
88
Setting outdoor unit option switch and key function
K1
K2
K3
K4
(A Type)
(B Type)
K4 (Number of
press)
KEY operation
Display on segment
SEG 1
SEG2, 3, 4
1 time
Outdoor unit model
1
AM160MXVAFC
Off, 1, 6
2 times
Order frequency (Compressor 1)
2
120 Hz
1, 2, 0
3 times
Order frequency (Compressor 2)
3
120 Hz
1, 2, 0
4 times
High pressure (MPa)
4
1 .52 MPa
1, 5, 2
5 times
Low pressure (MPa)
5
0 .43 MPa
0, 4, 3
6 times
Discharge temperature (Compressor 1)
6
87 °C
0, 8, 7
7 times
Discharge temperature (Compressor 2)
7
87 °C
0, 8, 7
8 times
IPM temperature (Compressor 1)
8
87 °C
0, 8, 7
9 times
IPM temperature (Compressor 2)
9
87 °C
0, 8, 7
10 times
CT sensor value (Compressor 1)
A
2 A
0, 2, 0
11 times
CT sensor value (Compressor 2)
B
2 A
0, 2, 0
12 times
Suction temperature
C
-42 °C
-, 4, 2
13 times
COND OUT temperautre
D
-42 °C
-, 4, 2
14 times
Temperature of liquid pipe
E
-42 °C
-, 4, 2
15 times
TOP temperature (Compressor 1)
F
-42 °C
-, 4, 2
16 times
TOP temperature (Compressor 2)
G
-42 °C
-, 4, 2
17 times
Outdoor temperature
H
-42 °C
-, 4, 2
18 times
EVI inlet temperature
I
-42 °C
-, 4, 2
19 times
EVI outlet temperature
J
-42 °C
-, 4, 2
20 times
Unused
K
Unused
21 times
Unused
L
Unused
22 times
EVI EEV step
M
300 steps
3, 0, 0
23 times
Unused
N
Unused
24 times
Fan step (SSR or BLDC)
O
13 steps
0, 1, 3
25 times
Current frequency (Compressor 1)
P
120 Hz
1,2,0
26 times
Current frequency (Compressor 2)
Q
120 Hz
1,2,0
27 times
Suction 2 temperature (H/R)
R
-42 °C
-, 4, 2
28 times
Master indoor unit address
S
Master indoor unit not selected
BLANK, N, D
If indoor unit No .1 is selected as the master unit
0,
0, 1
29 times
Snow sensor voltage
T
1 .80V
1,8,0