E-
18
Wiring Work
Silver solder
N
L
N
L
N
L
N
L
Indoor Unit 1
Outdoor Unit
Indoor Unit 2
Indoor Unit 3
Wired Remote
Control
208-230V~
h
ELB : Essential Installation
EEV kit
Indoor Unit 4 Indoor Unit 5 Indoor Unit 6
h
Ceiling, wall-mounted indoor unit.
Selecting compressed ring terminal
1
Before wiring work, you must turn off all power source.
2
Indoor unit power should be supplied through the breaker(MCCB, ELB) separated by the outdoor power.
3
The power cable should be used only copper wires.
4
Connect the power cable{1(L), 2(N)} among the units within maximum length and communication cable(F1, F2) each.
5
Connect F3, F4(for communication) when installing the wired remote Control.
Power and communication cable connection
Norminal dimensions for cable [mm
2
(inch
2
)]
1.5 (0.002)
2.5 (0.003)
4 (0.006)
Norminal dimensions for screw [mm(inch)]
4 (0.15")
4 (0.15")
4 (0.15")
4 (0.15")
4 (0.15")
B
Standard dimension [mm(inch)]
6.6 (0.25")
8.0 (0.31")
6.6 (0.25")
8.5 (0.33")
9.5 (0.37")
Allowance [mm(inch)]
±0.2 (±0.007")
±0.2 (±0.007")
±0.2 (±0.007")
D
Standard dimension [mm(inch)]
3.4 (0.13")
4.2 (0.16")
5.6 (0.22")
Allowance [mm(inch)]
+0.3 (+0.011")
-0.2 (-0.007")
+0.3 (+0.011")
-0.2 (-0.007")
+0.3 (+0.011")
-0.2 (-0.007")
d1
Standard dimension [mm(inch)]
1.7 (0.06")
2.3 (0.09")
3.4 (0.13")
Allowance [mm(inch)]
±0.2 (±0.007")
±0.2 (±0.007")
±0.2 (±0.007")
E
Min. [mm(inch)]
4.1 (3/16")
6 (1/4")
6 (1/4")
F
Min. [mm(inch)]
6 (1/4")
6 (1/4")
6 (1/4")
L
Max. [mm(inch)]
16 (5/8")
17.5 (3/4")
20 (3/4")
d2
Standard dimension [mm(inch)]
4.3 (0.16")
4.3 (0.16")
4.3 (0.16")
Allowance [mm(inch)]
+0.2 (+0.007")
0 (0")
+0.2 (+0.007")
0 (0")
+0.2 (+0.007")
0 (0")
t
Min. [mm(inch)]
0.7 (0.02")
0.8 (0.03")
0.9 (0.035")