41
EN
G
LIS
H
X
X
K13, K14: Changing current limit option table
Switch
Function
K13
K14
3 ton
4 ton
5 ton
ON
ON
Default
Default
Default
ON
OFF
Maximum current - 4(A)
Maximum current - 2(A)
Maximum current - 2(A)
OFF
ON
Maximum current - 6(A)
Maximum current - 4(A)
Maximum current - 4(A)
OFF
OFF
Maximum current - 8(A)
Maximum current - 6(A)
Maximum current - 6(A)
Classification
Model
Maximum current
3Ton
AM036FXMDCH
✴
22A
4Ton
AM048FXMDCH
✴
24A
5Ton
AM053FXMDCH
✴
32A
X
X
K15, K16: Changing defrost option table
Switch
Function
K15
K16
ON
ON
MID
ON
OFF
MID
OFF
ON
LOW1
OFF
OFF
LOW2
❋
❋
Defrost mode will start when the temperature difference between outdoor and outdoor heat exchanger has become
more than certain standard .
❋
❋
Factory default status is MID . When the function changes to LOW with option control, defrost entering temperature
decreases . When defrost entering temperature decreases, the operation hour will be long but this means that the
operation hour with the reduced heating capacity increases . This option is used at places where humidity is high and the
defrost mode enters too frequently .
❋
❋
Maintaining factory default status is recommended .
AM0@@FXMDCH_IM_EN_03408A(1).indd 41
2013-03-04 오후 4:28:27