48
English
Ins
tallation par
t
Installation Procedure
Option
SEG7
SEG8
SEG9
SEG10
SEG11
SEG12
Explanation
PAGE
(When setting SEG3)
Standard for mode
changing Cooling
→
Heating mode
(When setting SEG3)
Time required for mode
change
Compensation option for Long
pipe or height diffference
between indoor units
MTFC
Indication
and Details
Indication Details Indication
Details
Indication
Details
Indication
Details
Indication Details
1
0
1
0
5 min.
0
Use default value
0
Disuse
1
1.5
1
7 min.
1
1) Height
difference1) is more
than 30m or 2)
Distance
2)
is longer
than 110m
1
Use (1 sec)
2
2
2
9 min.
2
Use (2 sec)
3
2.5
3
11 min.
3
Use (3 sec)
4
Use (4 sec)
5
Use (5 sec)
4
3
4
13 min.
2
1) Height
difference1)
is 15~30m or
2) Distance
2)
is
50~110m
6
Use (6 sec)
5
3.5
5
15 min.
7
Use (7 sec)
6
4
6
7
20 min.
8
Use (8 sec)
7
4.5
30 min.
9
Use (9 sec)
A
Use (10 sec)
B
C
D
E
F
Option
SEG13
SEG14
SEG15
SEG16
SEG17
SEG18
Explanation
Set to variable breeze
Control variables when using hot water /
external heater
Indication
and Details
Indication
Details
Indication
Details
Set temp. for
heater On/Off
Delay time for
heater On
2
0
0
0
At the same time
as thermo on
No delay
1
1
1
At the same time
as thermo on
10 minutes
2
2
2
At the same time
as thermo on
20 minutes
3
3
3
1.5 °C
No delay
4
4
4
1.5 °C
10 minutes
5
5
5
1.5 °C
20 minutes
6
6
6
3.0 °C
No delay
7
7
7
3.0 °C
10 minutes
8
8
8
3.0 °C
20 minutes
9
9
9
4.5 °C
No delay
A
10
A
4.5 °C
10 minutes
B
11
B
4.5 °C
20 minutes
C
12
C
6.0 °C
No delay
D
13
D
6.0 °C
10 minutes
E
14
E
6.0 °C
20 minutes
F
Unavailable
DVM_BORACAY_IB_DB68-06415A-00_EN.indb 48
2016-08-31 오후 2:13:31