56
Option SEG13
SEG14
SEG15
SEG16
SEG17
SEG18
3)
Explanation
PAGE
-
CO
2
SENSOR
External Damper
3&4&37&%
Control variables when using hot water / external heater
Remote
Controller
Display
Indication
and Details
Indication Details Indication Details Indication Details Indication Details
Indication
Details
2
0
Disuse
0
Disuse
Set temp. for heater On/Off
Delay time for
heater On
0
At the same time as thermo on
No delay
1
At the same time as thermo on
10 minutes
2
At the same time as thermo on
20 minutes
1
Use
1
Use
3
1.5 °C
No delay
4
1.5 °C
10 minutes
5
1.5 °C
20 minutes
6
3.0 °C
No delay
7
3.0 °C
10 minutes
8
3.0 °C
20 minutes
9
4.5 °C
No delay
A
4.5 °C
10 minutes
B
4.5 °C
20 minutes
C
6.0 °C
No delay
D
6.0 °C
10 minutes
E
6.0 °C
20 minutes
Option SEG19
SEG20
SEG21
SEG22
SEG23
SEG24
Explanation
PAGE
3&4&37&%
3&4&37&%
3&4&37&%
3&4&37&%
3&4&37&%
Remote
Controller
Display
Indication
and Details
Indication Details
3
1)
Height difference : The difference of the height between the corresponding indoor unit and the indoor unit installed at the
lowest place.
For example, When the indoor unit is installed 40m higher than the indoor unit installed at the lowest place,
select the option "1".
2)
Distance : The difference between the pipe length of the indoor unit istalled at farthest place from an outdoor unit and the pipe
length of the corresponding indoor unit from an outdoor unit.
For example, when the farthest pipe length is 100m and the corresponding indoor unit is 40m away from an outdoor
VOJUTFMFDUUIFPQUJPO N
3)
Heater operation when the SEG9 of 02 series installation option is set to using hot water heater or when SEG15 is set to using
external heater
e.g. 1)
4FUUJOHTFSJFT4&(ww4FUUJOHTFSJFT4&(iw)PUXBUFSIFBUFSJTUVSOFEPOBUUIFTBNFUJNFBTUIF
heating thermostat is on, and turned off when the heating thermostat is off.
e.g. 2)
4FUUJOHTFSJFT4&(ww4FUUJOHTFSJFT4&(w"w
Room temp. ≤ set temp. + f(heating compensation temp.)
- External heater is turned on when the temperature is maintained as 4.5 °C for 10 minutes.
Room temp. > set temp. + f(heating compensation temp.)
- External heater is turned off when the temperature is maintained as 4.5 °C + 1 °C
(1 °C is the Hysteresis for On/Off selection.)
Setting an indoor unit address and installation option