14
Drain pipe and Drain hose Installation
Care must be taken when installing the drain hose for the indoor unit to ensure that
any condensate
water is correctly drained outside. The drain hose can be installed to the right or left
side of the base pan.
1
Unscrew the 4 tapped screws to remove the cover of the drain hose
connection port.
2
Insert the flexible hose to the drain hose port.
3
Install the drain hose so that its length can be as short as possible.
Internal diameter of the drain hose should be the same or slightly bigger
than the external diameter of the drain hose port.
4
Wrap the drain hose with the insulation drain as shown in figure and
secure it.
Fix the flexible hose to the indoor unit with the supplied
cable clamp securely.
(Use the screwdriver to fix the flexible hose securely.)
Note
Inner diameter of the drain hose
Give a slightly slant to the drain hose for proper drainage
of condensate.
Fix the flexible hose to the PVC with the supplied cable tie
securely.
Note
Flexible hose
Insulation
Cable-tie
Clamp hose
Drain hose connection port
Cable
Clamp
No gap
Indoor
Unit
32mm(Inner diameter)
Must fit tightly against body
without any gap.
NASA_Big Duct_AM@@@FNHDEH@_IM_EN_03653A-06.indd 14
2016-12-01 오후 3:06:53