2-2
Samsung Electronics
2-2 Product Specifications
Power Source
220 - 240 V~, 50 / 60 Hz
Ventilation Mode
Heat-Ex Ventilation
By-Pass Ventilation
The Level of the Air Volume
Turbo
High
Low
Turbo
High
Low
Power Supply(W)
115
80
45
115
80
45
Air Volume(m³/h)
260
250
180
250
250
180
External Static Pressure(Pa)
100
65
55
110
65
55
Temperature Exchange
Efficiency(%)
Cooling
70
70
74
-
-
-
Heating
70
70
74
-
-
-
Enthalpy Exchange
Efficiency(%)
Cooling
50
50
55
-
-
-
Heating
70
70
76
-
-
-
Size(widthxheightxdepth)(mm)
600 x 350 x 660
Weight(kg)
28.5
Duct Size(mm)
150
Trial Operation Conditions
1. Air Volume/ External Static Pressure, Comply with KS Heat Exhaust Ventilation System Standards(KS B6879).
2. Heat Exchange/Temperature Exchange Efficiency, Comply with regulations to pro-
mote high efficiency energy devices,
[Cooling], Indoor(24˚C DB/17˚C WB), Outdoor(35˚C DB/24˚C WB)
[Heating], Indoor(22˚C DB/13.9˚C WB), Outdoor(2˚C DB/0.44˚C WB)
Q
AN026JSKLKN
Power Source
220 - 240 V~, 50 / 60 Hz
Ventilation Mode
Heat-Ex Ventilation
By-Pass Ventilation
The Level of the Air Volume
Turbo
High
Low
Turbo
High
Low
Power Supply(W)
115
80
50
115
80
50
Air Volume(m³/h)
350
350
260
350
350
260
External Static Pressure(Pa)
155
100
85
155
100
85
Temperature Exchange
Efficiency(%)
Cooling
70
70
74
-
-
-
Heating
70
70
74
-
-
-
Enthalpy Exchange
Efficiency(%)
Cooling
50
50
55
-
-
-
Heating
70
70
76
-
-
-
Size(widthxheightxdepth)(mm)
1,012 X 270 X 1,000
Weight(kg)
42.5
Duct Size(mm)
200
Trial Operation Conditions
1. Air Volume/ External Static Pressure, Comply with KS Heat Exhaust Ventilation System Standards(KS B6879).
2. Heat Exchange/Temperature Exchange Efficiency, Comply with regulations to pro-
mote high efficiency energy devices,
[Cooling], Indoor(24˚C DB/17˚C WB), Outdoor(35˚C DB/24˚C WB)
[Heating], Indoor(22˚C DB/13.9˚C WB), Outdoor(2˚C DB/0.44˚C WB)
Q