(*1)

 

Height difference :   The difference of the height between the corresponding indoor uint and the indoor unit installed at the lowest place.  

For example, When the indoor unit is installed 40m higher than the indoor unit installed at the lowest place, select the 
option "1".

(*2)

 

Distance :   The difference between the pipe length of the indoor unit istalled at farthest place from an outdoor unit and the pipe length of the 

corresponding indoor unit from an outdoor unit. 
For example, when the farthest pipe length is 100 m(328 ft) and the corresponding indoor unit is 40 m away from an outdoor unit, 
select the option "2". 

(100 - 40 = 60m)

(*3)  Heater operation when the SEG9 of 02 series installation option is set to using hot water heater or when SEG15 is set to using external heater 

e.g. 1)  

 Setting 02 series SEG9 =”1” / Setting 05 series SEG18 = “0”: Hot water heater is turned on at the same time as the heating thermostat 

is on, and turned off when the heating thermostat is off. 

e.g. 2)  

 Setting 02 series SEG15 =”2” / Setting 05 series SEG18 =”A”: 

 

Room temp. ≤ set temp. + f(heating compensation temp.) 

 

 

-  External heater is turned on when the temperature is maintained as 4.5 °C for 10 minutes.  

 

Room temp. > set temp. + f(heating compensation temp.) 

 

-  External heater is turned off when the temperature is maintained as 4.5 °C + 1 °C (1 °C is the Hysteresis for On/Off selection.)

 

Option 

SEG13

SEG14

SEG15

SEG16

SEG17

SEG18

(*3)

Explanation

Control variables when using hot water / external heater 

Remote 

Controller 

Display

Indication 

and Details

Indication

Details

Set temp. for heater On/Off 

Delay time for heater On

2

0

At the same time as thermo on

No delay 

1

At the same time as thermo on

 

10 minutes 

2

At the same time as thermo on

20 minutes 

3

1.5 °C

No delay 

4

1.5 °C

10 minutes 

5

1.5 °C

20 minutes 

6

3.0 °C

No delay 

7

3.0 °C

10 minutes 

8

3.0 °C

20 minutes 

9

4.5 °C

No delay 

A

4.5 °C

10 minutes 

B

4.5 °C

20 minutes 

C

6.0 °C

No delay 

D

6.0 °C

10 minutes 

E

6.0 °C

20 minutes 

Setting an indoor unit address and installation option

DVM Big Duct_EU_IM_DB68-05047A-01_EN_16.03.30.indd   36

2016/4/7   15:54:52

Содержание Big Duct Type Series

Страница 1: ...DVM Big Duct_EU_IM_DB68 05047A 01_EN_16 03 30 indd 1 2016 4 7 15 54 17...

Страница 2: ...forwhichithasbeendesigned theindoorunitisnotsuitabletobe installedinareasusedforlaundry Donotusetheunitsifdamaged Ifproblemsoccur switchtheunitoffanddisconnectitfromthepowersupply Inordertopreventelec...

Страница 3: ...emaycorrodeandrefrigerantmayleak Theplacewherethereisamachinethatgenerateselectromagneticwaves Theairconditionermaynotoperate normallyduetocontrolsystem Theplacewherethereisadangerofexistingcombustibl...

Страница 4: ...t install the unit in such conditions first consult your dealer Avoid installing the air conditioner In areas where it is exposed to direct sunlight Close to heat sources In damp areas or locations wh...

Страница 5: ...on for PBA is applied b Height is less than 0 5m Both A B are applied c A B are inspection holes Indoor unit Space requirements for installation service Deciding on where to install the indoor unit Un...

Страница 6: ...r similar insulation to the indoor unit when installing belt or pipe type indoor unit on the ceiling A C B D Front Back Indoor Unit A B C D Front Back AM JNHF 1350 x 850 x 450 1350 x 450 1350 x 450 85...

Страница 7: ...ension position Inspection hole Suction side Discharge side No Name Description 1 Liquid pipe connection 9 52 3 8 2 Gas pipe connection 19 05 3 4 3 Drain pipe connection OD25 ID20 without drain pump 4...

Страница 8: ...re drilling the holes maintain the correct dimensions between the markings Pattern sheet is supplied depending on the model type Ensure that the ceiling is strong enough to support the weight of the i...

Страница 9: ...ns not supplied For the lines use insulated unwelded degreased and deoxidized copper pipe Cu DHP type to ISO 1337 or UNI EN 12735 1 suitable for operating pressures of at least 4200kPa and for a burst...

Страница 10: ...e must be no crack or wave on the bended area 5 It would be necessary to double the insulation thickness 10mm or more to prevent condensation even on the insulator when if the installed area is warm a...

Страница 11: ...uts first manually and then with a torque wrench applying the following torque If the pipes require brazing ensure that OFN Oxygen Free Nitrogen is flowing through the system Nitrogen blowing pressure...

Страница 12: ...No gap NBR T13 0 or thicker Insulation cover pipe Indoor unit Be sure to overlap the insulation Insulation pipe Must fit tightly against body without any gap Always make the seam of pipes face upwards...

Страница 13: ...ust be taken when installing the drain hose for the indoor unit to ensure that any condensate water is correctly drained outside The drain hose can be installed to the right of the base pan 1 Installi...

Страница 14: ...ormore Hanger Within 300 550mm Air vent 300mm or less Flexible hose Horizontal drainpipe more than 1 100 slope Ceiling 1 The drain pipe should be installed within 300mm to 550mm from the flexible hose...

Страница 15: ...t Without the drain pump 1 Install main air vent at the front of the farthest indoor unit from the main drain when installed indoor units are more than 3 2 You may need to install individual air vent...

Страница 16: ...all mounted indoor unit 220 240V or h ELCB Essential Installation WARNING Power off before connecting any wires Indoor PBA will be damaged while V1 V2 F3 F4 short each other Power and communication ca...

Страница 17: ...units T coef 1 55 T Lk Distance among each indoor unit m Ak Power cable specification mm2 ik Running current of each unit A Coef 35 6 Lk ik 10 of input voltage V 1000 Ak n k 1 Example of Installation...

Страница 18: ...sconnection from the power supply must be incorporated in the fixed wiring 3mm You must keep the cable in a protection tube Keep distances of 50mm or more between power cable and communication cable M...

Страница 19: ...Interface moduleandtheindoorunit 3 IfyouinstallaInterfacemoduletoanindoorunit everyoutdoorunitwhichis connectedtoanindoorunitcanbecontrolledsimultaneously 4 Eachindoorunitconnectedtothesamecentralized...

Страница 20: ...heceiling theholeonthewall 4 Reassembletheelectricalcomponentboxcover carefullytighteningthescrew Indoor Power supply Communication Cable Power Supply Max Min V Indoor Power cable 220 240V 50Hz 10 2 5...

Страница 21: ...n code If you input the inappropriate option code error may occur or the air conditioner is out of order The option code must be inputted correctly by the installation specialist or service agent Mode...

Страница 22: ...enu Sub menu 1 2 3 5 4 6 SEG Used 1 PresstheUserSetbutton Main Menu will be displayed and you can press the V buttons to select No 8 which will set the EasyTuning 2 Pressthe buttontoselectairflowstep...

Страница 23: ...oor unit option code is only possible in Master wired remote controller You can only check the indoor unit option code in Slave wired remote controller Setting indoor unit option code is possible when...

Страница 24: ...s the button anytime during setup to exit without setting Address will not be applied if you don t press button Setting Main RMC Address of an Indoor unit is available only with a master wired remote...

Страница 25: ...ng oil return defrost mode Motion detect sensor Option No 02XXXX 1XXXXX 2XXXXX 3XXXXX Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6 Explanation PAGE MODE Useofrobotcleaning Useofexternalroomtemperature sensor...

Страница 26: ...sated Waterin HeatingMode 3 0or1 channel1 0 Default 4 Disuse 0 Defaultvalue 0 Disuse 1 Turnoutin30min withoutmotion 2 channel2 1 2 C 3 6 F Disuse 1 OilreturnorNoisedecreasingin defrostmode 2 Turnoutin...

Страница 27: ...X X X X X 1 X X X X X SEG13 SEG14 SEG15 SEG16 SEG17 SEG18 SEG19 SEG20 SEG21 SEG22 SEG23 SEG24 2 X X X X X 3 X X X X X On SEG1 12 Off SEG13 24 The procedure of option setting Option setting is availabl...

Страница 28: ...utton to be changed to FAN mode in the ON status 7 Setting SEG9 SEG10 option Press Low Fan button to enter SEG9 value Press High Fan button to enter SEG10 value Each time you press the button will be...

Страница 29: ...press the button will be selected in rotation 14 Setting Dry mode Press Mode button to be change to Dry mode in the OFF status 15 Setting SEG18 SEG20 option Press Low Fan button to enter SEG18 value...

Страница 30: ...s 0 A 0 No Main address 0 9 100 digit 0 9 10 digit 0 9 Aunit digit 1 Main address setting mode Option SEG7 SEG8 SEG9 SEG10 SEG11 SEG12 Explanation PAGE __ SettingRMCaddress __ Groupchannel 16 Groupadd...

Страница 31: ...Off signal S Plasma ion Buzzer Number of hours using filter SEG19 SEG20 SEG21 SEG22 SEG23 SEG24 3 Individual control of a remote controller Heating setting compensation Removing condensated water in h...

Страница 32: ...nal room temperature sensor Minimizingfan operationwhen thermostatisoff 0 2 0 Disuse 0 Disuse Disuse 0 Disuse 0 Disuse 1 Use Disuse 1 RPM compensation 1 Use 2 Disuse Use 1 1 Use 2 Highceiling KIT 3 Us...

Страница 33: ...ng condensatedwaterinheatingmode EEVStepofstopped unitduringoilreturn defrostmode Motiondetectsensor Remote Controller Display Indication andDetails Indication Details Indication Details Indication De...

Страница 34: ...ntactcontrolwillnotbeoutput 2 Fanisturnedoncontinuallywhentheexternalheateristurnedon 3 Fanisturnedoffwhentheexternalheateristurnedonwithcoolingonlyindoorunit Coolingonlyindoorunit Tousethisoption ins...

Страница 35: ...C 6 4 C 7 3 5 C 7 3 5 C 7 4 5 C Option SEG7 SEG8 SEG9 SEG10 SEG11 SEG12 Explanation PAGE WhensettingSEG3 Standardformode changingCooling Heatingmode WhensettingSEG3 Timerequiredfor modechange Compens...

Страница 36: ...ermostatisoff e g 2 Setting02seriesSEG15 2 Setting05seriesSEG18 A Roomtemp settemp f heatingcompensationtemp Externalheateristurnedonwhenthetemperatureismaintainedas4 5 Cfor10minutes Roomtemp settemp...

Страница 37: ...ainedduringthetimewithSEG9 A SetwithSEG4 B SetwithSEG5 C SetwithSEG6 D SetwithSEG8 Cooling Thermo Off Heating Thermo Off Cooling Thermo On Heating Thermo On B C D Ts A c a Temp d b Standardtemp forHea...

Страница 38: ...will change Theunitdigitofan optionSEGyouwill change Changedvalue Indication 0 D 2 1 7 1 When changing a digit of an indoor unit address setting option set the SEG3 as A When changing a digit of indoo...

Страница 39: ...discharge air Providing information for user To complete the installation perform the following checks and tests to ensure that the air conditioner operates correctly Check the following Strength of t...

Страница 40: ...e Open Error of Indoor s Terminal Block X X 1 Clogging of outdoor s service valve 2 the refrigerant leakage X X Detection of the float switch X X X 1 Error of EEPROM 2 Error of Option setting 1 Error...

Страница 41: ...or Outdoor temperature sensor error Outdoor sensor error COND temperature sensor error Outdoor sensor error Inverter Emission temperature sensor error Outdoor sensor error Detection of Indoor Freezing...

Страница 42: ...oor unit protection control error Inverter OTP error Outdoor unit protection control error AC ZERO CROSSING SIGNAL OUT error Outdoor unit protection control error Compressor LOCK error Outdoor unit pr...

Страница 43: ...80 Powercable providedbyus 20 Wire tube power cable 3 Insert both sides of core wire of the power cable into the connection sleeve f f Method 1 Push the core wire into the sleeve from both sides Conne...

Страница 44: ...tape to finish Make sure that the connection parts are not exposed to outside Be sure to use insulation tape and a contraction tube made of approved reinforced insulating materials that have the same...

Страница 45: ...45 DVM Big Duct_EU_IM_DB68 05047A 01_EN_16 03 30 indd 45 2016 4 7 15 54 59...

Страница 46: ...DVM Big Duct_EU_IM_DB68 05047A 01_EN_16 03 30 indd 46 2016 4 7 15 54 59...

Страница 47: ...ossibilities Thank you for purchasing this Samsung product Big Duct Type Series AM JNHFKH Air Conditioner installation manual DB68 05047A 01 DVM Big Duct_EU_IM_DB68 05047A 01_EN_16 03 30 indd 47 2016...

Отзывы: