4-5 Setting to Cool or Heat only mode, checking and Cool/Heat modes operation test
Setting the outdoor option
•
Press and hold K2 to enter the option setting. (Only available when the operation is stopped)
- If you enter the option setting, display will show the following.
- Seg 1 and Seg 2 will display the number for selected option.
- Seg 3 and Seg 4 will display the number for set value of the selected option.
• Edited option will not be saved if you do not end the option setting as explained in above instruction.
※ While you are setting the option, you may press and hold the K1 button to reset the value to previous setting.
※ If you want to restore the setting to factory default, press and hold the K4 button while you are in the option
setting mode.
– If you press and hold the K4 button, setting will be restored to factory default but it doesn't mean that restored
setting is saved. Press and hold the K2 button. When the segments shows that tracking mode is in progress,
setting will be saved.
CAUTION
•
If you have selected desired option, you can shortly press the K1 switch to adjust the value of the Seg 1, Seg 2 and change the
function for the selected option.
Example)
•
If you have selected desired option, you can shortly press the K2 switch to adjust the value of the Seg 3, Seg 4 and change the
function for the selected option.
Example)
•
After selecting the function for options, press and hold the K2 switch for 2 seconds. Edited value of the option will be saved
when entire segments blinks and tracking mode begins.
Option item
Input unit
SEG1
SEG2
SEG3
SEG4
Function
Setting to Cool or Heat
only mode
Main
0
0
0
0
Cooling and Heating (Factory default)"
0
1
Only Cooling
0
2
Only Heating
Unused option
Main
0
1
0
0
Unused option
0
1
Unused option
Mixed mode indoor
input
Main
0
2
0
0
Disabled (Factory default)
0
1
Enabled
Auto Change Over
Main
0
3
0
0
Disabled (Factory default)
0
1
Enabled (Factory default)
Channel address
Main
0
4
A
U
Automatic setting (Factory default)
00 ~ 15
Manual setting
• Edited option will not be saved if you do not end the option setting as explained in above instruction.
※ While you are setting the option, you may press and hold the K1 button to reset the value to previous setting.
※ If you want to restore the setting to factory default, press and hold the K4 button while you are in the option
setting mode.
‐ If you press and hold the K4 button, setting will be restored to factory default but it doesn't mean that restored
setting is saved. Press and hold the K2 button. When the segments shows that tracking mode is in progress,
setting will be saved.
CAUTION
Содержание AR07TSFABWKN
Страница 101: ...PCB Diagram Samsung Electronics 5 9 Duct S This Document can not be used without Samsung s authorization ...
Страница 113: ...6 2 Samsung Electronics This Document can not be used without Samsung s authorization Home Duct ...
Страница 114: ...Samsung Electronics 6 3 Duct S ...
Страница 115: ...6 4 Samsung Electronics This Document can not be used without Samsung s authorization Console ...
Страница 118: ...Samsung Electronics 6 7 AJ020BXS3CH AJ BX 4CH AJ BX 5CH This Document can not be used without Samsung s authorization ...