• You must install an earth leakage breaker .
- ELCB(Earth Leakage Circuit Breaker)
- MCCB(Molded Case Circuit Breaker)
- ELB(Earth Leakage fuse breaker)
• Manufacturers are not responsible for fire caused by not installing ELCB or MCCB .
• Install the cabinet panel near the outdoor unit for service convenience and emergency operation switch off .
• You must install a circuit breaker that can prevent excess current and shut off the electric leakage on the outdoor
unit .
CAUTION
Specification for circuit breaker and power supply cord
X
X
Power supply cord is not supplied with air conditioner .
X
X
Select the power supply cord in accordance with relevant local and national regulations .
X
X
Wire size must comply with the applicable local and national code .
X
X
The appliance shall be provided with a certified power supply cord and interconnection cord complying with the national
regulations of the countries in which the appliance is to be sold .
Model
Power source
RLA
FLA
MCA
MOP
FAN1
FAN2
AM036FXMDCH
✴
208~230V~, 60Hz
16 .9
0 .6
0 .6
23
40
AM048FXMDCH
✴
22 .1
0 .6
0 .6
29
50
AM053FXMDCH
✴
26 .0
0 .6
0 .6
34
55
1) RLA is based on AHRI 210/240 colling standard condition [Indoor temp . :
26 .7°C/80°F(DB) / 19 .46°C/67°F(WB), Outdoor temp . : 35°C/95°F(DB)]
2) Voltage tolerance is ± 10% .
3) Maxium allowable voltage between phases is 2% .
Symbols
• RLA : Rated Load Ampere
• FLA : Full Load Ampere
• MCA : Minumum Circuit Ampere (A)
• MOP : Maximum Overcurrent Protective Device (A)
NOTE
Tightening power terminal
X
X
Connect the cables to the terminal board using the compressed ring terminal .
X
X
Use rated cables only .
X
X
Connect the cables with driver and wrench that can apply the rated torque to the screws .
X
X
Make sure that appropriate tightening torque is applied for cable connection . If the terminal is loose, arc heat may occur
and cause fire and if the terminal is connected too firmly, terminal may get damaged .
Tightening torque
M4
12 .0~15 .0 kgf•cm
1 .2~1 .5 N•m
Communication : F1, F2
M5
20 .0~25 .0 kgf•cm
2 .0~2 .5 N•m
1 phase AC power : L1, L2