7-4 Refrigerant Adjustment
7-5 Flare Nut Fixing Torque
Model Name
Class
At installation
At service
Total Connecting
Pipe Length (LT)
Air-Purge Method
Refrigerant
Adjustment
Air-Purge Method
Refrigerant Quantity
AJ020BXJ2CH
LT≤30m
Refer to the detailed
Connecting up and
purging the circuit.
(8-2 page)
Unnecessary
Purge air using a
vacuum pump
or an additional
refrigerant cylinder.
Refer to specification sheet
30m≤LT≤50m
Add 10g of refrigerant
(R-410A) for every 1m
Add 10g of refrigerant
(R-410A) for every 1m
AJ020BXS3CH
LT≤40m
Unnecessary
Refer to specification sheet
40m≤LT≤50m
Add 20g of refrigerant
(R-410A) for every 1m
Add 20g of refrigerant
(R-410A) for every 1m
AJ024BXJ3CH
LT≤40m
Unnecessary
Refer to specification sheet
40m≤LT≤70m
Add 10g of refrigerant
(R-410A) for every 1m
Add 10g of refrigerant
(R-410A) for every 1m
AJ024BXS4CH
AJ030BSX4CH
AJ036BXJ4CH
LT≤40m
Unnecessary
Refer to specification sheet
40m≤LT≤70m
Add 20g of refrigerant
(R-410A) for every 1m
Add 20g of refrigerant
(R-410A) for every 1m
AJ036BXS4CH
LT≤50m
Unnecessary
Refer to specification sheet
50m≤LT≤70m
Add 20g of refrigerant
(R-410A) for every 1m
Add 20g of refrigerant
(R-410A) for every 1m
AJ048BXJ5CH
LT≤50m
Unnecessary
Refer to specification sheet
50m≤LT≤70m
Add 10g of refrigerant
(R-410A) for every 1m
Add 10g of refrigerant
(R-410A) for every 1m
It would be the best choice to use the standard tube length to keep the basic quality of Room Air conditioner, for ex
-
ample cooling and heating capacity, sound level, vibration level, and reliability.
But, according to a certain different installation condition, the connection tube length could be changed in the recom
-
mendation length that is shown above.
In this case, installer should keep the installation condition to keep the quality of Room Air conditioner.
▪
Refrigerant should be charged additionally as written above according to the change of the length of the connection
tube. It needs to affect the decrease in cooling and heating capacity or of the reliability of compressor that may be
caused by a lack of refrigerant.
▪
Installation position difference between the indoor unit and the outdoor unit should not exceed over than 15 meters.
▪
When the connection pipe is been extended longer than 5 meters, it might need to change the diameter of the elec
-
trical wire to a larger size in order to keep a voltage drop for starting room air conditioner is not less than 85% of the
rated voltage.And then, a voltage meter will be useful to check the rate of the voltage drop.
Outer diameter (mm)
Tightening torque
Body cap (N · m)
Charging port cap (N · m)
ø 6.35
20 to 25
10 to 12
ø 9.52
20 to 25
ø 12.70
25 to 30
ø 15.88
30 to 35
Содержание AR07TSFABWKN
Страница 101: ...PCB Diagram Samsung Electronics 5 9 Duct S This Document can not be used without Samsung s authorization ...
Страница 113: ...6 2 Samsung Electronics This Document can not be used without Samsung s authorization Home Duct ...
Страница 114: ...Samsung Electronics 6 3 Duct S ...
Страница 115: ...6 4 Samsung Electronics This Document can not be used without Samsung s authorization Console ...
Страница 118: ...Samsung Electronics 6 7 AJ020BXS3CH AJ BX 4CH AJ BX 5CH This Document can not be used without Samsung s authorization ...