Refrigerant pipe installation
f
Basic amount of refrigerant within the outdoor unit (kg)
- Amount of additional refrigerant has to be calculated based on the sum of all liquid pipe length.
Classification
AM080FXVAG
✴
AM100FXVAG
✴
AM120FXVAG
✴
AM140FXVAG
✴
AM160FXVAG
✴
Basic type
5.5
5.2
5.5
7.7
7.4
Classification
AM180FXVAG
✴
AM200FXVAG
✴
AM220FXVAG
✴
AM240HXVAG
✴
AM260HXVAG
✴
Basic type
8.7
8.4
8.4
14.3
14.3
Classification
AM240MXVGNR AM260MXVGNR AM280MXVGNR AM300MXVANR
Basic type
14.0
14.0
14.0
14.0
f
Amount of additional refrigerant depending on the pipe size (
ⓐ
)
- Amount of additional refrigerant has to be calculated based on the sum of all liquid pipe length.
Size of liquid pipe
Ø 6.35
Ø 9.52
Ø 12.70
Ø 15.88
Ø 19.05
Ø 22.22
Ø 25.40
Ø 28.58
Additional amount (kg/m)
0.02
0.06
0.125
0.18
0.27
0.35
0.53
0.65
- For the indoor unit already connected to EEV kit, the additional refrigerant charging is 0.01kg per meter regardless of
the pipe size.