E-
16
Group control installation
K9 K10 K11 K12
K9 K10 K11 K12
The group control can control 16 rooms(64 indoor units/standard) with
a wired controller. When a whole unit is operating, each unit operates
in the same mode(such as mode settings and the fan speed, etc.).
To control each unit separately, you can control it with the centralized
controller or PC controller(S-Net) too. However, the group control and
the separate control can' t be operated at the same time.
Group Control
Connect the power cable (F1, F2 and FA, FB) between indoor units.
1
Set the optional switch(SW05).
2
Group Control Installation
◆
Set the set you want to control as Master. (Set only a set
of 16 rooms)
◆
Set the optional switch(K9) of the indoor unit to do a
group control as OFF.
◆
Set the indoor unit as Master and then set its optional
switch(K10) as OFF.
N
N
N
N
o
o
o
o
tt
tt
e
e
e
e
K9
K10
OFF
OFF
OFF
ON
Switch No.
Master Indoor Unit
Slave Indoor Unit
Indoor unit
Master
Indoor unit
Slave
Indoor Unit
Set during the
group control
Set Master indoor unit
during the group control
Function