11. AHRI Data
Model
Rated Capacity
(Btu/h)
EER
(Btu/h)
IEER
(Btu/h)
High COP(47F)
(W/W)
Low COP(17F)
(W/W)
SCHE
(Btu/h /W)
Cooling
Heating
Non-
Ducted Ducted
Non-
Ducted Ducted
Non-
Ducted Ducted
Non-
Ducted Ducted
Non-
Ducted Ducted
AM072BXVG**
69,000
77,000
13.55
11.50
34.60
24.20
4.11
3.80
2.68
2.55
28.60
26.40
AM096BXVG**
92,000
103,000
13.70
12.40
35.00
25.10
4.20
3.83
2.91
2.73
32.10
27.20
AM120BXVG**
114,000
129,000
12.90
12.00
31.85
24.60
4.13
3.80
2.79
2.80
31.10
26.50
AM144BXVG**
138,000
154,000
12.00
12.10
29.30
25.70
3.85
3.68
2.67
2.70
27.80
26.00
AM168BXVG**
160,000
180,000
11.20
11.10
28.80
24.83
3.60
3.65
2.45
2.55
27.30
25.50
AM192BXVG**
184,000
206,000
11.90
11.80
25.90
26.00
3.61
3.55
2.48
2.65
27.00
25.30
AM216BXVG**
206,000
232,000
11.20
10.90
24.80
23.70
3.53
3.45
2.31
2.60
26.40
23.90
AM240BXVG**
228,000
258,000
10.60
10.60
22.60
23.30
3.35
3.25
2.12
2.45
26.40
23.70
AM264BXVG**
252,000
282,000
11.80
11.50
26.30
21.50
3.61
3.55
2.52
2.40
25.70
24.80
AM288BXVG**
274,000
308,000
11.90
11.40
25.90
22.50
3.60
3.50
2.50
2.40
24.50
23.70
AM312BXVG**
298,000
334,000
11.10
11.10
24.30
21.70
3.60
3.45
2.50
2.35
24.40
21.20
AM336BXVG**
320,000
360,000
10.80
10.90
23.70
21.50
3.52
3.40
2.40
2.30
23.60
20.70
AM360BXVG**
342,000
386,000
10.50
10.40
23.50
21.30
3.52
3.40
2.35
2.30
23.40
20.40
AM384BXVG**
366,000
412,000
10.70
10.50
21.80
21.00
3.42
3.30
2.45
2.35
23.20
19.70
AM408BXVG**
388,000
438,000
10.00
9.80
21.60
20.50
3.35
3.30
2.45
2.35
22.40
19.20
AM432BXVG**
412,000
462,000
9.60
9.60
21.00
20.00
3.30
3.25
2.45
2.35
22.40
19.60
AM456BXVG**
436,000
488,000
9.50
9.50
20.00
19.80
3.20
3.20
2.35
2.25
22.30
19.50
AM480BXVG**
458,000
514,000
9.50
9.50
19.10
19.60
3.20
3.20
2.25
2.20
22.20
19.50