Fixing the installation plate
2. Fix the indoor unit.
If you fix the indoor unit on a wall
(1) Fix the installation plate to the wall giving attention to the weight of the indoor unit.
If you fix the indoor unit on a window frame
(1) Determine the positions of the wooden uprights to be
attached to the window frame.
(2) Attach the wooden uprights to the window frame giving
attention to the weight of the indoor unit.
(3) Attach the installation plate to the wooden upright using
tapping screws.
If you fix the indoor unit on a gypsum board
(1) Use stud finder to find out locations of the studs.
(2) Fix the plate hanger on two studs.
• If you mount the plate to a concrete wall using plastic anchors, make sure that
gaps between the wall and the plate, created by projected anchor, is less than
20mm.
• Search for other spots if there are less than two studs, or the distance between the studs are different from the
plate hanger.
• Fix the installation plate without inclining to one side.
1. Extend the assembly cable if necessary.
• Do not connect two or more different cables to extend the length.
It may cause fire.
• Make sure that a wall can withstand the weight of the product. If you install the product in a place where it is not
strong enough to withstand the product weight, the unit could fall and cause injury.
Connecting the assembly cable
When you install the unit, make first refrigerant connections and then electrical connections.
Connect the air conditioner to grounding system before performing the electrical connection.
If unit is uninstalled, first disconnect electrical cables, then refrigerant connections.
If the outdoor unit is more than 5 meters away from the indoor unit, you must extend the cable.
The maximum length of the cable is 15(
09/12
)/20(
18/24
) meters.
• Connect the power cable to the auxiliary circuit breaker. If every pole fails to connect to
the power supply, it must be incorporated in a wire with a contact opening of ≥3mm.
Model
Power cable
Interconnection cable
Type GL
09/12
3G, 1.0mm
² H07RN-F
5G, 1.0mm
² H07RN-F
20A
18
3G, 1.5mm
² H07RN-F
2G, 0.75mm
² H05RN-F
3G, 1.5mm
² H07RN-F
25A
24
3G, 2.5mm
² H07RN-F
3G, 2.5mm
² H07RN-F
2G, 0.75mm
² H05RN-F
Cable specification
Connecting the cable