53
ENGLISH
Option SEG19
SEG20
SEG21
SEG22
SEG23
SEG24
Explanation
PAGE
3&4&37&%
Heating setting compensation / Removing
condensated water in heating mode
&&74UFQPGTUPQQFE
unit during oil
return/defrost mode
3&4&37&%
3&4&37&%
Remote
Controller
Display
Indication and
Details
Indication
Details
Indication
Details
Indication
Details
Heating Setting
Compensation
Removing
Condensated
Water in
Heating Mode
3
0
Default
4)
Disuse
0
Default
value
1
2 °C
Disuse
1
Oil return
or Noise
decreasing
in defrost
mode
2
5 °C
Disuse
3
Default
4)
Use
5
)
4
2 °C
Use
5)
5
5 °C
Use
5)
*
Advanced function: Controlling cooling/heating current or power saving with motion detect.
1)
Minimizing fan operation when thermostat is off
- Fan operates for 20 seconds at an interval of 5 minutes in heat mode.
2)
1: Fan is turned on continually when the hot water heater is turned on,
3: Fan is turned off when the hot water heater is turned on with cooling only indoor unit
Cooling only indoor unit: To use this option, install the Mode Select switch (MCM-C200) on the outdoor unit and fix it
as cool mode.
3)
When the following 2 or 3 is used as external heater On/Off signal, the signal for monitoring external contact control
will not be output.
2: Fan is turned on continually when the external heater is turned on,
3: Fan is turned off when the external heater is turned on with cooling only indoor unit
Cooling only indoor unit: To use this option, install the Mode Select switch (MCM-C200) on the outdoor unit and fix it
as cool mode.
❋
*G'BOJTTFUUPPGGGPSDPPMJOHPOMZJOEPPSVOJUCZTFUUJOHUIF4&(PS4&(ZPVOFFEUPVTFBOFYUFSOBMTFOTPS
or wired remote controller sensor to detect indoor temperature exactly.
4)
Default setting value
- 4Way Cassette, Mini 4Way Cassette: 5 °C
- Other indoor units: 2 °C
5)
This function can be applied to 4 Way Cassette and Mini 4 Way Cassette only. If the air conditioner operates the heating
mode immediately after finishing the cooling mode, the condensated water in the drain pan becomes water vapor by
the heat of the indoor unit heat exchanger. Since the water vapor might be condensed on the indoor unit, which may
fall into a living space, use this function to get rid of the water vapor out of the indoor unit by operating the fan (for
maximum 20 minutes) even when the indoor unit is turned off after cooling mode is turned to heating mode .
Air Flow
Suction side
Discharge side
Electronic heater should
not be installed.
t
Do not install the electronic heater in the flow channel of the indoor unit fan.
CAUTION
Duct Indoor unit