12-3 PCB Inspection Method
12-3-1 Pre-inspection Notices
1. Check if you pulled out the AC power plug when you eliminate the PCB or front panel.
2. Don't hold the PCB side not impose excessive force on it to eliminate the PCB.
3. Don't pull the lead wire but hold the whole housing to connect or disconnect a connector to the PCB.
4. In case of outdoor PCB disassembly, check first the complete discharge of condenser(C101) after 30 seconds power off.
12-3-2 Inspection Procedure
1. Check connector connection and peeling of PCB or bronze coating pattern when you think the PCB is broken.
2. The PCB is composed of the 3 parts.
1.
●
Indoor Main PCB Part
: MICOM and surrounding circuit, relay, room fan motor driving circuit and control circuit, sensor
driving circuit, power circuit of DC12V and DC5V, and buzzer driving circuit.
1.
●
Display part
: LED lamp, Switch, Remocon module
1.
●
Outdoor Main PCB part
: MICOM and surrounding circuit. IPM and PFC circuit and control circuit.
1.
●
EMI PCB Part
: Line filter and Noise Capacitor, Varistor
12-3-3 Detailed Inspection Procedure
Plug out and pull the PCB
out of the electronic box.
Check the PCB fuse.
Supply power.
If the operating lamp
twinkles at this time,
the above 1)~3) have
no relation.
Press the ON/OFF button.
Press the ON/OFF button.
1. FAN Speed [High]
2. Continuous Operation
1) Is the fuse disconnected?(F701)
Checking the power voltage.
1) Is the DB71input voltage AC200V~AC240V?
2) Is the voltage between both terminals of the
C103 on the 2
nd
side of the transformer DC12V
±0.5V?
3) Is the voltage between both terminals of OUT
and GND of IC02(KA78L05) DC5V ±0.5V?
Checking the power voltage.
1) Check the voltage of the relay(RY71) coil(IC05
PIN #13 and GND : 0V, PIN #4 and GND : 5V)
during operation.
2) Check the voltage of both terminals of
terminal block 1 and N(1) after 3 minute
operation.: AC220V
1) Is the voltage over AC180V being imposed on
terminal #3 and #5 of the fan motor
connector(CN72)?
2) The fan motor of the indoor unit doesn't run.
3) The power voltage between terminal #3 and #5
of the connector(CN72) is 0V.
• Overcurrent
• Indoor Fan Motor Short
• AC Part Pattern Short of the MAIN PCB
• Power Cord is fault, Fuse open. Wrong
Power Cable Wiring, AC Part is faulty.
• Switching Trans or Power Circuit is faulty
• Power Circuit is faulty, Load Short
• Relay(RY71) Coil Disconnection, IC05 is
faulty
• Relay(RY71) Contact is faulty
• Fan Motor of the indoor is faulty
• Fan Motor Connector(CN72) is faulty
• ASS'Y Main PCB is faulty
• Connection is faulty
No
Procedure
Inspection Method
Cause
1
2
3
4
24437A(1)_1 1/16/05 9:58 PM Page 12-20
Содержание AS09BPA
Страница 30: ...MEMO Samsung Electronics 5 4 ...
Страница 34: ...MEMO Samsung Electronics 5 8 ...
Страница 35: ...Samsung Electronics 5 9 5 4 Ass y Control Out AS09BPAX DB93 03450B AS12BPAX DB93 03450A ...
Страница 46: ...Samsung Electronics 7 2 This Document can not be used without Samsung s authorization 7 2 Outdoor Unit ...
Страница 48: ...Samsung Electronics 8 2 8 2 Outdoor Unit This Document can not be used without Samsung s authorization ...
Страница 80: ...MEMO 12 23 Samsung Electronics ...
Страница 82: ...13 2 Samsung Electronics Block Diagram INDOOR FAN CONTROL SMPS AC COMMUNICATION SUB PCB BUZZER CONTROL ...
Страница 84: ...Block Diagram 13 4 Samsung Electronics DC_LINK CAP B D DIODE IPM OUTDOOR FAN SMPS IGBT ...
Страница 95: ...MEMO Samsung Electronics 14 11 ...