Samsung Electronics
4-5-4 Total current trip error
1. Checklist :
1) Is the input power voltage proper?
2) Is the refrigerant charged properly?
3) Does the compressor rotate normally?(Reverse rotation, Locking etc.)
4) Does the outdoor fan operate normally?(Fan propeller loss, Motor error ect.)
5) Is the installation condition of outdoor unit good?(Piping, Space etc.)
6) Is there no ventilation obstruction at the surrounding of outdoor unit?(Outdoor unit cover, Fan front obstruction etc.)
7) Is there no ventilation obstruction at the surrounding of indoor unit?(Overload condition in heating mode)
2. Troubleshooting procedure
No
Yes
Yes
Are the service valves full opened?
Yes
Yes
Check AC power source
No
No
Reinstall and remove the obstruction
Is the installation of outdoor unit good?
Reinstall and remove the obstruction
No
Is the installation of indoor unit good?
Exchange the compressor
No
Does the compressor rotate normally?
Open valve screw to the end.
Is AC power voltage normal during the
compressor in operation?
Exchange INVERTER PCB
Yes
4-19
DB98-29522A_USA_SM.indd 39
2008-2-29 13:18:25
Содержание DH140EAV
Страница 62: ...Samsung Electronics DH140CAV 5 3 DB98 29522A_USA_SM indd 58 2008 3 13 12 50 40...
Страница 66: ...Samsung Electronics 5 7 5 3 Assy control out UH105 140CAV DB98 29522A_USA_SM indd 62 2008 2 29 13 18 45...
Страница 68: ...Samsung Electronics 5 9 MEMO DB98 29522A_USA_SM indd 64 2008 2 29 13 19 02...
Страница 95: ...Samsung Electronics 6 27 MEMO DB98 29522A_USA_SM indd 27 2008 2 29 13 19 13...
Страница 101: ...Samsung Electronics 9 Preference Sheet 9 1 Refrigerating Cycle Diagram 9 1 DB98 29522A_USA_SM indd 2 2008 2 29 13 25 45...