ENGLISH-64
Electrical wiring work
Connecting the power terminal
f
Connect the cables to the terminal board with solderless ring terminals.
f
Properly connect the cables by using certified and rated cables and make sure to fix them properly so that external force
is not applied to the terminal.
f
Use a driver and wrench that can apply the rated torque when tightening the screws on the terminal board.
f
Tighten the terminal screws by complying rated torque value. If the terminal is loose, fire can occur due to arc heat
generation and if the terminal is too tight, terminal board could get damaged.
AM038/048/055KXWD
✴
L N
MCCB+
ELB
or
ELCB
Protection tube for power cable
Conduit (field supply)
Conduit mounting plate
Lock nut (field supply)
1 phase 2 wires 208 ~ 230 V
Extermal Contact Signal
/Communication cable
between Indoor units
Extermal Power Supply
Screw
Tightening torque for terminal
Remarks
N·m
lbf·ft
M4
1.2~1.8
0.9~1.3
Communication : F1, F2
M5
2.0~3.0
1.5~2.2
1 phase AC power supply: : 1(L), 2(N), L, N
See the following figure when connecting the communication or external contact through the knock-out hole on the top left
corner of the cabinet.
(Field installation range for the power cable protection tube)