Refrigerant pipe installation
Insulating the header joint
X
X
Fasten the header joint using a cable tie and cover the connected part .
X
X
Insulate the header joint and the brazing part and wrap the connected part with an
adhesive insulation tape to prevent dew formation .
Insulation
Adhesive insulation
tape
Insulation for the
refrigerant pipe
Insulation for the
header joint
Insulation after brazing a stopper
Adhesive insulation tape
X
X
Fix the header joint with a hanger after insulating it .
Insulating the Y-join, liquid & gas side connecting pipe
X
X
Attach the insulation provided with the Y-joint to the insulation purchased privately without a gap . Wrap the connected
part with insulation (Purchased privately) of a thickness of at least 10mm (3/8”) .
X
X
Use insulation that should be able to handle an interior temperature of over 120°C(248°F) . Wrap the Y- joint with
insulation of a thickness of at least 10mm (3/8”) .
Fix securely without any gap .
Provided
insulation
Fix securely
without any gap .
Pipe insulation
(Purchased privately)
Pipe insulation
(Purchased privately)
150mm
(5 .90”)
Y-joint
Thickness of the insulation (Purchased privately)
should be at least thicker than 10mm (3/8”) .
Insulation tape
(Purchased privately)
Pipe insulation
(Purchased privately)
Pipe
❋
❋
Attach the adhesive insulation
tape to the pipe as shown in the
picture after insulating the pipe .