohm OD EEV V V Electronic expansion valve Outdoor EEV COMPRSSOR2 Motor compressor2 AIR 10K Thermistor Cond Out Temp _10Kohm F101 FUSE INV PCB FAN1 Motor fan1 COND 10K Thermis...

Страница 36: ...NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC15 90 85 80 75 65 60 55 50 45 40 35 30 25 20 15 10 5 0 63 250 125 500 2000 1000 8000 4000 Silent 3 Hearing threshold Silent 2 Silent 1 Cooling Heatin...

Страница 37: ...eshold Silent 2 Silent 1 Cooling Heating 90 85 80 75 65 60 55 50 45 40 35 30 25 20 15 10 5 0 NC 70 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC15 8000 90 85 80 75 65 60 55 50 45 40 35 30 2...

Страница 38: ...Center Frequency Hz NC 70 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70...

Страница 39: ...50 500 1000 2000 4000 8000 A Sound Power Level dB Octave Band Center Frequency Hz 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110 A NC 70 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 3...

Страница 40: ...cooling operating is possible under expand operational range only for HR system 4 In case of heatlng mode operating is possible underwarming up operation range However continus opearting is impossibl...

Страница 41: ...Outdoor temperature F DB 0 99 Capacity coef cient of outdoor unit on defrost operation 0 98 0 96 0 95 0 91 0 88 0 86 0 91 1 00 On heating operation frost can be formed on heat exchanger according to...

Страница 42: ...r Suction pipe T_S Pressure Sensor Low PS_L Pressure SolenoidValve Sensor SolenoidValve 4Way2 V_4W2 High1 4Way V_4W PS_H1 CheckValve Solenoid Valve Discharge1 CV_D2 HotGasbypass CV_D1 V_HG Solenoid Va...

Страница 43: ...1 Do not install the product in a place where it is directly exposed to sea water and sea breeze Make sure to install the product behind a structure such as building that can block see breeze Even whe...

Страница 44: ...an area with weak electromagnetic waves and put the main power cable and communication cables in a separately installed protection tube Make sure that there is no equipment that generates electromagne...

Страница 45: ...ecause the refrigerant running of MCU may create noise Outdoor unit space requirements Space requirement was decided based on following conditions Cooling mode outdoor temperature of 35 C 95 F Larger...

Страница 46: ...n value h1 h2 additional clearance h1 2 h2 2 Half of the exceeded height should be added to the service space S1 S2 Unit mm inch Case 3 Over 500 20 Over 500 20 Over 600 24 Over100 4 Over100 4 Over100...

Страница 47: ...listed in above table and do not use imitated accessories Classification Model Name Specification MBH kW Y Joint Only H R MXJ YA1500M 76 and below 22 4 and below MXJ YA2500M MXJ YA3100M MXJ YA3800M O...

Страница 48: ...the wind speed of 30m s If you cannot fix the outdoor unit on the base ground fix it by side or use extra structure 5 In heating operation defrost water may form so you must really care about the dra...

Страница 49: ...for connecting the anti vibration pad Unit mm inch Base ground Hbeamoranti vibration frame Over 200 8 Over 200 8 Over 50 2 Outdoorunitinstallation Unit mm inch Classification DVM S2 Large type A 1 295...

Страница 50: ...ear the installation space When the outdoor unit is installed on the roof check the strength and waterproof status of the roof Unit mm inch 960 37 80 760 29 92 100 3 94 80 3 15 80 3 15 80 3 15 6 0 120...

Страница 51: ...r unit on the rooftop check the strength and make sure to waterproof the rooftop Construct draining pit around the base construction and pay attention to the drainage around the outdoor unit Condensat...

Страница 52: ...gn substance may enter into the product and there could be a risk of personal injury Wear protection equipment at all times when making galvanized sheet metal duct since the orker may get injured by t...

Страница 53: ...ay accumulate if the area of the frame or the base ground is larger hh Installing the outdoor unit in windy region In windy regions such as near sea shores protection wall or wind protection duct must...

Страница 54: ...52 36 558 21 97 871 34 29 2413 95 345 13 58 723 28 46 723 28 46 464 18 27 180 7 09 980 38 58 668 26 3 532 20 94 567 22 32 765 30 12 540 21 26 180 7 09 953 37 52 1123 44 21 2271 89 41 1150 45 28 1632 6...

Страница 55: ...erant pipe and there shouldn t be any harmful ion oxide dust iron content or moisture inside pipe Use tools and accessories that fit on R 410A only Installation process Compatibilitywith Tool purpose...

Страница 56: ...igerant pipe according to main pipe size of each outdoor unit capacity When the pipe length including elbow between an outdoor unit and the farthest indoor unit exceeds 90m 295ft you must increase the...

Страница 57: ...ed to the outdoor unit A apply the pipe size A Indoorunit capacity MBH Indoorunit capacity kW Branchpipelengthwithin 148ft 45m Branchpipelengthbetween 148ft 295ft 45 90m Liquid Gas Liquid Gas inch mm...

Страница 58: ...9 52 3 8 50 164 12 7 1 2 200 656 12 9 52 3 8 30 98 12 7 1 2 160 525 14 12 7 1 2 90 295 15 88 5 8 200 656 16 12 7 1 2 90 295 15 88 5 8 200 656 18 12 7 1 2 80 262 15 88 5 8 200 656 20 12 7 1 2 60 197 1...

Страница 59: ...harging is 0 0067lb ft 0 01kg m regardless of the pipe size 1 2 5m 16 4 1 2 5m 16 4 1 2 5m 16 4 1 4 5m 16 4 1 4 10m 32 8 1 4 15m 49 2 3 8 10m 32 8 3 8 10m 32 8 3 8 10m 32 8 3 8 10m 32 8 1 4 5m 16 4 3...

Страница 60: ...nding AM NFDCH AM NGDCH 0 26 0 12 0 49 0 22 0 49 0 22 0 71 0 32 0 71 0 32 Ceiling AM NCDCH 0 86 0 39 0 86 0 39 1 23 0 56 2 09 0 95 MPAHU V AHU AM NZDCH 0 73 0 33 1 10 0 50 1 10 0 50 1 83 0 83 1 94 0 8...

Страница 61: ...d pipe 6 35 1 4 35 114 8 0 02 0 013 0 7 1 49 5 575 12 19 9 52 3 8 50 164 0 0 06 0 040 3 0 6 56 12 70 1 2 15 49 2 0 125 0 084 1 875 4 13 Classification Model name of indoorunit Numberofindoorunits Unit...

Страница 62: ...re to prevent any damages on the exterior of the outdoor unit Remove all burrs around the knock out hole and apply varnish on the cross section and edges of the knock out hole to prevent rust Use a ca...

Страница 63: ...the sealed pipe on the bottom side of the service valve cut it with a pipe cutter rst and then start the welding When the sealed pipe is welded without cutting you may get injured by the refrigerant w...

Страница 64: ...tdoor units Check the changes in comparison with the DVM and Caution Correct installation Incorrect installation Refrigerant pipes should be connected at the same orlower level than the ones connected...

Страница 65: ...Refrigerantpipeinstallation 10 Installation Examples of refrigerant pipe installation 1 Using Y joint 2 Usingdistribution header...

Страница 66: ...ribution header a b c d e f g h i j k Installing only with distribution header a b c d e f g h i Outdoor Outdoor unit Module installation Pipe length 10 m 33 or less x z y Equivalent length 13 m 43 or...

Страница 67: ...Y joint and distribution header Installing only with distribu tion header Note1 Required conditions must be satisfied EEV kit Model name Remarks kk Actual pipe length 2m 6 6 MEV E24SA 1 indoor Apply t...

Страница 68: ...e connection welding Liquid pipe connection welding 70 mm When installing MCU use the pattern sheet for installation that is provided with the product When welding the gas pipes protect the product wi...

Страница 69: ...4 2 4 2 50 60 18 18 4 2 4 2 50 60 28 28 4 2 4 2 76 90 24Ton AM288BXVTF 60 208 230 18 18 4 2 4 2 50 60 22 22 4 2 4 2 62 70 28 28 4 2 4 2 76 90 Module 1 Module 2 Nom Units RLA FLA Power Supply RLA FLA...

Страница 70: ...r o not use the ower cable with the core wire e osed due to insulator damage occurred during remo al of the sheath hen the core wire is e osed it ma cause fire Insulator innercover Exposedwire core Th...

Страница 71: ...n the illustration Name Tempergrade Applicable conditions When the protection tube is installed indoorand not exposed to outside because it is embedded in concrete structure Flexible PVC conduit PVC W...

Страница 72: ...er checking that R S T 3 phase 3 wire is properly connected Malfunction may occur if one or more of the wires among R S T phases 3 Phases 3 Wires are not connected properly Malfunction Turing on off o...

Страница 73: ...2 17 5 1 2 Allowance mm inch 0 3 0 011 0 2 0 007 0 3 0 011 0 2 0 007 0 3 0 011 0 2 0 007 0 5 0 019 0 2 0 007 0 5 0 019 0 2 0 007 0 5 0 019 0 2 0 007 0 5 0 019 0 4 0 015 d1 Standard dimension mm inch 3...

Страница 74: ...he thin cable upward and the thick cable downward Fix the power cablewith a cable tie Solderless ring terminal Cable tie 1 Front connection 10 Installation Connecting the power terminal 2 Closing the...

Страница 75: ...he vibration of the compressor is transferred to the pipes and can damage the power supply cables or pipes creating the danger of fire or explosion Make sure that the place where the sheath of power s...

Страница 76: ...ation fix it with cable tie 3 Fix the housing which has an insulator to the terminal board Fixing the ground cable Grounding Connect the ground cable to the grounding hole inside the power supply box...

Страница 77: ...2 OF1 OF2 R1 R2 Terminal block with indoorunit Terminal block with outdoor unit sub module Terminal block with solution device A Where to install the interface module Install the interface module in l...